Inspections for the day of: Wednesday, July 3, 2019.
Number of inspections: 14
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorMark Moncarr
TitleELE-INSPECTOR
Phone #685-9023
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE19-02009 Final7/2/20197/3/20197/3/2019 1:55:08 PMAPASS
Phone #: ###-#### Inspection requested via web by mark hood Ok final. GFI functions properly.
ELE19-02008 Final7/2/20197/3/20197/3/2019 1:54:43 PMAPASS
Phone #: ###-#### Inspection requested via web by mark hood Ok final.
ELE19-02408 Electrical Rough-In7/3/20197/3/20197/3/2019 1:27:34 PMPPASS
Wall cover. Randy is the contact. Phone #: ###-#### Inspection requested via web by Buster Bowen Ok cover 1 wall. W down hallway to double doors on S side.
ELE19-02154 Permanent Service7/3/20197/3/20197/3/2019 12:56:50 PMPPASS
Please inspect as soon after lunch as possible, so we can get Idaho power to rehook. Thanks Phone #: ###-#### Inspection requested via web by Barbara Szurgot p/s u/g n ok
ELE19-00798 Final7/2/20197/3/20197/3/2019 11:34:57 AMAPASS
Key is on the meter base
Call Jason with any questions at ###-####421 Phone #: ###-#### Inspection requested via web by Clayton Morgan Ok final. 2 pole 15 max fuse on mini split.
ELE19-02192 Permanent Service7/2/20197/3/20197/3/2019 11:16:05 AMAPASS
It will be open. If you have any questions please feel free to contact Tony ###-####. Thanks!! Phone #: ###-#### Inspection requested via web by Clayton Morgan p/s o/h n ok
ELE19-02054 Final7/2/20197/3/20197/3/2019 10:24:20 AMAPASS
LB 5150. If you have any questions please feel free to contact Darren ###-####. Thanks!! Phone #: ###-#### Inspection requested via web by Clayton Morgan Ok final.
ELE19-01464 Final7/2/20197/3/20197/3/2019 10:12:11 AMAFAIL
nick is the point of contact. Phone #: ###-#### Inspection requested via web by A.M.E. Office 2 recepts in medicine cabinets, and GFI in quad need to be tamper resistant.
ELE19-01928 Conference7/1/20197/3/20197/3/2019 9:37:57 AMADONE
William Phone #: ###-#### Discussed pulling GEC out of meter and re-routing to panel. A few locations where wires stapled above boxes need to be moved more to center of stud. Wires need to be 1-1/4 away from face of stud. A few locations where 14/2 is used along with 12/2 need to be breakered at a maximum of 15a.
ELE19-01928 Rough-In Permanent Service7/1/20197/3/20197/3/2019 9:34:58 AMACANC
I would like the inspection as early as possible on the 3rd. I have a flight from Boise at 12:30 pm. Thank you very much Phone #: ###-#### Inspection requested via web by Marisa Weppner
ELE19-02364 Electrical Rough-In7/2/20197/3/20197/3/2019 9:18:59 AMAPASS
Brian Prussia is best contact Phone #: ###-#### Inspection requested via web by BRS Permitting Items UL listed.
ELE19-00786 Final7/2/20197/3/20197/3/2019 9:18:20 AMAPASS
Garage code is 2458 Phone #: ###-#### Inspection requested via web by Kevin Heideman Ok final.
ELE19-02480 Rough-In Permanent Service7/2/20197/3/20197/3/2019 8:39:52 AMAPASS
Phone #: ###-#### Inspection requested via web by Ryan Schaffer p/s u/g n ok
ELE17-02286 Final7/2/20197/3/20197/3/2019 5:55:53 AMAPASS
Phone #: ###-#### Inspection requested via web by Kendra Lanham This is to close out RI. Homeowner pulled permit to do trim out themselves. ELE19-02427.