Inspections for the day of: Friday, November 15, 2019.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorMark Moncarr
TitleELE-INSPECTOR
Phone #685-9023
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE17-03835 ELE-Aging Inspection11/15/201911/15/201911/19/2019 5:12:31 AM DONE
Please schedule a final inspection.
ELE19-03230 Final11/15/201911/15/201911/15/2019 2:57:48 PMPPASS
Will be open, HO live on site Phone #: ###-#### Inspection requested via web by Darryn Coburn Ok final. Hood and DW cord and plug.
ELE19-03949 Electrical Rough-In11/15/201911/15/201911/15/2019 1:47:58 PMPNR
Phone #: ###-#### Inspection requested via web by Justin Yount Will need to have double layer 5/8 installed for exterior cans. Must not cover until inspected.
ELE19-04439 Temporary Service11/15/201911/15/201911/15/2019 1:30:31 PMPPASS
This Ia Already To Go Lot Is Above The Address That Comes Up on GPS Please Call With Any Issues Phone #: ###-#### Inspection requested via web by jason shifflett t/s o/h n ok
ELE19-03949 Permanent Service11/15/201911/15/201911/15/2019 1:05:25 PMPPASS
p/s u/g n ok
ELE19-04402 Final11/14/201911/15/201911/15/2019 11:47:14 AMAPASS
House is vacant, key is under the planter, but someone should be there. Call Fred with any questions at ###-####. Chip should be there his number is ###-#### Phone #: ###-#### Inspection requested via web by Clayton Morgan Ok final. Breaker correct size.
ELE19-04402 Electrical Rough-In11/14/201911/15/201911/15/2019 11:46:51 AMAPASS
House is vacant, key is under the planter, but someone should be there. Call Fred with any questions at ###-####. Chip should be there his number is ###-#### Phone #: ###-#### Inspection requested via web by Clayton Morgan Ok cover. Weather rated fittings, proper wire size.
ELE19-03963 Electrical Rough-In11/14/201911/15/201911/15/2019 11:46:13 AMAPASS
Contact: Derrick Kamper ceiling inspection please Phone #: ###-#### Inspection requested via web by Deb Gooden Ok cover ceilings 3rd floor N and S side offices.
ELE19-04350 Rough-In Permanent Service11/14/201911/15/201911/15/2019 10:29:44 AMAPASS
Inspection requested via web by ERIC CENTERS Ok cover. p/s u/g n ok
ELE19-02061 Final11/14/201911/15/201911/15/2019 9:51:12 AMAPART
Mark Phone #: ###-#### This is NOT a TCO. House checked out fine. Garage needs finished to allow a C of O. A few areas need addressed.
1. Lockout for hood, and a GFI to right of FP upsairs.
2. A few blanks installed because fixtures are not in yet. There is a blank above mstr tub. Blank must remain in place at final. Cord hanging, pendant, or chain hung fixtures not allowed in this area. Furniture in garage can be moved inside home. Nobody is to reside in home until a final inspection is completed.
MIS19-00380 ELE-Conference11/15/201911/15/201911/15/2019 9:42:25 AMAFAIL
New 70sq ft bump out added to front of dwelling. No permits for all trades pulled. Possible work done to plumb and mech a long with elec.
1. Exterior light is needed beside new exterior door. There is an existing light at entry door, but far enough away that it will not provide proper lighting for carport area.
2. Exterior receptacle needed on new addition.
3. Light needed upon entry of new mudroom. Would be considered hall or storage area.