MEC18-01795
| Pressure Test | 5/1/2018 | 5/1/2018 | 5/1/2018 3:33:35 PM | P | PASS |
|
|
20lb gas pass whole system- fireplace gas piping is installed now thru appliance
|
MEC18-01851
| Rough-in | 5/1/2018 | 5/1/2018 | 5/1/2018 3:32:08 PM | P | PASS |
|
|
fireplace R/I ok- gas stubbed into fireplace by other mech contractor and pressure tested
|
MEC18-01910
| Final | 5/1/2018 | 5/1/2018 | 5/1/2018 3:27:28 PM | P | CANC |
|
|
If this could your last stop of the day that would be great. Our installer is installing it today. you can call Skip on your way ###-#### Phone #: ###-#### >> Inspection requested via web by Devony Bullard Inspection cancelled from web by: Devony Bullard
|
MEC18-01754
| Pressure Test | 5/1/2018 | 5/1/2018 | 5/1/2018 3:02:39 PM | P | FAIL |
|
|
gate is open and it''s on the side of the house // Sergio Phone #: ###-####- gauge still doesnt zero out
|
MEC18-01328
| Final | 4/30/2018 | 5/1/2018 | 5/1/2018 2:36:08 PM | P | FAIL |
|
|
Please inspect after 2 PM. We are doing corrections at noon. Phone #: ###-#### Inspection requested via web by Mary LaFayette- gas line didnt have pressure in it only pressured up from shut off valve behind stove to gauge
|
MEC18-01900
| Final | 5/1/2018 | 5/1/2018 | 5/1/2018 1:58:57 PM | P | PASS |
|
|
Please call prior to inspection. Charlotte ###-#### or Beverly ###-#### Phone #: ###-#### Inspection requested via web by Mary LaFayette- ac co ok
|
MEC18-01710
| Final | 4/24/2018 | 5/1/2018 | 5/1/2018 1:50:30 PM | P | CANC |
|
|
Call Rita when going to job site. ###-####. Thank you! Phone #: ###-#### Inspection requested via web by Tyler Collado- per phone call with homeowner reschedule for tomorrow pm- i already scheduled inspection
|
MEC18-01893
| Final | 4/30/2018 | 5/1/2018 | 5/1/2018 1:26:51 PM | P | PASS |
|
|
INSTALLER DAVID ###-#### Phone #: ###-#### Inspection requested via web by Aaron Alandt- furnace ac coil co ok
|
MEC18-00956
| Final | 5/1/2018 | 5/1/2018 | 5/1/2018 11:32:34 AM | P | CANC |
|
|
MEC AND FIREPL G /CODE 4200 Phone #: ###-#### Inspection requested via web by Oleg Chervak- per phone with Oleg
|
MEC18-01110
| Final | 4/30/2018 | 5/1/2018 | 5/1/2018 11:00:04 AM | A | FAIL |
|
|
final Phone #: ###-#### Inspection requested via web by Brandon Sorensen- need drip leg on gas lines between shut off valve and appilance both W/H and furnace- need uv tape on lineset outside at A/C- flue pipe cannot be trapped need 1/4" per foot of slope and redone- need to insulate 6" fresh air in garage- left correction notice on furnace in garage
|
MEC18-01830
| Pressure Test | 5/1/2018 | 5/1/2018 | 5/1/2018 10:31:17 AM | P | CANC |
|
|
Phone #: ###-#### >> Inspection requested via web by Devony Bullard Inspection cancelled from web by: Devony Bullard
|
MEC17-02485
| Mec-Aging Inspection | 5/1/2018 | 5/1/2018 | 5/1/2018 10:29:51 AM | | NH |
|
|
no one home- no access- left notice front door
|
MEC18-01905
| Rough-in | 4/30/2018 | 5/1/2018 | 5/1/2018 10:07:03 AM | A | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by GREGORY ANDERSEN- need to fix all rips and tears in armaflx- b vent needs 1" clearance to sheetrock W/H flue- need transfer grill installed in laundry closet- left correction notice front window
|
MEC18-01905
| Pressure Test | 4/30/2018 | 5/1/2018 | 5/1/2018 10:05:37 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by GREGORY ANDERSEN- 20lb gas pass
|
MEC18-01280
| Final | 4/30/2018 | 5/1/2018 | 5/1/2018 9:20:42 AM | A | PART |
|
|
Please contact Dave with any questions @###-#### Phone #: ###-#### Inspection requested via web by Dave DeChambeau- need airbalance report onsite- Temp occupancy ok
|
MEC18-01328
| Pressure Test | 4/30/2018 | 5/1/2018 | 4/30/2018 4:00:38 PM | P | CANC |
|
|
Please inspect after 2 PM. We are doing corrections at noon. Phone #: ###-#### Inspection requested via web by Mary LaFayette
|