MEC19-03636
| Rough-in | 8/19/2019 | 8/20/2019 | 8/20/2019 3:41:08 PM | P | PASS |
|
|
inspecting condensate drain and line set Phone #: ###-#### Inspection requested via web by Joseph Profitt- R/I ok- call in final when ready will need access into mobile home at final
|
MEC19-03709
| Final | 8/20/2019 | 8/20/2019 | 8/20/2019 2:50:09 PM | P | NR |
|
|
Please call when on way: Maddie ###-#### Phone #: ###-#### Inspection requested via web by Arielle Hendricks- still installing- this will need flue test witnessed call me 1 day in advance to set up a time to meet and to schedule
|
MEC19-03708
| Final | 8/20/2019 | 8/20/2019 | 8/20/2019 1:56:33 PM | P | CANC |
|
|
Please inspect in the later PM and call on way: Chuck ###-#### Phone #: ###-#### >> Inspection requested via web by Arielle Hendricks Inspection cancelled from web by: Arielle Hendricks
|
MEC19-02164
| Final | 8/20/2019 | 8/20/2019 | 8/20/2019 1:45:38 PM | P | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Matthew BLANKENSHIP- need all exterior penetrations sealed- need all equipment operational
|
MEC19-02154
| Final | 8/20/2019 | 8/20/2019 | 8/20/2019 1:44:38 PM | P | NR |
|
|
Phone #: ###-#### Inspection requested via web by Matthew BLANKENSHIP- condensers havent been set- all penetrations will need sealed
|
MEC19-03538
| Rough-in | 8/20/2019 | 8/20/2019 | 8/20/2019 1:23:38 PM | P | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Gary Reeves- gas line to range not in wall- dryer duct 2nd floor not in wall reroute- left correction notice front entry
|
MEC19-03538
| Pressure Test | 8/20/2019 | 8/20/2019 | 8/20/2019 1:21:20 PM | P | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Gary Reeves- gas gauge doesnt zero out
|
MEC19-03641
| Rough-in | 8/19/2019 | 8/20/2019 | 8/20/2019 1:01:35 PM | P | PART |
|
|
inspecting condensate drain and line set Phone #: ###-#### Inspection requested via web by Joseph Profitt- R/I will pass once gas line underground is fixed
|
MEC19-03641
| Pressure Test | 8/19/2019 | 8/20/2019 | 8/20/2019 1:00:29 PM | P | PART |
|
|
undergound gas line Phone #: ###-#### Inspection requested via web by Joseph Profitt- 20lb gas pass- need minimum 12" below grade on underground gas piping piping near mobile home not deep enough
|
MEC19-03640
| Rough-in | 8/19/2019 | 8/20/2019 | 8/20/2019 12:53:50 PM | P | PART |
|
|
inspecting condensate drain and line set Phone #: ###-#### Inspection requested via web by Joseph Profitt- R/I will pass when gas line issues are addressed
|
MEC19-03640
| Pressure Test | 8/19/2019 | 8/20/2019 | 8/20/2019 12:53:19 PM | P | FAIL |
|
|
undergound gas line Phone #: ###-#### Inspection requested via web by Joseph Profitt- gauge below 20psi- need to run under ground over near meter location about 6 feet away right now
|
MEC19-03112
| Final | 8/20/2019 | 8/20/2019 | 8/20/2019 12:42:33 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by jamie berg- final ok
|
MEC19-03111
| Final | 8/20/2019 | 8/20/2019 | 8/20/2019 12:38:24 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by jamie berg- final ok
|
MEC19-03696
| Rough-in | 8/19/2019 | 8/20/2019 | 8/20/2019 11:16:09 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Brian Preece- fireplace R/I ok
|
MEC19-02354
| Final | 8/20/2019 | 8/20/2019 | 8/20/2019 10:59:32 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Dave Sorensen
|
MEC19-03562
| Rough-in | 8/19/2019 | 8/20/2019 | 8/20/2019 10:31:45 AM | A | PASS |
|
|
I will be there and ready by 10 Phone #: ###-#### Inspection requested via web by jeff jedlick- R/I ok- will look at range hood on final vent out wall owner has decided what they want, may need make up air installed
|
MEC19-03277
| Final | 8/15/2019 | 8/20/2019 | 8/20/2019 9:44:43 AM | P | CANC |
|
|
This is a Flue Pressure and Final Inspect. Please meet our installer at home at 1:30 PM . Contact for Right Now is Mary ###-#### Phone #: ###-#### >> Inspection requested via web by Mary LaFayette Inspection cancelled from web by: Mary LaFayette
|
MEC19-03539
| Rough-in | 8/19/2019 | 8/20/2019 | 8/20/2019 9:35:19 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Gary Reeves- R/I ok
|
MEC19-03579
| Final | 8/20/2019 | 8/20/2019 | 8/20/2019 9:23:17 AM | A | PASS |
|
|
Lockbox on gas meter by back door. 4955. Seam inspection and wall cover Inspection requested via web by william kerwin- seal on duct ok- ok to insulate- R/I ok- ok to cover hard lids- recall in when grid is installed
|
MEC19-03513
| Pressure Test | 8/16/2019 | 8/20/2019 | 8/20/2019 8:57:03 AM | A | NH |
|
|
NEED FLUE PRESSURE TEST . FOR MORNING INSPECTION Phone #: ###-#### Inspection requested via web by Trina DeBoard- no one home- no access- still need to add gas pressure test to permit and pay fee- electrical permit still needs issued also
|
MEC19-03516
| Rough-in | 8/19/2019 | 8/20/2019 | 8/20/2019 8:36:35 AM | A | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Terek Worley- 1- all rips and tears in arma flex need fixed all piping 2- flue needs to be b vent all the way to furnace- who installed firepla e????
|
MEC19-03514
| Rough-in | 8/19/2019 | 8/20/2019 | 8/20/2019 8:35:28 AM | A | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Terek Worley- 1- fresh air pinched off at truss needs to flow smoothly reroute 2- combustion air for laundry room needs to commence with in 12" of ceiling and floor 3- bath fan master bath pinched off going thru joist reroute smoothly 4- b vent needs to be ran all the way to furnace ion attic
|
MEC19-03132
| Final | 8/20/2019 | 8/20/2019 | 8/20/2019 8:11:53 AM | A | FAIL |
|
|
Contractor wants to see about a temp/partial pass to get c of o . Call brian ###-####950 Inspection requested via web by william kerwin- plan mod still under review- reschedule when bld permit is issued and new plans onsite
|