ELE12-02468
| ELE-Aging Inspection | 1/25/2018 | 1/25/2018 | 1/29/2018 9:01:40 AM | | DONE |
|
|
Talked to John on phone. He is working on finishing up job.
|
ELE18-00211
| Final | 1/22/2018 | 1/25/2018 | 1/25/2018 2:37:57 PM | P | PASS |
|
|
Please call Neil ###-#### on your way. If you have any questions please feel free to contact Luke ###-####. Thanks!!! Phone #: ###-#### Inspection requested via web by Clay Morgan Ok final. Panel labeled complete.
|
ELE18-00061
| Permanent Service | 1/23/2018 | 1/25/2018 | 1/25/2018 1:30:34 PM | P | PASS |
|
|
Service disconnect and reconnect for upgrade from 100 amps to 200 amps. Phone #: ###-#### Inspection requested via web by Jonathan Poot p/s o/h n ok
|
ELE17-03625
| Final | 1/25/2018 | 1/25/2018 | 1/25/2018 1:30:02 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Ryan Wilson Ok final.
|
ELE17-04120
| Electrical Rough-In | 1/25/2018 | 1/25/2018 | 1/25/2018 12:54:37 PM | P | PASS |
|
|
please call when on way // Dan Phone #: ###-#### Ok cover utility and bath. No wiring added, just reconfigured a few walls in those 2 areas.
|
ELE17-03608
| Final | 1/24/2018 | 1/25/2018 | 1/25/2018 11:48:27 AM | P | PASS |
|
|
Garage code is 6288 enter Phone #: ###-#### Inspection requested via web by Zane Robertson Ok final.
|
ELE17-03673
| Final | 1/24/2018 | 1/25/2018 | 1/25/2018 11:02:35 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by steve cooper Ok final. There are 2-3/0 light boxes in ceiling above tub in master bath. Light boxes DO have blank covers. Electrical contractor spoke to homeowners and said that he would not hang cord and chain fixtures over the tub. 410.10(D). Pendants or cord and chain hung fixtures need to be atleast 3ft away from inside edge of tub horizontally, and 8ft vertically. There were 2 cord and chain fixtures in the utility that were marked mstr bath. No fixtures were installed above tub when I finaled it out.
|
ELE18-00001
| Final | 1/24/2018 | 1/25/2018 | 1/25/2018 10:51:53 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by steve cooper Ok final floor heat.
|
ELE18-00004
| Rough-In Permanent Service | 1/24/2018 | 1/25/2018 | 1/25/2018 10:26:08 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Todd Hall p/s u/g n ok
|
ELE17-04074
| Final | 1/24/2018 | 1/25/2018 | 1/25/2018 10:25:45 AM | A | PASS |
|
|
CODE 1234 Phone #: ###-#### Inspection requested via web by Bob Glenn Ok final.
|
ELE18-00126
| Final | 1/24/2018 | 1/25/2018 | 1/25/2018 9:09:58 AM | A | PASS |
|
|
Pls contact Spencer (Foreman) @ ###-#### or Barry (Electrician) @ ###-#### one hr prior or if you have any questions. Thank you. Inspection requested via web by Rob Maes Ok final. Meter and solar disc located on NE corner of house.
|