Inspections for the day of: Monday, June 17, 2019.
Number of inspections: 18
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBrian Scoles
TitleMEC INSPECTOR
Phone #914-4915
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
MEC19-01007 Final6/17/20196/17/20196/17/2019 3:48:15 PMPPASS
PLEASE CALL SCOTT BANNER FOR ACCESS ###-#### AT LEAST 30 MIN PRIOR SO HE CAN MEET INSPECTOR. THANKS Phone #: ###-#### Inspection requested via web by Andrea Creek- final ok
MEC19-02370 Rough-in6/17/20196/17/20196/17/2019 3:26:22 PMPNR
John Phone #: ###-####- crawl needs completed- bedroom has supply right at entry of door instead of being under window is there a reason not where indicted on man J- need to fix all rips and tears in arma flex bare copper showing- needs register can installed for transfer in hallway to bedrooms or pan off wood with metal, wood not exceptable material for ducting
MEC19-02370 Rough-in6/17/20196/17/20196/17/2019 3:18:25 PMPNR
John- this for the fire place rough-in Phone #: ###-####- need installation insrtuction accessible behind glass- flexible flue doesnt have 1" clearance to combustibles at roof touching plywood-
MEC19-02370 Pressure Test6/17/20196/17/20196/17/2019 3:17:07 PMPFAIL
John Phone #: ###-####- gauge wont zero out
MEC19-02226 Final6/13/20196/17/20196/17/2019 2:41:08 PMPPASS
Please call Robert Gelok prior to inspection. ###-#### Phone #: ###-#### Inspection requested via web by Mary LaFayette- furnace a/c coil co ok
MEC19-02290 Final6/10/20196/17/20196/17/2019 1:39:21 PMPNR
Please call Dave to ensure install is complete. Thank you! ###-#### Phone #: ###-#### Inspection requested via web by Rick Borg
MEC19-01085 Final6/17/20196/17/20196/17/2019 12:59:04 PMPPART
If there are any questions please contact Ryan J. at ###-#### Phone #: ###-#### Inspection requested via web by Stacia Haumann- need to reroute 2 primary coil drains so secondary drain can have wet switch installed and work with TML to see whos going to install secondary wet switch- gas piping ok-
MEC19-02558 Rough-in6/17/20196/17/20196/17/2019 12:40:34 PMPFAIL
Phone #: ###-#### Inspection requested via web by Kristy Watson
1- duct in crawl needs minimum 4" clearance off ground
2- b vent at roof needs 1" clearance to combustibles laying against plywood sheathing
3- need to seal all spot welds on supply and return boots
4- need to seal dryer duct to termination box in wall
5- need to resubmit man J to city for approval and have approved man j onsite with equipment brand installed- shows payne and has bryant installed

left correction notice front window
MEC19-02558 Pressure Test6/17/20196/17/20196/17/2019 12:36:22 PMPPASS
Phone #: ###-#### Inspection requested via web by Kristy Watson- 20lb gas pass tagged meter location
MEC19-02496 Pressure Test6/17/20196/17/20196/17/2019 11:32:32 AMAPASS
20lb gas pass whole system- tagged meter location- 5lb flue pass
MEC19-02496 Conference6/13/20196/17/20196/17/2019 11:28:09 AMPDONE
can you call when you are on your way please. conference and pressure test. Phone #: ###-#### Inspection requested via web by Melinda Hughes
1- dryer duct needs firred out
2- support gas piping per csst gas piping installation instructions in attic
3- insulation shield needs 1" clearance to combustibles
4- b vent needs 1" clearance to combustibles floor and ceiling and b vent in furnace closet can not run over the electrical box
5- range ducting and location ?
6- combustion aior for furnace closet 1 high and 1 low
7 exhaust fans vented to outside

went over onsite with homeowner Melinda

call in R/I inspection when ready
MEC19-02338 Final6/12/20196/17/20196/17/2019 10:36:26 AMPPASS
Inspection requested via web by Margie Rowe
MEC18-05261 Final6/14/20196/17/20196/17/2019 10:23:03 AMAPASS
Please call Mark for access ###-#### Inspection requested via web by Aaron Alandt- final ok
MEC18-05261 Rough-in6/17/20196/17/20196/17/2019 10:22:44 AMAPASS
Please call Mark for access ###-#### Inspection requested via web by Aaron Alandt- R/I ok-
MEC18-02215 Final6/14/20196/17/20196/17/2019 9:45:00 AMAFAIL
Mechanical Final Inspection needed for AM Monday please contact Karl with any questions thank you. Phone #: ###-#### Inspection requested via web by Karl Hestekin- correction not made in kitchen- roof ok
MEC19-02463 Final6/12/20196/17/20196/17/2019 8:53:18 AMAPASS
Phone #: ###-#### Inspection requested via web by Devry King- furnace a/c coil co ok
MEC18-00547 Mec-Aging Inspection6/17/20196/17/20196/17/2019 8:05:27 AM CANC
contractor needs to call in inspection when ready
MEC18-04711 Mec-Aging Inspection6/17/20196/17/20196/17/2019 8:04:48 AM CANC
WIP