Inspections for the day of: Tuesday, February 25, 2020.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorMark Moncarr
TitleELE-INSPECTOR
Phone #685-9023
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE20-00375 Final2/25/20202/25/20202/25/2020 2:20:27 PMPPASS
Phone #: ###-#### Inspection requested via web by Scott Campbell Ok final. AFC located on inside of door.
ELE20-00494 Electrical Rough-In2/25/20202/25/20202/25/2020 1:46:23 PMPPASS
Floor heat 2 baths Ok cover flr heat 2 baths
ELE19-03017 Electrical Rough-In2/25/20202/25/20202/25/2020 12:44:12 PMPPASS
GYM CEILING Phone #: ###-#### Inspection requested via web by Debby Pierce Ok cover gym ceiling
ELE20-00079 Final2/24/20202/25/20202/25/2020 12:02:31 PMAPASS
Phone #: ###-#### Inspection requested via web by shane miller Ok final.
ELE19-04524 Final2/25/20202/25/20202/25/2020 11:31:16 AMPPASS
Lockbox code is 1111, installed lockout on hood Phone #: ###-#### Inspection requested via web by Dan Hobdey Lockout installed for hood.
ELE20-00494 Conference2/25/20202/25/20202/25/2020 11:24:49 AMPCANC
Floor heat in all Bathrooms Phone #: ###-#### Inspection requested via web by Kevin Heideman Changed to RI inspection for 2 baths
ELE20-00659 Temporary Service2/25/20202/25/20202/25/2020 10:49:39 AMPPASS
Phone #: ###-#### Inspection requested via web by Kevin Heideman t/s u/g n ok
ELE20-00660 Temporary Service2/25/20202/25/20202/25/2020 10:48:59 AMPPASS
Phone #: ###-#### Inspection requested via web by Kevin Heideman t/s u/g n ok
ELE20-00661 Temporary Service2/25/20202/25/20202/25/2020 10:48:06 AMPPASS
Phone #: ###-#### Inspection requested via web by Kevin Heideman t/s u/g n ok
ELE20-00229 Final2/24/20202/25/20202/25/2020 10:22:58 AMAFAIL
Ran 6 dedicated circuits for mini splits and replaced lighting throughout units. Units are vacant code for doors is 123456 call with any questions thanks! Phone #: ###-#### Inspection requested via web by Trevor Soesbe
1. Service recepts required for AC units on both sides of structure.
2. Remove and replace all non weather proof boxes and flex on back of structure with weather rated items.
3. For each sub panel on same structure with meter pack, assure 4 wire system and install 2 grd rods and grounding electrode conductor.
4. Weather rated labels for each AC disconnect confirming apt number.
ELE20-00576 Permanent Service2/24/20202/25/20202/25/2020 10:10:43 AMAPASS
Ready for inspection Phone #: ###-#### Inspection requested via web by Casey Fouts Where overhead service drop will be attached at new service location, as close as the pole is the drop should be easily be 12' over residential property. p/s o/h n ok
ELE19-00947 Electrical Rough-In2/24/20202/25/20202/25/2020 9:16:14 AMAPASS
Andy Phone #: ###-#### Ok cover hardlid in vestibule 1st floor W entrance.
ELE20-00652 Electrical Rough-In2/24/20202/25/20202/25/2020 9:07:43 AMAPASS
The contractor will be on site for access. Access to the area under constuction is a man door on the left side of the home. Phone #: ###-#### Inspection requested via web by Jonathan Poot Ok cover outside wall on S side of house to right of fireplace.