Inspections for the day of: Friday, September 13, 2019.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBrian Scoles
TitleMEC INSPECTOR
Phone #914-4915
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
MEC18-02752 Conference9/12/20199/13/20199/13/2019 4:07:42 PMPDONE
If this could be the last appoint for the day that would be very helpful since I''ll be at work. Just text me 15 minutes a head of time and I''ll meet you there. Phone #: ###-#### Inspection requested via web by Daniel Grover- discussed gas test, exhaust fan install and termination location and insulation on ducting and registers in basement- will pressure test whole systen next week
MEC19-03799 Rough-in9/13/20199/13/20199/13/2019 3:22:28 PMPPASS
Phone #: ###-#### Inspection requested via web by Konrad Swartz- R/I ok
MEC19-03798 Rough-in9/13/20199/13/20199/13/2019 3:19:45 PMPPASS
Phone #: ###-#### Inspection requested via web by Konrad Swartz- R/I ok
MEC19-03797 Rough-in9/13/20199/13/20199/13/2019 3:19:04 PMPPASS
Phone #: ###-#### Inspection requested via web by Konrad Swartz- R/I ok
MEC19-04061 Final9/12/20199/13/20199/13/2019 2:41:04 PMPPASS
Please call Brett on your way - ###-#### Phone #: ###-#### Inspection requested via web by Arielle Hendricks- furnace a/c coil co ok
MEC19-03986 Rough-in9/12/20199/13/20199/13/2019 1:58:02 PMPFAIL
Phone #: ###-#### Inspection requested via web by Gary Reeves- see pressure test notes for all corrections computer gliched on me somehow showed up there
MEC19-03986 Pressure Test9/12/20199/13/20199/13/2019 1:56:10 PMPFAIL
Phone #: ###-#### Inspection requested via web by Gary Reeves
1- gas gauge at 2psi
2- need to resubmit man j to city for approval for way ducting installed (R/A) or run per approved man j onsite R/A shows upstairs and installed downstairs
3- arma flex needs rips and tears fixed in wall bare copper can be seen
4- crawl ducting needs completed for R/I inspection
5- framing needs completed around supply duct 2nd floor and install metal ducting thru attic with draft stop

left notice front window
MEC19-03949 Final9/9/20199/13/20199/13/2019 1:33:05 PMPFAIL
Please call Gordon at ###-####. He lives at a Senior housing down the road. Thank you Phone #: ###-#### Inspection requested via web by Scott Wickstrom- need right size fuses in a/c disconnect- need to seal lineset penetration outside at a/c weather/rodent proof- need to provide co detectors near bedroom none found- recall in when corrections made
MEC19-03938 Rough-in9/11/20199/13/20199/13/2019 1:06:47 PMPPASS
SEAN ###-#### Phone #: ###-#### Inspection requested via web by Mike Almanza- fireplace R/I ok
MEC19-03938 Pressure Test9/11/20199/13/20199/13/2019 1:06:30 PMPPASS
SEAN ###-#### Phone #: ###-#### Inspection requested via web by Mike Almanza- 20lb gas pass from furnace location to fireplace