Inspections for the day of: Wednesday, October 17, 2018.
Number of inspections: 14
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTom Saunders
TitleELE-INSPECTOR
Phone #208-794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE18-03560 Electrical Rough-In10/11/201810/17/201810/17/2018 2:49:05 PMPPASS
Please call Mitch, the foreman, when you are on your way ###-#### Phone #: ###-#### Inspection requested via web by Ashley White...
UL listed equipment...30A breaker installed in panel...will need access for final
ELE14-00813 Final10/17/201810/17/201810/17/2018 2:42:00 PMPPASS
no corrections at time of perm service inspection
ELE14-00855 Final10/17/201810/17/201810/17/2018 2:39:10 PMPPASS
no corrections at time of permanent service inspection
ELE14-00913 ELE-Aging Inspection10/17/201810/17/201810/17/2018 2:38:01 PM PASS
final scheduled
ELE14-00913 Final10/17/201810/17/201810/17/2018 2:37:40 PMPPASS
no corrections at time of permanent service
ELE18-02794 Final10/17/201810/17/201810/17/2018 1:49:57 PMPPASS
Phone #: ###-#### Inspection requested via web by Lynn Cable...ok to final
ELE18-02793 Final10/17/201810/17/201810/17/2018 1:49:56 PMPPASS
Phone #: ###-#### Inspection requested via web by Lynn Cable...ok to final
ELE18-02377 Electrical Rough-In10/16/201810/17/201810/17/2018 12:38:15 PMAPASS
We need a wall rough, Kenny is the site contact.Thank you! Phone #: ###-#### Inspection requested via web by Stacie Tasker...
wall cover ok
ELE18-03739 Final10/16/201810/17/201810/17/2018 12:08:11 PMAPASS
Pls contact Bryce (Foreman) @ ###-#### or George (Electrician) @ ###-#### one hr prior or if you have any questions. Thank you. Inspection requested via web by Rob Maes...
OCPD, disconnect, and labelling ok
ELE18-02651 Final10/16/201810/17/201810/17/2018 11:54:39 AMAPASS
Phone #: ###-#### Inspection requested via web by Thomas Bond...ok to final
ELE18-03781 Final10/12/201810/17/201810/17/2018 11:28:32 AMAPASS
Call Foreman with any questions : Bryce Waterman Phone #: ###-#### Inspection requested via web by Rob Maes...
OCPD, disconnect and labelling ok
ELE18-02300 Electrical Rough-In10/17/201810/17/201810/17/2018 11:04:23 AMAPASS
Bathroom and storage wall cover and vestibule ceiling cover Phone #: ###-#### Inspection requested via web by Jason Parke...ok to cover areas stated
ELE18-00849 Final10/16/201810/17/201810/17/2018 10:39:43 AMAPART
Partial Final Phone #: ###-#### Inspection requested via web by Kerri Hamilton...exterior of building minus electrical rm and half of warehouse up to dividing wall...ok
GFI protection need added for outlets in wash rm
ELE18-02503 Final10/16/201810/17/201810/17/2018 9:37:03 AMAFAIL
Ready for re-inspect of industrial equipment Phone #: ###-#### Inspection requested via web by Paula Gratiot...
1..correct breaker for compressor needs installed-3 phase
2..supports need added to compressor feeds
3..junction box at laser needs addressed-bonded, blank, and KO seal
3..paint booth breaker needs labeled and verified correct size-paper work on booth
4..relocated panel needs labelling completed
5..new drops at poles need GFI protection 110 and 220 up to 50A
6..Boise City ordinance-no violation shall be retaind...visible code violations need fixed-existing panels need labelling, KOs need installed at multiple locations, GFI protection in existing 110 outlets