ELE18-04543
| Final | 1/22/2019 | 1/22/2019 | 1/22/2019 4:36:20 PM | P | PASS |
|
|
Inspection requested via web by BRS Permitting Labelling, disconnect, and OCPD ok
|
ELE18-04543
| Electrical Rough-In | 1/22/2019 | 1/22/2019 | 1/22/2019 4:35:03 PM | P | PASS |
|
|
Inspection requested via web by BRS Permitting UL listing verified by paper work..no acess to roof
|
ELE18-04386
| Final | 1/22/2019 | 1/22/2019 | 1/22/2019 4:18:01 PM | P | PASS |
|
|
Casey Phone #: ###-####...ok to final
|
ELE18-04135
| Final | 1/22/2019 | 1/22/2019 | 1/22/2019 4:01:37 PM | P | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Jonathan Poot... 1..panel shall be labelled to its clear and specific circuit 2..all outlets in bathrooms shall have GFCI protection 3..outlets in bath ship lap need spark rings 4..outlets without ground shall have GFCI protection or 2 wire outlets installed
|
ELE19-00203
| Electrical Rough-In | 1/21/2019 | 1/22/2019 | 1/22/2019 3:25:05 PM | P | PASS |
|
|
Electrical underground for new charging stations. Phone #: ###-#### Inspection requested via web by Kevin Perez... ok to cover
|
ELE19-00257
| Final | 1/22/2019 | 1/22/2019 | 1/22/2019 3:22:53 PM | P | NR |
|
|
Brent Phone #: 208-###-####...need meter set first...perm service rescheduled to next day
|
ELE19-00257
| Permanent Service | 1/22/2019 | 1/22/2019 | 1/22/2019 3:19:52 PM | P | CANC |
|
|
Brent Phone #: 208-###-####...rescheduled to next day...contractor ok'ed
|
ELE14-00724
| ELE-Aging Inspection | 1/22/2019 | 1/22/2019 | 1/22/2019 3:14:53 PM | | CANC |
|
|
too busy
|
ELE14-00717
| ELE-Aging Inspection | 1/22/2019 | 1/22/2019 | 1/22/2019 3:14:40 PM | | CANC |
|
|
too busy
|
ELE13-02178
| ELE-Aging Inspection | 1/22/2019 | 1/22/2019 | 1/22/2019 3:14:28 PM | | CANC |
|
|
too busy
|
ELE13-00855
| ELE-Aging Inspection | 1/22/2019 | 1/22/2019 | 1/22/2019 3:14:07 PM | | CANC |
|
|
too busy
|
ELE19-00264
| Conference | 1/22/2019 | 1/22/2019 | 1/22/2019 3:06:24 PM | P | PASS |
|
|
Please call before you stop by and I''ll meet you there. Phone #: ###-#### Inspection requested via web by Seth Olsen... discussed kitchen addition...homeowner has done work before
|
ELE19-00250
| Rough-In Permanent Service | 1/21/2019 | 1/22/2019 | 1/22/2019 2:20:32 PM | P | PASS |
|
|
repacing a fuse panel box and will need re-energized by afternoon Phone #: ###-#### Inspection requested via web by Andy Derrick... p/s o/h reconnect ok service will be changed out at later date...interior fuse panel update at this time only
|
ELE19-00250
| Electrical Rough-In | 1/22/2019 | 1/22/2019 | 1/22/2019 2:19:20 PM | P | PASS |
|
|
repacing a fuse panel box and will need re-energized by afternoon Phone #: ###-#### Inspection requested via web by Andy Derrick... service has no disconnect at meter..new o/h service with disconnect needs installed and grounding brought up to code...contractor is aware of...need to get power restalled for changing out fuse panel first
|
ELE19-00245
| Rough-In Permanent Service | 1/21/2019 | 1/22/2019 | 1/22/2019 1:55:27 PM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Dylan Pierce... rough ok to cover p/s o/h new ok
|
ELE18-04361
| Final | 1/18/2019 | 1/22/2019 | 1/22/2019 1:31:42 PM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Kevin Perez...ok to final
|
ELE18-04697
| Final | 1/18/2019 | 1/22/2019 | 1/22/2019 1:07:35 PM | A | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Krista Ratterree... meter must be installed and power on before final can be scheduled and inspected
|
ELE19-00246
| Temporary Service | 1/21/2019 | 1/22/2019 | 1/22/2019 12:55:42 PM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Neal Rumsey... t/s u/g new ok
|
ELE18-04539
| Final | 1/18/2019 | 1/22/2019 | 1/22/2019 12:41:42 PM | A | PASS |
|
|
Jason Curley is the contact. Scheduling both rough and final at the same time with permission from Daryl Phone #: ###-#### Inspection requested via web by BRS Permitting... Labelling, disconnect, and OCPD ok
|
ELE18-04539
| Electrical Rough-In | 1/18/2019 | 1/22/2019 | 1/22/2019 12:40:25 PM | A | PASS |
