Inspections for the day of: Thursday, July 16, 2020.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorMark Moncarr
TitleELE-INSPECTOR
Phone #685-9023
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE20-01669 Final7/16/20207/16/20207/16/2020 1:48:29 PMPPASS
Phone #: ###-#### Inspection requested via web by John VanZandt Ok final.
ELE20-02428 Electrical Rough-In7/16/20207/16/20207/16/2020 1:16:10 PMPPASS
Underground conduit for pool install before foundation backfill Phone #: ###-#### Inspection requested via web by Therrin Robertson Ok cover grd work
ELE20-02348 Permanent Service7/9/20207/16/20207/16/2020 12:34:05 PMPPASS
There will be guys there working. If you have any questions please feel free to contact Andrew ###-####. Thanks!! Phone #: ###-#### Inspection requested via web by Clayton Morgan p/s o/h rec ok
ELE20-02425 Electrical Rough-In7/16/20207/16/20207/16/2020 12:33:11 PMPPASS
For access call Jaman 30 minutes before inspection Phone #: ###-#### Inspection requested via web by Terry Scott Ok cover kitchen, living wall with fireplace. Outlet needed to left of fireplace upon final.
ELE20-02418 Final7/15/20207/16/20207/16/2020 11:33:50 AMAFAIL
2 separate garages off of exiting services for residences.
Phone #: ###-#### Inspection requested via web by Kendra Lanham Power to existing detached garage with 2 seperate vehicle bays for renters is running overhead at a height of about 8ft. Needs to follow 225.17-.19 for overhead feeder masts. Contractor said would probably go underground instead. Also needs a single pole disconnect for each seperate space before equiptment.
ELE20-01994 Electrical Rough-In7/16/20207/16/20207/16/2020 11:31:58 AMPCANC
Underground. Phone #: ###-#### >> Inspection requested via web by Andy Chambers Inspection cancelled from web by: Andy Chambers
ELE20-00529 Final7/15/20207/16/20207/16/2020 11:31:35 AMAPASS
Phone #: ###-#### Inspection requested via web by Greg Idsinga Ok final. Waiting for lights to come in. There are roughly 12-14 keyless fixtures with lamps installed. As per 410.22, this is considered a complete installation.
ELE20-02380 Electrical Rough-In7/15/20207/16/20207/16/2020 10:37:09 AMAPASS
Andrew is the contact person Phone #: ###-#### Inspection requested via web by David Green Ok cover areas listed.
ELE20-02406 Electrical Rough-In7/15/20207/16/20207/16/2020 9:38:52 AMAPASS
Covered patio rough in. NMB is stubbed in for can lights, but can lights will not installed until after the fire boxes are built and fire taped. the whole box will be open after drywall for inspection of cans later. Thank you Phone #: ###-#### Inspection requested via web by Steve Blackmer Ok cover back porch. Double layer boxes are in place for recess cans.
ELE20-00405 Permanent Service7/15/20207/16/20207/16/2020 9:24:03 AMAPASS
Phone #: ###-#### Inspection requested via web by Robert Murray p/s o/h n ok