ELE18-04835
| Electrical Rough-In | 2/11/2019 | 2/12/2019 | 2/12/2019 2:07:56 PM | P | PASS |
|
|
We are laying a special floor down on the yoga room and would like to drop ceiling tiles in there before. It will be a partial inspection, if thats ok. I will be there till 4 PM and will try to get you as much area I can so you can look while you are there. Thank you Phone #: ###-#### Inspection requested via web by Shawn Case Ok cover ceiling in yoga studio.
|
ELE18-03769
| Final | 2/12/2019 | 2/12/2019 | 2/12/2019 1:20:59 PM | P | FAIL |
|
|
Thank you Phone #: ###-#### Inspection requested via web by Eric Brown All electrical work associated with home is good. A/C disconnects for mini split system needs corrections made by heating company. In disc to right, neutral wires need identified as hot conductors. NM cable in left disc cannot be used in outdoor damp or wet locations. Bushing also need for wires exiting wall into disc. Western Heating and Air were the installers.
|
ELE19-00510
| Electrical Rough-In | 2/12/2019 | 2/12/2019 | 2/12/2019 12:21:20 PM | P | PART |
|
|
Phone #: ###-#### Inspection requested via web by Matthew White Ok cover kitchen. 1 outlet each were added to each side of cooktop. 1 outlet added to backside of peninsular facing into dining.
|
ELE19-00508
| Electrical Rough-In | 2/12/2019 | 2/12/2019 | 2/12/2019 11:24:20 AM | P | PASS |
|
|
listing inspection for solar panels Phone #: ###-#### Inspection requested via web by Ryan King Ok cover. Verified UL listing of components.
|
ELE14-02862
| Final | 2/12/2019 | 2/12/2019 | 2/12/2019 11:11:53 AM | P | PASS |
|
|
Talked to Terry with Stephens Electric on 2/12/19. Drove to site and verified that house was demolished and a new home is now on property.
|
ELE15-00807
| ELE-Aging Inspection | 2/12/2019 | 2/12/2019 | 2/12/2019 9:54:39 AM | | DONE |
|
|
Left card at front door location stating that floor heat in mstr bath needed inspected after contractor install for previous homeowners.
|
ELE17-03800
| Final | 2/11/2019 | 2/12/2019 | 2/12/2019 9:39:15 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Don Conley Ok final. During RI stage the electrical contractor brought it to the attention of the builder and homeowner to trim tree on alley side of house. IDP's service drop was re-run over the top, and laying on, a large tree branch.
|
ELE15-00884
| ELE-Aging Inspection | 2/12/2019 | 2/12/2019 | 2/12/2019 9:02:01 AM | | FAIL |
|
|
Correction not made. Bond lug inside pole base is not utilized. Needs bonded as per previous inspection by Eric Storey.
|
ELE15-00849
| ELE-Aging Inspection | 2/12/2019 | 2/12/2019 | 2/12/2019 8:48:56 AM | | DONE |
|
|
Talked to Lewis and Jessica on 2/12/19. Jessica is trying to contact proper personnel to gain access to water feature. Original contact at location no longer works there.
|
ELE16-00683
| Final | 2/11/2019 | 2/12/2019 | 2/12/2019 8:25:55 AM | A | CANC |
|
|
Steve-Eric you may not need to go herebecause you finaled this but it did not close the case can you please doc final. if you need to go out there please call Steve Phone #: ###-#### Talked to homeowner. Re-scheduled for the 14th
|