Inspections for the day of: Friday, February 1, 2019.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTom Saunders
TitleELE-INSPECTOR
Phone #208-794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE19-00403 Final1/31/20192/1/20192/1/2019 2:00:56 PMPPASS
Phone #: ###-#### Inspection requested via web by Tyler Bowen...ok to final
ELE18-02434 Conference2/1/20192/1/20192/1/2019 1:55:25 PMPPASS
Request to extend permit. Please call Matt if you have questions ###-#### ...ok to final
ELE18-01684 Final2/1/20192/1/20192/1/2019 1:31:08 PMPPASS
call for acess- Danielle Phone #: ###-####..
ok to final
ELE19-00394 Electrical Rough-In1/31/20192/1/20192/1/2019 1:04:04 PMPFAIL
Should all be open Phone #: ###-#### Inspection requested via web by Brad Baker...
1..NM cable ran parallel to framing members shall keep 1 1/4" distance from nearest edge of framing member 300.4(D)
2..where NM cable enters a junction box or device box a minimum of a 1/4 " of sheathing shall be in box- MULTIPLE LOCATIONS..314.17(C)
3..NM cable shall be secured/supported every 4 1/2 ft and within 12" of every cable entry into enclosure-334.30, within 8" of plastic boxes 314.17(C)
4..home runs need stapled within 12" of panel
ELE18-01099 Conference2/1/20192/1/20192/1/2019 11:41:45 AMPPASS
Customer request to extend permit. Call Luke ###-####-6499...spoke with permit holder...hasnt had time to start project...ok to extend permit
ELE18-02665 Permanent Service1/31/20192/1/20192/1/2019 11:00:55 AMANR
PLEASE CONTACT RICH BAIL ON SITE ###-#### Phone #: ###-#### Inspection requested via web by Deb Gooden...
available fault current label required
independent verification of 3 phase 1600V service needs done
all before perm service can be given
ELE18-03531 Final1/31/20192/1/20192/1/2019 10:38:47 AMAFAIL
Duane-please call GC 1 hr prior to meet for access Phone #: ###-####...
exhaust fan/light in shower shall have GFCI protection and be rated to be installed in damp location.
ELE19-00308 Final1/31/20192/1/20192/1/2019 9:46:10 AMAPASS
service change Phone #: ###-#### Inspection requested via web by Calvin Bohrer...
ok to final
ELE19-00297 Final2/1/20192/1/20192/1/2019 9:11:32 AMAPASS
attn Tom Saunders Phone #: ###-#### Inspection requested via web by Caleb Gaylord..
ok to final
ELE19-00407 Electrical Rough-In1/31/20192/1/20192/1/2019 8:53:13 AMAPASS
Inspection requested via web by Same Electric...
rough in kitchen ok to cover