Inspections for the day of: Tuesday, July 9, 2019.
Number of inspections: 14
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBrian Scoles
TitleMEC INSPECTOR
Phone #914-4915
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
MEC19-02924 Conference7/9/20197/9/20197/9/2019 3:42:37 PMPDONE
Please Call Greg for a consult only on this job ###-#### Phone #: ###-#### Inspection requested via web by Greg Mendiola- discussed underground gas piping under existing concrete slab and options
MEC19-02902 Final7/8/20197/9/20197/9/2019 2:46:10 PMPPASS
after 2 call before coming Phone #: ###-#### Inspection requested via web by Kim Lithander- a/c coil co ok
MEC19-01869 Final7/8/20197/9/20197/9/2019 1:45:06 PMPPASS
re inspection code 2468 Phone #: ###-#### Inspection requested via web by Randy Hart- final ok
MEC19-01975 Final7/9/20197/9/20197/9/2019 12:56:11 PMPPASS
final ok
MEC19-01975 Rough-in7/8/20197/9/20197/9/2019 12:48:14 PMPPASS
Greg is the contact. Phone #: ###-#### Inspection requested via web by stan lillquist- R/I ok
MEC19-02896 Final7/9/20197/9/20197/9/2019 12:11:03 PMPPASS
electrial permit has been issued
MEC18-04280 Rough-in7/8/20197/9/20197/9/2019 10:28:24 AMAPASS
Please call Brad at least 30 min prior to inspection, thank you. Phone #: ###-#### Inspection requested via web by Rhonda Marcum- 1st floor main hallway registers flex and insulation ok- all 2nd floor registers flex and insulation ok- ok for ceiling tiles
MEC19-02758 Final7/8/20197/9/20197/9/2019 9:23:00 AMAFAIL
Phone #: ###-#### Inspection requested via web by Kim Evans- furnace a/c coil co ok- need right size breaker installed at disconnect at a/c has 30 needs max 15
MEC19-02917 Rough-in7/8/20197/9/20197/9/2019 9:08:37 AMAPASS
cover inspection Phone #: ###-#### Inspection requested via web by Brandon Sorensen- 5 class rooms FCUs and outside air ok to cover- need to see 2 exhaust fans connected to registers- call in when ready
MEC19-02256 Final7/8/20197/9/20197/9/2019 8:36:11 AMAPASS
Phone #: ###-#### Inspection requested via web by Joe Taylor- final ok
MEC18-05684 Mec-Aging Inspection7/9/20197/9/20197/9/2019 8:06:22 AM CANC
contractor needs to schedule inspection- permit will expire next aging if no activity
MEC18-03634 Mec-Aging Inspection7/9/20197/9/20197/9/2019 7:47:17 AM CANC
MEC18-03634 DOC - Permit Expired7/9/20197/9/20197/9/2019 7:46:51 AMAPASS
no activity
MEC19-02420 Final7/3/20197/9/20197/8/2019 2:21:02 PMACANC
Please call Dan on way to inspection ###-#### Phone #: ###-#### >> Inspection requested via web by Justin Osterhout Inspection cancelled from web by: Justin Osterhout