|
|
Jason Curley is the contact. Scheduling both rough and final at the same time with permission from Daryl Phone #: ###-#### Inspection requested via web by BRS Permitting... UL listed equipment on roof verified by contractor oked by Daryl UL listed equipment on ground verified
|
ELE18-03288
| Final | 1/18/2019 | 1/22/2019 | 1/22/2019 12:25:00 PM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Heath Thomas... ok to final
|
ELE18-04692
| Final | 1/22/2019 | 1/22/2019 | 1/22/2019 11:50:02 AM | A | PASS |
|
|
Brian Phone #: ###-####... Labelling, disconnect, and OCPD ok
|
ELE18-04692
| Rough-In Permanent Service | 1/17/2019 | 1/22/2019 | 1/22/2019 11:49:24 AM | A | PASS |
|
|
Brian Phone #: ###-####... rough only...perm service not needed UL listed equipment used
|
ELE18-04709
| Final | 1/18/2019 | 1/22/2019 | 1/22/2019 11:37:18 AM | A | PASS |
|
|
Contact Jason Curley. The rough and final are scheduled for the same day with permission from Daryl. Phone #: ###-#### Inspection requested via web by BRS Permitting... Labelling, disconnect, and OCPD ok
|
ELE18-04709
| Electrical Rough-In | 1/18/2019 | 1/22/2019 | 1/22/2019 11:36:40 AM | A | PASS |
|
|
Contact Jason Curley. The rough and final are scheduled for the same day with permission from Daryl. Phone #: ###-#### Inspection requested via web by BRS Permitting... UL listed equipment
|
ELE19-00216
| Permanent Service | 1/18/2019 | 1/22/2019 | 1/22/2019 11:17:18 AM | A | PASS |
|
|
Please contact me as soon as its done Phone #: ###-#### Inspection requested via web by Thomas wilson... p/s u/g new ok
|
ELE19-00125
| Electrical Rough-In | 1/18/2019 | 1/22/2019 | 1/22/2019 11:17:18 AM | A | PASS |
|
|
Requesting 8:00 am inspection time. Contact Chris @ ###-####. Phone #: ###-#### Inspection requested via web by Ken Olsen... UL listed equipment verified...removing neon to LED lighting using existing power
|
ELE18-04114
| Final | 1/21/2019 | 1/22/2019 | 1/22/2019 11:17:17 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Kerri Hamilton...ok to final
|
ELE19-00125
| Final | 1/22/2019 | 1/22/2019 | 1/22/2019 11:17:17 AM | A | PASS |
|
|
Requesting 8:00 am inspection time. Contact Chris @ ###-####. Phone #: ###-#### Inspection requested via web by Ken Olsen... ok to final
|
ELE19-00143
| Electrical Rough-In | 1/18/2019 | 1/22/2019 | 1/22/2019 10:24:58 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Lee Long... rough ok to cover basement and added workroom
|
ELE18-04767
| Final | 1/21/2019 | 1/22/2019 | 1/22/2019 9:55:10 AM | A | PASS |
|
|
Danny is the contact. Phone #: ###-#### Inspection requested via web by Buster Bowen... ok to final
|
ELE18-04183
| Final | 1/22/2019 | 1/22/2019 | 1/22/2019 9:12:42 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Laurie Hoelscher... UL listing and disconnect...ok to final
|
ELE18-04183
| Electrical Rough-In | 1/16/2019 | 1/22/2019 | 1/22/2019 9:12:06 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Laurie Hoelscher... rough ok
|
ELE17-00783
| Electrical Rough-In | 1/18/2019 | 1/22/2019 | 1/22/2019 9:05:38 AM | A | PASS |
|
|
Chris Phone #: ###-####... rough for pool rm...ok to cover
|
ELE18-04354
| Final | 1/22/2019 | 1/22/2019 | 1/22/2019 8:48:12 AM | A | PASS |
|
|
final underground to shop...ok to final
|
ELE19-00089
| Final | 1/21/2019 | 1/22/2019 | 1/22/2019 8:46:55 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Eric Schroeder... ok to final
|
ELE18-04140
| Final | 1/18/2019 | 1/22/2019 | 1/22/2019 8:34:10 AM | A | PASS |
|
|
There will be someone home. If you have any questions please feel free to contact Darren ###-####. Thanks!!! Phone #: ###-#### Inspection requested via web by Clayton Morgan.. corrections made...ok to final
|
ELE18-04491
| Final | 1/18/2019 | 1/22/2019 | 1/22/2019 8:23:24 AM | A | PASS |
|
|
garage code 2468 Phone #: ###-#### Inspection requested via web by Darryn Coburn.. ok to final
|
ELE19-00204
| Temporary Service | 1/18/2019 | 1/22/2019 | 1/22/2019 7:56:37 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Darryn Coburn... t/s u/g new ok
|