Inspections for the day of: Wednesday, November 14, 2018.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTom Saunders
TitleELE-INSPECTOR
Phone #208-794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE18-03561 Final11/13/201811/14/201811/14/2018 3:16:48 PMPFAIL
Ben Phone #: ###-####..
1..panel shall be legibly identified as to its clear and specific purpose or use..408.4
2..closet lights too close to closet shelf or rod..410.16
3..riser shall be strapped within 3ft of meter
4..sealtite shall be strapped within 8" of disconnect
ELE17-00783 Electrical Rough-In11/14/201811/14/201811/14/2018 2:29:06 PMPCANC
Chris Phone #: ###-####...homeowner unable to meet in afternoon and was late scheduling for morning. Was unable to make inspection in AM so homeowner said will reschedule for friday when has day off
ELE18-04381 Permanent Service11/14/201811/14/201811/14/2018 2:15:57 PMPPASS
office number -###-#### Mike is the Electrician on site Phone #: ###-#### Inspection requested via web by Matthew White..
verify at final eddison circuits on 2-pole breakers and clearance of 3ft is infront of panel
p/s u/g reconnect ok
ELE17-03257 Final11/14/201811/14/201811/14/2018 2:04:08 PMPFAIL
Rocky- Phone #: ###-####...
Bad GFI breaker on exterior oitlets
ELE18-04336 Electrical Rough-In11/13/201811/14/201811/14/2018 1:42:31 PMPPASS
Taylor Barton Contact Phone #: ###-#### Inspection requested via web by BRS Permitting..
UL listed equipment
line side tap...panel in backyard...will need access for final
ELE18-04131 Electrical Rough-In11/14/201811/14/201811/14/2018 1:20:55 PMPPASS
Please do a cover inspection for the Kitchen areas! Thx. Steve, Phone #: ###-#### Inspection requested via web by Steven Meredith..
phase 2 of remodel...kitchen ok to cover
ELE18-04372 Permanent Service11/14/201811/14/201811/14/2018 12:50:28 PMACANC
meet homeowner gary grey at 8AM to go over service...rescheduled wrong day
ELE18-04372 Permanent Service11/13/201811/14/201811/14/2018 12:49:50 PMACANC
new fuse box on South side of bulding // Gary Gray Phone #: ###-####....
rescheduled for 11/15/18 AM
ELE18-04371 Electrical Rough-In11/13/201811/14/201811/14/2018 9:59:15 AMAPASS
new outlets added on new wall Phone #: ###-#### Inspection requested via web by Barbara Szurgot...office new wall...1 outlet, new walls reworked...ok to cover
ELE18-02698 Electrical Rough-In11/13/201811/14/201811/14/2018 9:36:32 AMAFAIL
Paul (Pavel) Phone #: ###-####...
1..junctionboxes shall be completely closed
2..wires shall be stapled within 8" of box and 4.5ft there after
3..all wires shall be ran and stapled as needed for future island circuits
ELE18-04379 Temporary Service11/13/201811/14/201811/14/2018 8:52:38 AMAPASS
Phone #: ###-#### Inspection requested via web by Neal Rumsey...t/s u/g new ok
ELE18-04378 Temporary Service11/13/201811/14/201811/14/2018 8:52:14 AMAPASS
Phone #: ###-#### Inspection requested via web by Neal Rumsey...t/s u/g new ok
ELE18-02759 Electrical Rough-In11/13/201811/14/201811/14/2018 8:51:49 AMAPASS
This is a cover inspection for the new office space. Also inspecting the service and transformer install. We are at this site starting at 6am. Phone #: ###-#### Inspection requested via web by Aaron Whiteley...
walls of new office ok to cover
service off existing panel with added transformer..ok power on