MEC19-02955
| Final | 7/10/2019 | 7/11/2019 | 7/11/2019 3:51:04 PM | P | PASS |
|
|
Please call Maddie on your way - ###-#### Phone #: ###-#### Inspection requested via web by Arielle Hendricks- a/c coil co ok
|
MEC19-01558
| Final | 7/10/2019 | 7/11/2019 | 7/11/2019 3:23:30 PM | P | PASS |
|
|
code is 1027 Phone #: ###-#### Inspection requested via web by Joseph Profitt- final ok
|
MEC19-02831
| Rough-in | 7/11/2019 | 7/11/2019 | 7/11/2019 2:38:29 PM | P | FAIL |
|
|
Add. P test. Phone #: ###-#### Inspection requested via web by Joe Taylo- need approved man j onsite for inspection- need crawl completed- gas line into fire place needs secured- need to pan off all wood in R/A path and seal- need to fix 10" return above furenace inner liner showing- need 10 mil inert tape on gas penetration- remove hangers on csst to range and secure to floor and add nail plate bathroom side at floor
|
MEC19-02831
| Pressure Test | 7/11/2019 | 7/11/2019 | 7/11/2019 2:36:01 PM | A | PART |
|
|
Add. P test. Phone #: ###-#### Inspection requested via web by Joe Taylor- 20lb gas pass- need to see flue under test max 15lb gauge- will tag gas line when flue test witnessed
|
MEC19-02954
| Final | 7/10/2019 | 7/11/2019 | 7/11/2019 2:09:48 PM | P | PASS |
|
|
Please call Rob on your way - ###-#### Phone #: ###-#### Inspection requested via web by Arielle Hendricks- a/c coil co ok
|
MEC19-02920
| Rough-in | 7/11/2019 | 7/11/2019 | 7/11/2019 1:44:33 PM | P | FAIL |
|
|
Joshua Phone #: ###-####- need uv protection on lineset outside at a/c location
|
MEC19-02212
| Final | 7/11/2019 | 7/11/2019 | 7/11/2019 1:18:39 PM | P | PASS |
|
|
Vinny is sup on-site: ###-#### Phone #: ###-#### Inspection requested via web by Mike Almanza-
|
MEC19-02952
| Final | 7/10/2019 | 7/11/2019 | 7/11/2019 12:50:42 PM | P | PASS |
|
|
Please contact owner Mark prior to arrival. Phone #: ###-#### Inspection requested via web by Jamee Shoecraft- final ok
|
MEC19-02957
| Final | 7/10/2019 | 7/11/2019 | 7/11/2019 11:22:43 AM | P | PART |
|
|
kitchen hood // James Phone #: ###-####- need all appliance set into place under class 1 hood- need air balance report onsite for all hoods- left side of north hood needs 18" ss panels installed in ceiling can not have ceiling tile within 18" went over with general onsite- need to uv protect arma flex on roof and seal water tight on line set penetration- call in when ready- dishwasher hood ok-
|
MEC18-05917
| Final | 7/10/2019 | 7/11/2019 | 7/11/2019 11:19:05 AM | P | PART |
|
|
partial final Phone #: ###-#### Inspection requested via web by Nicholas Paige- need to set up above ceiling temp test- need all appliances under class 1 hood set into place and flex gas piping hooked up- walked rest of job all good- few items for final
|
MEC19-01632
| Final | 7/11/2019 | 7/11/2019 | 7/11/2019 9:53:40 AM | A | FAIL |
|
|
Call me with any questions 208 631 6575 Inspection requested via web by jeff jedlick- need automatic timers installed on both units on energy star fans just has regular switch installed- need approved manual J onsite couldnt find any-
|
MEC19-02917
| Rough-in | 7/10/2019 | 7/11/2019 | 7/11/2019 9:25:47 AM | A | PASS |
|
|
cover inspection Phone #: ###-#### Inspection requested via web by Brandon Sorensen- R/I ok- need to install access doors on both exhaust fan transitions to access electrical by final- call in final when ready
|
MEC19-02254
| Final | 7/10/2019 | 7/11/2019 | 7/11/2019 8:38:15 AM | A | PASS |
|
|
final Phone #: ###-#### Inspection requested via web by Brandon Sorensen- final ok
|
MEC19-02254
| Card not on site to sign | 7/11/2019 | 7/11/2019 | 7/11/2019 8:38:01 AM | P | PASS |
|
|
final Phone #: ###-#### Inspection requested via web by Brandon Sorensen- no card onsite to sign
|
MEC18-03813
| Mec-Aging Inspection | 7/11/2019 | 7/11/2019 | 7/11/2019 8:05:12 AM | | CANC |
|
|
|
MEC18-03813
| DOC - Permit Expired | 7/11/2019 | 7/11/2019 | 7/11/2019 8:05:04 AM | A | PASS |
|
|
no activity
|
MEC18-05725
| Mec-Aging Inspection | 7/11/2019 | 7/11/2019 | 7/11/2019 8:04:09 AM | | FAIL |
|
|
contractor shall schedule a flue test witness and correction- permit will expire next aging if no activity
|
MEC18-05728
| Mec-Aging Inspection | 7/11/2019 | 7/11/2019 | 7/11/2019 8:03:03 AM | | FAIL |
|
|
contractor shall schedule a flue test witness- permit will expire next aging if no activity
|
MEC18-03796
| Mec-Aging Inspection | 7/11/2019 | 7/11/2019 | 7/11/2019 8:02:16 AM | | CANC |
|
|
|
MEC18-03796
| DOC - Permit Expired | 7/11/2019 | 7/11/2019 | 7/11/2019 8:02:01 AM | A | PASS |
|
|
no activity
|