Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
MEC19-01224 Final3/26/20193/29/20193/29/2019 4:01:24 PMPPASS
INSTALLER JAROD ###-#### Phone #: ###-#### Inspection requested via web by Aaron Alandt- furnace a/c coil co ok- 5lb flue test pass
MEC19-01235 Final3/29/20193/29/20193/29/2019 3:34:30 PMPPASS
Phone #: ###-#### Inspection requested via web by Mary LaFayette- furnace a/c coil co ok
MEC19-01068 Rough-in3/28/20193/29/20193/29/2019 3:05:23 PMPCANC
Phone #: ###-#### Inspection requested via web by Gary Reeves- fresh concrete pour in garage no access to furnace or man j- outside air in garage needs insulated to R-8- reschedule when access is ok
MEC19-01068 Pressure Test3/28/20193/29/20193/29/2019 3:03:42 PMPCANC
Phone #: ###-#### Inspection requested via web by Gary Reeves- fres concrete pour in garage- no access
MEC19-01185 Final3/26/20193/29/20193/29/2019 2:28:05 PMPPASS
Field super: Chard Robertson Phone #: ###-#### Inspection requested via web by Lisa Whitney- furnace only co ok
MEC19-01261 Final3/28/20193/29/20193/29/2019 2:04:46 PMPPASS
Please call Dave on your way - ###-#### Phone #: ###-#### Inspection requested via web by Arielle Hendricks- a/c coil co ok
MEC18-05917 Rough-in3/29/20193/29/20193/29/2019 1:31:49 PMPPART
Dru Phone #: ###-####- area E NW corner seal on all duct ok- ok to insulate- fire damper framing fail- went over condensate drain- Dru knows about fire damper framing issues- recall in when fixed
MEC19-01134 Rough-in3/28/20193/29/20193/29/2019 11:12:35 AMAFAIL
Phone #: ###-#### Inspection requested via web by Randy Hart-
1- fireplace instructions on inside of glass need to be readily accessible
2- all supply and R/A registers need to be sealed with mastic
3- need ladder provided by contractor to access furnace/coil in attic
4- all exhaust fan connections need sealed where metal duct ties on to plastic fan housing under flex
5- ducting pinched off in attic above master bath needs to flow smoothly on 2 supply runs
6- need nail plate flor and ceiling both sides of framing on condensate drain 2nd floor and ceiling 1st floor
7- range ducting needs tape sealed to pipe has gaps
8- gas test fail at 14psi
9- b vent in garage between joists needs 1" clearance

left correction notice front living room window on inside
MEC19-01134 Pressure Test3/28/20193/29/20193/29/2019 11:06:08 AMAFAIL
Phone #: ###-#### Inspection requested via web by Randy Hart- gauge at 14psi
MEC19-01213 Final3/28/20193/29/20193/29/2019 10:01:06 AMAPASS
Final inspection needed for AM Friday for Audio Chiropractic if you have questions call Karl at ###-#### thank you. Phone #: ###-#### Inspection requested via web by Karl Hestekin- final ok- card signed
MEC19-01213 Rough-in3/29/20193/29/20193/29/2019 9:51:57 AMAPASS
Final inspection needed for AM Friday for Audio Chiropractic if you have questions call Karl at ###-#### thank you. Phone #: ###-#### Inspection requested via web by Karl Hestekin- R/I ok- relocated registers in new ceiling per print- ok for ceiling tiles
MEC19-01232 Rough-in3/28/20193/29/20193/29/2019 9:09:12 AMAPASS
Phone #: ###-#### Inspection requested via web by Dan Otero- fireplace R/I ok
MEC19-01124 Rough-in3/28/20193/29/20193/29/2019 8:43:04 AMAPASS
Phone #: ###-#### Inspection requested via web by Dan Otero- fireplace R/I ok