MEC19-04307
| Conference | 7/8/2020 | 6/23/2020 | 7/8/2020 10:02:34 AM | A | CANC |
|
|
We would like to speak about the project and the new additions we are wanting to add to the project. Phone #: ###-#### >> Inspection requested via web by Shawn Whitaker Inspection cancelled from web by: Shawn Whitaker
|
MEC20-02272
| Final | 6/22/2020 | 6/23/2020 | 6/23/2020 3:36:18 PM | P | FAIL |
|
|
Please call the homeowner when on way: Richard ###-#### Phone #: ###-#### Inspection requested via web by Arielle Hendricks- furnace a/c coil co locking caps ok- secondary drain needs trap removed and ran to garage floor- send pic for reinspect
|
MEC20-01731
| Rough-in | 6/23/2020 | 6/23/2020 | 6/23/2020 3:06:03 PM | P | PART |
|
|
2nd floor cover please Phone #: ###-#### Inspection requested via web by GREGORY ANDERSEN- 2nd floor units 201-212 R/I supply return exhaust and dryer duct ok- ok to cover
|
MEC20-02537
| Final | 6/22/2020 | 6/23/2020 | 6/23/2020 2:35:17 PM | P | PASS |
|
|
Please call Aleks on your way - ###-#### Phone #: ###-#### Inspection requested via web by Arielle Hendricks- furnace a/c coil co locking caps ok
|
MEC20-02124
| Final | 6/22/2020 | 6/23/2020 | 6/23/2020 2:01:08 PM | P | PASS |
|
|
Call ahead 15 minutes. Jody Phone #: ###-####- electric furnace a/c coil co locking caps ok
|
MEC20-01953
| Final | 6/22/2020 | 6/23/2020 | 6/23/2020 1:25:05 PM | P | FAIL |
|
|
Please call tenant Nicole in route to inspection ###-#### Phone #: ###-#### Inspection requested via web by Justin Osterhout- needs right size breaker installed in panel has 30 max on condenser is 25- recall in when correction made
|
MEC20-02526
| Conference | 6/23/2020 | 6/23/2020 | 6/23/2020 12:27:37 PM | P | DONE |
|
|
PLEASE CONTACT ANDREY AND WALKTHOUGH THIS PROJECT WITH HIM. WE WANT TO BE SURE THAT WE ARE CODE COMPLIANT, THANK YOU Phone #: ###-#### Inspection requested via web by Oleg Chervak- discussed pvc drains- condenser middle units need pvc drain/pan installed under condenser and freeze protection provided- 1st floor middle units need exhaust fan minimum 3 feet from property line- went over with Alex onsite
|
MEC20-02509
| Conference | 6/23/2020 | 6/23/2020 | 6/23/2020 12:25:38 PM | P | DONE |
|
|
PLEASE CONTACT ANDREY AND WALKTHOUGH THIS PROJECT WITH HIM. WE WANT TO BE SURE THAT WE ARE CODE COMPLIANT, THANK YOU. Phone #: ###-#### Inspection requested via web by Oleg Chervak- discussed pvc drains- condensers middle units will need drain/pan underneath and freeze protected on decks- exhaust fans 1st floor needs to be 3 feet from property line- talked with Alex about this onsite
|
MEC20-02494
| Final | 6/22/2020 | 6/23/2020 | 6/23/2020 11:11:35 AM | A | FAIL |
|
|
Home owner works from home and will be there to let you in Phone #: ###-#### Inspection requested via web by Amanda Casper- a/c coil co ok- need locking caps on a/c service ports outside- send pic for reinspect
|
MEC20-02554
| Pressure Test | 6/22/2020 | 6/23/2020 | 6/23/2020 10:46:57 AM | A | PASS |
|
|
Home owner will be home but please call me at ###-#### for directions to find the gauge for pressure test. Phone #: ###-#### Inspection requested via web by Terry Warden- 20lb gas pass- need framing completed around b vent and firecaulk floor and ceiling penetrations
|
MEC19-04307
| Conference | 6/22/2020 | 6/23/2020 | 6/23/2020 10:11:33 AM | A | DONE |
|
|
We would like to speak about the project and the new additions we are wanting to add to the project. Phone #: ###-#### Inspection requested via web by Shawn Whitaker- discussed all aspects of mechanical install- homeowner will adjust permit accordingly- will call in another conference after walls are installed
|
MEC20-01731
| Conference | 6/22/2020 | 6/23/2020 | 6/23/2020 9:23:55 AM | A | DONE |
|
|
Phone #: ###-#### Inspection requested via web by GREGORY ANDERSEN- discussed flex duct installation for supply and exhaust- multiple locations discussed- received engineer approval for flex ducting on supply ducting in question
|
MEC20-01722
| Pressure Test | 6/22/2020 | 6/23/2020 | 6/23/2020 8:43:42 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Joe Kennedy- 20lb gas pass
|
MEC20-01722
| DOC - Permit Finaled | 6/23/2020 | 6/23/2020 | 6/23/2020 8:43:29 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Joe Kennedy- 20lb gas pass
|
MEC20-02519
| Final | 6/22/2020 | 6/23/2020 | 6/23/2020 8:26:11 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Angie Pereira- furnace a/c coil co locking caps ok
|
MEC19-03851
| Mec-Aging Inspection | 6/23/2020 | 6/23/2020 | 6/23/2020 7:57:47 AM | | CANC |
|
|
permit expired
|
MEC19-03851
| DOC - Permit Expired | 6/23/2020 | 6/23/2020 | 6/23/2020 7:57:33 AM | A | PASS |
|
|
permit expired- no calls no activity
|