Inspections for the day of: Tuesday, July 23, 2019.
Number of inspections: 23
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBrian Scoles
TitleMEC INSPECTOR
Phone #914-4915
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
MEC19-03169 Final7/22/20197/23/20197/23/2019 4:06:41 PMPPASS
Phone #: ###-#### Inspection requested via web by Mary LaFayette- a/c coil co ok
MEC19-03115 Final7/19/20197/23/20197/23/2019 3:36:11 PMPPASS
Homeowner Sarah Davis ###-#### Phone #: ###-#### Inspection requested via web by Mary LaFayette- furnace a/c coil co ok
MEC19-01650 Final7/22/20197/23/20197/23/2019 3:19:46 PMPPART
Phone #: ###-#### Inspection requested via web by Gary Reeves- need to remove stucco from around gas piping and seal weather tight- rest is good- recall in when correction made
MEC19-03178 Final7/22/20197/23/20197/23/2019 2:53:38 PMPPASS
Please call Chuck on your way - ###-#### Phone #: ###-#### Inspection requested via web by Arielle Hendricks- furnace a/c coil co ok
MEC19-03146 Rough-in7/23/20197/23/20197/23/2019 2:14:28 PMPPART
Partial light test. Wont be ready until 2:00 p.m. Phone #: ###-#### Inspection requested via web by Drew Tverdy- light test on drop and 12 feet of square duct ok- will look at remaining welds next inspection
MEC19-03141 Final7/23/20197/23/20197/23/2019 1:52:16 PMPPART
PLEASE CALL HOMEOWNER DONNA WHEN 30 MINS IN ROUTE Phone #: ###-#### Inspection requested via web by Rick Montgomery- minisplit condenser ok- homeowner needs to get electrical permit issued for condenser work to final this permit out
MEC19-01298 Final7/23/20197/23/20197/23/2019 1:30:55 PMPPASS
water heater permit been issued
MEC19-03130 Final7/23/20197/23/20197/23/2019 1:20:04 PMPPASS
Please call tech on site in route to inspection -- Bill ###-#### --He is installing today Phone #: ###-#### Inspection requested via web by Justin Osterhout- a/c coil co ok
MEC19-01925 Final7/23/20197/23/20197/23/2019 12:40:35 PMPPART
final Phone #: ###-#### Inspection requested via web by Brandon Sorensen- need to seal all new ducting installed- recall in when ready
MEC19-02109 Final7/23/20197/23/20197/23/2019 12:39:41 PMPPASS
final Phone #: ###-#### Inspection requested via web by Brandon Sorensen- final ok- card signed
MEC19-03029 Final7/19/20197/23/20197/23/2019 12:07:12 PMPPASS
Please inspect from 11:30-2 and call Terri at least 15 minutes prior to inspection so she can get home. ###-#### Phone #: ###-#### Inspection requested via web by Mary LaFayette- a/c coil co ok
MEC19-02958 Final7/23/20197/23/20197/23/2019 11:43:44 AMAPASS
final on gas piping ok
MEC19-01753 Final7/23/20197/23/20197/23/2019 11:42:42 AMPPART
final - call jeremy Phone #: ###-#### Inspection requested via web by Brandon Sorensen- need to see if you can get more out of MAU unit 82% is a bit low on air balance-
MEC19-02926 Rough-in7/23/20197/23/20197/23/2019 11:25:13 AMPPASS
cover Phone #: ###-#### Inspection requested via web by Brandon Sorensen- remaining seal on ducts ok- ok to insulate- leave ceiling tiles out at drops to see insulation at final- need access to roof at final for RTU
MEC19-01588 Final7/23/20197/23/20197/23/2019 10:59:06 AMPPASS
garage code 1234 Phone #: ###-#### Inspection requested via web by Terek Worley- final ok
MEC19-02379 Pressure Test7/22/20197/23/20197/23/2019 10:34:47 AMAPASS
hydronic pressure test. If questions call Josh @ ###-####. Phone #: ###-#### Inspection requested via web by Stacia Haumann- 3 seperate hydronic test pass- ok to insulate- will look at remainder of piping during grid inspection
MEC19-03168 Final7/22/20197/23/20197/23/2019 10:14:30 AMAPASS
Phone #: ###-#### Inspection requested via web by Mary LaFayette- a/c coil co ok
MEC19-02163 Final7/18/20197/23/20197/23/2019 9:50:58 AMAPASS
Phone #: ###-#### Inspection requested via web by Randy Hart- final ok
MEC19-03146 Rough-in7/23/20197/23/20197/23/2019 9:41:46 AMPCANC
Partial light test on grease duct. Phone #: ###-#### >> Inspection requested via web by Drew Tverdy Inspection cancelled from web by: Drew Tverdy
MEC19-01958 Final7/22/20197/23/20197/23/2019 9:21:29 AMAPASS
LATTER WILL BE LEFT FOR YOU. GARAGE CODE 0425 Phone #: ###-#### Inspection requested via web by Oleg Chervak
MEC19-03133 Final7/22/20197/23/20197/23/2019 8:56:12 AMAPASS
Phone #: ###-#### Inspection requested via web by Mary LaFayette- furnace a/c coil co ok
MEC19-02921 Final7/22/20197/23/20197/23/2019 8:37:25 AMAPASS
Phone #: ###-#### Inspection requested via web by Nicholas Paige- final ok- card signed
MEC18-04202 Mec-Aging Inspection7/23/20197/23/20197/23/2019 8:03:42 AM FAIL
contractor needs to pull water heater permit for owner furnished water heater they installed when doing furnace install