MEC19-02630
| Final | 6/20/2019 | 6/21/2019 | 6/21/2019 2:37:16 PM | P | PASS |
|
|
Please call Jim Peirsee prior to inspection. ###-#### Phone #: ###-#### Inspection requested via web by Mary LaFayette- furnace a/c coil co ok
|
MEC19-02476
| Pressure Test | 6/17/2019 | 6/21/2019 | 6/21/2019 2:07:51 PM | P | NR |
|
|
THIS P/T IS FOR FLUE, WE ARE NOT DOING THE GAS LINE UNTIL FUTURE DATE, WILL GET GAS P/T ; FINAL AT THAT TIME Phone #: ###-#### Inspection requested via web by Aaron Alandt- flue not under pressure- schedule this when final is called in
|
MEC19-02648
| Final | 6/20/2019 | 6/21/2019 | 6/21/2019 1:52:06 PM | P | PASS |
|
|
Please inspect PM and call Jeremy on your way - ###-#### Phone #: ###-#### Inspection requested via web by Arielle Hendricks- furnace a/c coil co ok
|
MEC19-02478
| Rough-in | 6/21/2019 | 6/21/2019 | 6/21/2019 1:21:57 PM | P | PASS |
|
|
Pressure test/rough in for gas piping. Please call Rachael with any questions. Phone #: ###-#### Inspection requested via web by Rachael Moore- gas piping R/I ok
|
MEC19-02478
| Pressure Test | 6/21/2019 | 6/21/2019 | 6/21/2019 1:15:53 PM | P | PASS |
|
|
Pressure test/rough in inspection for pipe run. Call Rachael with any questions. Phone #: ###-#### Inspection requested via web by Rachael Moore- 20lb gas pass whole system tagged meter location-
|
MEC19-02479
| Rough-in | 6/21/2019 | 6/21/2019 | 6/21/2019 1:15:24 PM | P | NR |
|
|
Rough in inspection for 2 bath vents and 1 dryer vent. Please call Rachael with any questions. Phone #: ###-#### Inspection requested via web by Rachael Moore- insulation shields on b vent for unit heaters needs minimum 1" clearance to combustibles- need to add air conditioning to permit for mini split- went over onsite with owner- recall in inspection when ready- 2 bath fans ok- need to fir out wall and install nail plates on dryer vent at ceiling
|
MEC19-01377
| Rough-in | 6/20/2019 | 6/21/2019 | 6/21/2019 11:24:37 AM | A | PART |
|
|
Temp occupancy requested. Greg is the contact. Phone #: ###-#### Inspection requested via web by stan lillquist- needs uv protection on linset on roof and supports installed- condensers on roof need secured to roof curbs- need roofing completed on all pentrations on roof and weather tight- need to seal duct and fire caulk ceiling pentrations in furnace/water heater room northeast corners- went over with Greg onsite- signed temp occupany card
|
MEC19-02626
| Final | 6/20/2019 | 6/21/2019 | 6/21/2019 10:54:24 AM | A | PASS |
|
|
Please inspect late AM. Homeowner Helga Wilcox-Fraire ###-#### Phone #: ###-#### Inspection requested via web by Mary LaFayette- furnace a/c coil co ok
|
MEC19-02627
| Final | 6/20/2019 | 6/21/2019 | 6/21/2019 10:30:20 AM | A | PASS |
|
|
Homeowner Manju Ranjit ###-#### Phone #: ###-#### Inspection requested via web by Mary LaFayette- furnace a/c coil co ok
|
MEC19-02585
| Rough-in | 6/20/2019 | 6/21/2019 | 6/21/2019 10:01:28 AM | A | PASS |
|
|
Call Jason @ ###-#### with any inspection issues. Phone #: ###-#### Inspection requested via web by Angie Maguire- R/I ok- need to seal dryer duct to termination box by final- need to insulate supply plenum drop and any other bare metal in crawl by final- will check at final
|
MEC19-02661
| Rough-in | 6/20/2019 | 6/21/2019 | 6/21/2019 9:38:37 AM | A | FAIL |
|
|
rough in inspection for the pass through fan in the bed room. bath room fan, and transfer grills. mini split to be installed latter. Phone #: ###-#### Inspection requested via web by jeremy wanders- 3/4" condensate needs ran up to head location and remove flexable condensate in wall and maintain sloe in wall to outside of house
|
MEC19-02628
| Final | 6/20/2019 | 6/21/2019 | 6/21/2019 9:22:14 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Mary LaFayette- furnace a/c coil co ok
|
MEC19-02244
| Rough-in | 6/20/2019 | 6/21/2019 | 6/21/2019 8:53:19 AM | A | PASS |
|
|
rough - call scott Phone #: ###-#### Inspection requested via web by Brandon Sorensen- R/I ok- ok for ceiling tiles excluding break room where condensate drain work will be doneneeds to be in approved metal GC is on it
|
MEC19-02255
| Final | 6/20/2019 | 6/21/2019 | 6/21/2019 8:50:28 AM | A | PASS |
|
|
final - call scott Phone #: ###-#### Inspection requested via web by Brandon Sorensen- final ok
|
MEC18-05404
| Mec-Aging Inspection | 6/21/2019 | 6/21/2019 | 6/21/2019 8:07:34 AM | | CANC |
|
|
WIP- call in inspection when ready -permit will need to have extension called in by next aging permit or permit will expire
|
MEC18-05435
| Mec-Aging Inspection | 6/21/2019 | 6/21/2019 | 6/21/2019 8:06:04 AM | | FAIL |
|
|
needs called in for inspection if work was complete- permit will expire next aging and new permit will need issued if permit expires
|