Inspections for the day of: Monday, November 25, 2019.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTom Saunders
TitleELE-INSPECTOR
Phone #208-794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE19-04489 Final11/25/201911/25/201911/25/2019 3:11:45 PMPFAIL
200amp overhead service Phone #: ###-#### Inspection requested via web by Kendra Lanham...
1) panel needs clear and proper labelling..408.4
ELE19-04496 Permanent Service11/19/201911/25/201911/25/2019 3:00:54 PMPNR
Contact: Matt Cinko Phone #: ###-#### Inspection requested via web by Deb Gooden...
not ready...panel needs lowered, grounding needs updated, and riser needs guide wire kit
ELE19-02828 Rough-In Permanent Service11/22/201911/25/201911/25/2019 1:32:51 PMPNR
Phone #: ###-#### Inspection requested via web by Tom Jenkins...
AFC label needs applied to service before power can be turned on
ELE18-02951 Electrical Rough-In11/22/201911/25/201911/25/2019 12:59:06 PMPPASS
Call 30 mins ahead for access-Albert Phone #: ###-####...rough ok to cover
ELE19-04534 Final11/25/201911/25/201911/25/2019 12:19:56 PMPPASS
Joseph Phone #: ###-####...
labelling, disconnect, and OCPD ok
ELE19-04090 Final11/20/201911/25/201911/25/2019 12:01:53 PMAPASS
Area code 801. Final solar inspection. Plans are on site at inverter. Phone #: ###-#### Inspection requested via web by Ashley Lanham...
labelling, disconnect, and OCPD ok
ELE19-02930 Final11/22/201911/25/201911/25/2019 9:42:06 AMAFAIL
Phone #: ###-#### Inspection requested via web by Zane Robertson...
1) overhead service needs guide wire kit installed...230.28
2) bracing is required for masts that exceed 30"
Idaho Power requirement as well
ELE19-04245 Final11/22/201911/25/201911/25/2019 8:50:12 AMAPASS
Requesting electrical final. Thanks Tim Phone #: ###-#### Inspection requested via web by Tim Lawrence...job complete...ok to final
ELE19-04554 Final11/22/201911/25/201911/25/2019 8:37:03 AMACANC
randy Phone #: ###-####...
perm service inspection required first
power needs on and no code violation shall be retained (exterior light) before final can be given
ELE19-04554 Permanent Service11/25/201911/25/201911/25/2019 8:34:12 AMAPASS
randy Phone #: ###-####...
p/s u/g new ok...comes from meter pack location