Inspections for the day of: Friday, May 31, 2019.
Number of inspections: 29
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBrian Scoles
TitleMEC INSPECTOR
Phone #914-4915
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
MEC19-01881 Final5/29/20195/31/20195/31/2019 3:55:16 PMPPASS
Please call Carlos in route to inspection ###-#### Phone #: ###-#### Inspection requested via web by Justin Osterhout- furnace a/c coil co ok
MEC18-05458 Final5/29/20195/31/20195/31/2019 3:24:38 PMPPART
Final Inspection. Please contact Scott at ###-#### prior to arrival on-site. Phone #: ###-#### Inspection requested via web by Heather Gransbery- need engineer approval on fire dampers installed in elevator equipment room for whats installed- need installation instruction on roofing boots used with bvent on roof- unit heater on mezz needs 1/4" per foot rise to outside- temp occupancy ok
MEC19-02231 Final5/29/20195/31/20195/31/2019 3:02:53 PMPPASS
INSTALLER DAVID ###-#### Phone #: ###-#### Inspection requested via web by Aaron Alandt- furnace a/c coil co ok- 5lb flue pass
MEC19-02241 Final5/30/20195/31/20195/31/2019 2:50:21 PMPPASS
Please call Blake on your way - ###-#### Phone #: ###-#### Inspection requested via web by Arielle Hendricks- furnace a/c coil co ok
MEC19-02218 Final5/29/20195/31/20195/31/2019 2:43:09 PMPPASS
Please call Craig on your way - ###-#### Phone #: ###-#### Inspection requested via web by Arielle Hendricks- furnace a/c coil co ok
MEC19-02216 Final5/29/20195/31/20195/31/2019 2:14:13 PMPPASS
INSTALLER GERRY ###-#### Phone #: ###-#### Inspection requested via web by Aaron Alandt- furnace a/c coil co ok
MEC19-01612 Rough-in5/31/20195/31/20195/31/2019 2:01:20 PMPPASS
fire damper inspection- fire damper clearances ok-angles ok- still need all firecaulking removed- Temp occupancy ok- call in final when registers have been installed on fire dampers and fire caulk is removed
MEC19-02256 Rough-in5/30/20195/31/20195/31/2019 1:53:38 PMPPASS
rough-in and p-test witness Phone #: ###-#### Inspection requested via web by Joe Taylor- R/I ok- needs to seal return and supply boots on all spot welds by final- if furnace/water heater closet gets doors on it will need combustion air by final- check equipment atfinal not set at r/i
MEC19-02256 Pressure Test5/31/20195/31/20195/31/2019 1:47:51 PMPPASS
rough-in and p-test witness Phone #: ###-#### Inspection requested via web by Joe Taylor- 20lb gas pass
MEC19-02154 Rough-in5/31/20195/31/20195/31/2019 1:36:54 PMPPASS
Phone #: ###-#### Inspection requested via web by Matthew BLANKENSHIP- R/I both units ok
MEC19-02257 Final5/31/20195/31/20195/31/2019 12:57:00 PMPPASS
Please call Brett on your way - ###-#### Phone #: ###-#### Inspection requested via web by Arielle Hendricks- furnace only co ok
MEC18-05895 Final5/30/20195/31/20195/31/2019 11:31:40 AMANH
Duct installation. Phone #: ###-#### Inspection requested via web by Bryan Palmer
MEC19-02217 Final5/30/20195/31/20195/31/2019 11:13:50 AMAPASS
Branden -###-####- furnace a/c coil co ok
MEC19-02217 Pressure Test5/30/20195/31/20195/31/2019 11:13:06 AMAPASS
5lb flue pass
MEC18-05852 Final5/30/20195/31/20195/31/2019 10:51:09 AMAFAIL
garage code 2102 Phone #: ###-#### Inspection requested via web by Michael Stimpson- range duct needs ran insmooth interior metal no flex duct- water heater flue needs 6" clearance to conbustibles for single wall pipe
MEC19-02253 Final5/30/20195/31/20195/31/2019 10:36:39 AMAPASS
Phone #: ###-#### Inspection requested via web by Tim Petsche- R/I ok on 2 supply ducts- ok to cover
MEC19-01612 Conference5/30/20195/31/20195/31/2019 10:02:30 AMADONE
Rob Phone #: ###-####- discussed fire dampers and looked at angles- reschedule for R/I in after noon- went over installation instructions with contractor onsite
MEC19-02212 Rough-in5/30/20195/31/20195/31/2019 9:44:33 AMAPASS
VINNY ###-#### Phone #: ###-#### Inspection requested via web by Mike Almanza-fireplace r/i ok
MEC19-00577 Final5/30/20195/31/20195/31/2019 9:21:50 AMAPASS
garage code #3162 Phone #: ###-#### Inspection requested via web by Debbie Marino- fireplace and hvac final ok
MEC19-02240 Final5/31/20195/31/20195/31/2019 9:06:34 AMAPASS
Inspection requested via web by Floyd Floyd Peek- 20lb gas pass- unit heater and fluing ok
MEC19-02250 Final5/30/20195/31/20195/31/2019 8:53:04 AMAFAIL
PLEASE CALL HOMEOWNER MADYLON WHEN 30 MINS IN ROUTE Phone #: ###-#### Inspection requested via web by Rick Montgomery- need to witness flue test in conditioned space to final this permit out- furnace a/c coil co ok-
PLM19-01936 Water Heater Final5/29/20195/31/20195/31/2019 8:34:15 AMAPASS
Phone #: ###-#### Inspection requested via web by Mary LaFayette- water heater co ok
MEC19-01982 Final5/29/20195/31/20195/31/2019 8:33:08 AMAPASS
Phone #: ###-#### Inspection requested via web by Mary LaFayette- furnace a/c coil co ok
MEC19-01139 Rough-in5/30/20195/31/20195/31/2019 8:18:55 AMAPASS
hard lids for conference and 2 offices Phone #: ###-#### Inspection requested via web by Brandon Sorensen- register, flex and grid 3 rooms ok for ceiling tiles
MEC18-02865 Mec-Aging Inspection5/31/20195/31/20195/31/2019 7:44:42 AM CANC
MEC18-02865 DOC - Permit Expired5/31/20195/31/20195/31/2019 7:44:22 AMAPASS
no activity
MEC19-00577 Conference5/30/20195/31/20195/30/2019 2:28:33 PMAPASS
8:30 am Duct Blast Phone #: ###-#### Inspection requested via web by Debbie Marino- duct blast test pass
MEC19-02212 Rough-in5/30/20195/31/20195/30/2019 11:37:57 AMPCANC
VINNY ###-#### Phone #: ###-#### >> Inspection requested via web by Mike Almanza Inspection cancelled from web by: Mike Almanza
MEC19-02217 Final5/29/20195/31/20195/30/2019 10:31:24 AMACANC
INSTALLER BRANDAN ###-#### Phone #: ###-#### Inspection requested via web by Aaron Alandt- per phone call with Branden will due flue test at final thats scheduled for am tomorrow