Inspections for the day of: Monday, April 29, 2019.
Number of inspections: 19
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBrian Scoles
TitleMEC INSPECTOR
Phone #914-4915
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
MEC19-01680 Final4/26/20194/29/20194/29/2019 4:10:06 PMPPASS
Contact - Mike @ ###-#### Phone #: ###-#### Inspection requested via web by Dianne Maxwell- rtu final ok
MEC19-01037 Final4/29/20194/29/20194/29/2019 3:32:30 PMPPASS
final ok- card signed
MEC19-01683 Final4/29/20194/29/20194/29/2019 3:31:45 PMPPASS
Phone #: ###-#### Inspection requested via web by George Masing- unit heater final ok
MEC19-01509 Rough-in4/29/20194/29/20194/29/2019 2:51:23 PMPPASS
Phone #: ###-#### Inspection requested via web by Debbie Marino- fireplace and hvac R/I ok
MEC19-01509 Pressure Test4/29/20194/29/20194/29/2019 2:50:38 PMPPASS
Phone #: ###-#### Inspection requested via web by Debbie Marino- 20lb gas pass- 5lb flue pass
MEC19-01702 Final4/25/20194/29/20194/29/2019 2:20:17 PMPPASS
INSTALLER JAROD ###-#### Phone #: ###-#### Inspection requested via web by Aaron Alandt- a/c coil co ok
MEC19-01622 Final4/29/20194/29/20194/29/2019 1:41:05 PMPPASS
furnace a/c coil co ok- 5lb flue test pass
MEC19-01622 Pressure Test4/28/20194/29/20194/29/2019 1:40:35 PMPPASS
Please call technicians prior to heading out to ensure flue is on pressure and ready.
Customer will not be home until after 1pm. Phone #: ###-#### Inspection requested via web by Andrea Grigsby- 5lb flue test pass
MEC19-01377 Rough-in4/26/20194/29/20194/29/2019 11:27:01 AMAPART
meet Greg at 1130 am- ###-####- R/I on insulation on supply, return air and OSA ok in attic ok to cover- still need to see exhaust fan rough in and insulation in crawl space
MEC18-05917 Rough-in4/26/20194/29/20194/29/2019 11:07:19 AMAPART
Phone #: ###-#### Inspection requested via web by Nicholas Paige- grease duct welds ok- all welds completed on grease duct system- seal area H1 supply duct only ok to insulate
MEC18-05917 Pressure Test4/26/20194/29/20194/29/2019 11:05:30 AMAPART
Phone #: ###-#### Inspection requested via web by Nicholas Paige- 60lb gas pass whole system- still need to see low pressure test when piping installed to cook line and boilers
MEC19-01703 Pressure Test4/25/20194/29/20194/29/2019 10:13:49 AMAPASS
Please contact owner prior to arrival. Phone #: ###-#### Inspection requested via web by Jamee Shoecraft- 20lb gas pass- need to issue fireplace permit to final this permit out
MEC19-01105 Final4/29/20194/29/20194/29/2019 9:57:22 AMAPASS
Call ed 20 min ahead
Thanks Phone #: ###-#### Inspection requested via web by Manuel Canto- final ok
MEC19-01683 Final4/26/20194/29/20194/29/2019 9:32:55 AMAFAIL
Brian Phone #: ###-####- single wall flue pipe needs 6" clearance to combustibles and needs insulation shield installed
MEC18-06140 Final4/23/20194/29/20194/29/2019 9:04:41 AMAFAIL
Phone #: ###-#### Inspection requested via web by Marisa Hone- need to witness flue test- furnace a/c coil co ok
MEC19-00452 Conference4/26/20194/29/20194/29/2019 8:39:07 AMAPASS
8:30 am Duct Blast Phone #: ###-#### Inspection requested via web by Debbie Marino- duct blast test pass
MEC19-01558 Rough-in4/26/20194/29/20194/29/2019 8:24:45 AMAFAIL
Phone #: ###-#### Inspection requested via web by Joseph Profitt- fresh air ducting needs completed on front entry- crawl needs completed- R/A registers cans needs spotweld sealed- dryer duct needs sealed to termination box- exhaust fan bath 1 needs duct sealed to plastic at fan location- needs to straighten gas pipe at meter locstion and retest- line set needs ran on rough in stage- left correction notice front window
MEC19-01558 Pressure Test4/26/20194/29/20194/29/2019 8:22:04 AMAFAIL
Phone #: ###-#### Inspection requested via web by Joseph Profitt- gas piping at meter location needs straightened and retested- 5lb flue x 2 pass
MEC18-03082 Mec-Aging Inspection4/29/20194/29/20194/29/2019 7:57:07 AM FAIL
contractor needs to schedule inspection when works completed- bld permit still open