Inspections for the day of: Friday, October 4, 2019.
Number of inspections: 17
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTom Saunders
TitleELE-INSPECTOR
Phone #208-794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE19-03644 Permanent Service10/3/201910/4/201910/4/2019 2:48:34 PMPPASS
Service upgrade : Going from 100 Amp service to 200 Amp service : Idaho Power will not be out to shut Power off till 1:00 pm they need inspection done before 4 before to turn Power back on Please !! Phone #: ###-#### Inspection requested via web by Charles Davis...
p/s u/g reconnect ok
ELE19-03498 Electrical Rough-In10/4/201910/4/201910/4/2019 2:15:43 PMPPASS
Phone #: ###-#### Inspection requested via web by Seth Stears...
UL listing verified
lineside connection
accessible from outside...no one needs to be present for final
ELE19-03789 Temporary Service10/4/201910/4/201910/4/2019 1:51:56 PMPPASS
Temporary power pole that had to be relocated. Mike will be the contact. Pole is ready for power. Phone #: ###-#### Inspection requested via web by Deb Ipsen..t/s o/h new ok
ELE19-03613 Electrical Rough-In10/3/201910/4/201910/4/2019 1:19:43 PMPPASS
Inspection of underground trench from transformer to new panel location. Road portion (1/3 of trench) has been fill in for Idaho Power traffic. Remainder of trench and both ends are open for inspection. Call Dustin Palmer for gate access if needed. Phone #: ###-#### Inspection requested via web by Tod Lane...
ok to cover...verified depth by pictures as time constraints and trench needing back filled
ELE19-03797 Temporary Service10/4/201910/4/201910/4/2019 12:33:37 PMPPASS
Changed out overhead temp pole per Idaho Power Phone #: ###-#### Inspection requested via web by Jay VanSchoiack..t/s o/h new ok
ELE19-03794 Final10/4/201910/4/201910/4/2019 12:17:08 PMPPASS
New AC circuit added on exterior of garage west wall. Panel in garage.
Street name is actually Trail Circle but city system only shows it as Trail Cir. Phone #: ###-#### Inspection requested via web by David McClellan...ok to final
ELE19-03790 Final10/3/201910/4/201910/4/2019 11:52:58 AMAFAIL
Fransisco-service off longer than 1 year-call office to get directions to the meter Phone #: ###-####...
electrical contractor needs to be hired
multiple corrections need done to service panel
ELE19-03055 Final10/3/201910/4/201910/4/2019 11:26:52 AMANR
Randy Phone #: ###-#### Inspection requested via web by Sean DeLacy...needed conference ..overviewed GFCI requirement for recepticles
ELE19-02736 Final10/3/201910/4/201910/4/2019 10:48:30 AMAFAIL
Garage code is 5477 Phone #: ###-#### Inspection requested via web by Ryan Wilson...
1) romex shall be protected from physical damage-island D/W
2) switch plate needs installed...patio switch dining rm
3) outlets need added in pantry...shall be installed so that no point along the wall line is more than 24 inces - 210.52(C)(1)
ELE19-03793 Rough-In Permanent Service10/4/201910/4/201910/4/2019 10:35:50 AMAFAIL
Its All Ready For You Thanks And Have A Great Day! Phone #: ###-#### Inspection requested via web by jason shifflett...
listed on correction notice...contractor aware
ELE17-00694 ELE-Aging Inspection10/4/201910/4/201910/4/2019 9:48:23 AM PASS
still under construction
ELE19-03784 Conference10/3/201910/4/201910/4/2019 9:44:50 AMAPASS
Call ahead // Dave Phone #: ###-####...
discussed placement and wiring of hot tub...tempered windows and bonding of rain cutter and gazebo
ELE19-03258 Permanent Service10/3/201910/4/201910/4/2019 9:16:04 AMPCANC
Please call before arriving our electrician will be on site. Thank you! Phone #: ###-#### >> Inspection requested via web by BRS Permitting Inspection cancelled from web by: BRS Permitting
ELE19-03792 Temporary Service10/4/201910/4/201910/4/2019 8:33:09 AMAPASS
Its All Ready To Go Thanks Dave Phone #: ###-#### Inspection requested via web by jason shifflett...t/s u/g new ok
ELE19-03476 Final10/4/201910/4/201910/4/2019 8:18:27 AMAPASS
Phone #: ###-#### Inspection requested via web by Brad Girard...grid ceiling ok to cover and ok to final
ELE19-01582 Temporary Service10/3/201910/4/201910/4/2019 8:06:55 AMACANC
Temporary power pole that had to be relocated.Shannon will be the contact. Phone #: ###-#### Inspection requested via web by Deb Ipsen...wrong permit used for temp service...will need to open another permit bor original temp service permit...call city of Boise
ELE19-02683 Final10/2/201910/4/201910/3/2019 8:48:57 AMPCANC
Phone #: ###-#### >> Inspection requested via web by Robert Murray Inspection cancelled from web by: Robert Murray