Inspections for the day of: Thursday, December 15, 2016.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorMark Moncarr
TitleELE-INSPECTOR
Phone #685-9023
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE12-02116 ELE-Aging Inspection12/15/201612/15/201612/20/2016 7:09:05 AM DONE
Talked to contractor, said he was going to call for final
ELE12-02205 ELE-Aging Inspection12/15/201612/15/201612/15/2016 12:47:17 PM DONE
###-#### non working no.
ELE16-04032 Electrical Rough-In12/15/201612/15/201612/15/2016 12:22:03 PMPPASS
rough in of walls Phone #: ###-#### Inspection requested via web by Tom Jenkins ok cover
ELE16-04038 Electrical Rough-In12/15/201612/15/201612/15/2016 12:04:27 PMPPASS
Phone #: ###-#### Inspection requested via web by John VanZandt ok cover
ELE16-03982 Final12/14/201612/15/201612/15/2016 11:35:36 AMAPASS
Please Call Jordan at ###-#### Prior To Arriving. Phone #: ###-#### Inspection requested via web by Louis Keller final ok
ELE16-03982 Permanent Service12/15/201612/15/201612/15/2016 11:35:14 AMPPASS
Please Call Jordan at ###-#### Prior To Arriving. Phone #: ###-#### Inspection requested via web by Louis Keller p/s u/g n ok
ELE16-03990 Electrical Rough-In12/14/201612/15/201612/15/2016 10:58:05 AMAPASS
Please Call Me And Ill meet You There And Go Over This Wonderful Job! Thanks So Much Dave ###-#### Phone #: ###-#### Inspection requested via web by jason shifflett ok cover
ELE16-04027 Rough-In Permanent Service12/14/201612/15/201612/15/2016 10:39:43 AMAPASS
Phone #: ###-#### Inspection requested via web by Dustin Kuester p/s u/g n ok
ELE16-04030 Rough-In Permanent Service12/14/201612/15/201612/15/2016 10:39:17 AMAPASS
Phone #: ###-#### Inspection requested via web by Dustin Kuester p/s u/g n ok
ELE16-03213 Final12/14/201612/15/201612/15/2016 10:05:18 AMPCANC
home owner ###-####, Pat Miller ###-#### Phone #: ###-#### Inspection requested via web by PAT MILLER Talked to contractor, homeowner will not be there, will schedule for next week
ELE16-03186 Final12/14/201612/15/201612/15/2016 9:05:12 AMAFAIL
Michael Phone #: ###-####
1. 424.44(G) Heated floors in all baths need GFI protection.
2. Outlet on front and back of house need to be Weather Resistant outlets.
3. Single pole lockout for hood in kitchen.
4. Lockouts for both ovens.
5. 2 outlets downstairs N. wall show open ground.
6. 210.8(A)(7) All outlets within 6' of sink in downstairs mechanical room need GFI protection.