Inspections for the day of: Friday, April 5, 2019.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTom Saunders
TitleELE-INSPECTOR
Phone #208-794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE19-00742 Final4/5/20194/5/20194/5/2019 2:18:28 PMPPASS
Please call 20 minutes prior to arrival Phone #: ###-#### Inspection requested via web by Mike Leonard....
ok to final
ELE18-02459 Final4/5/20194/5/20194/5/2019 2:07:17 PMPPASS
Mucho Phone #: ###-####...
ok to final
ELE19-00990 Final4/4/20194/5/20194/5/2019 1:00:40 PMPPASS
Phone #: ###-#### Inspection requested via web by Kenneth Rhode...ok to final
ELE19-01210 Final4/5/20194/5/20194/5/2019 11:53:00 AMPFAIL
House is vacant and is for sale-lockbox code is 5260 on front door Phone #: ###-#### Inspection requested via web by Same Electric...
1) outlet and light needed at attic fan location..210.70(C)
2) all openings in panels/load centers shall be closed...no code violation shall be retained...furnace load center needs a blank
3) clearances for main panel need addressed...3ft in front and 30" side...cabinet needs addressed around panel
ELE16-02662 ELE-Aging Inspection3/29/20194/5/20194/5/2019 11:05:56 AMAFAIL
contact homeowner to get access...
correction notice posted...requiring action within 30 days
ELE18-01889 Electrical Rough-In4/4/20194/5/20194/5/2019 10:40:19 AMAPASS
wall rough in west building Phone #: ###-#### Inspection requested via web by Debby Pierce...all walls ok to cover
ELE18-02523 Electrical Rough-In4/4/20194/5/20194/5/2019 10:39:04 AMAPASS
2nd. floor hard lid inspection Phone #: ###-#### Inspection requested via web by Debby Pierce...ok to cover
ELE18-04192 Final4/3/20194/5/20194/5/2019 9:58:44 AMAPASS
electrician phone # ###-#### Phone #: ###-#### Inspection requested via web by Matthew White...corrections made ok to final
ELE19-01200 Electrical Rough-In4/4/20194/5/20194/5/2019 9:33:15 AMAPASS
Call Matt on site if any questions, ###-#### Phone #: ###-#### Inspection requested via web by Bryan Atkins...
wall cover and hard lid locations ok to cover
ELE19-01200 Permanent Service4/5/20194/5/20194/5/2019 9:31:59 AMAPASS
Call Matt on site if any questions, ###-#### Phone #: ###-#### Inspection requested via web by Bryan Atkins...
p/s u/g new ok...meter pack east side of building
ELE19-00673 Final4/4/20194/5/20194/5/2019 8:51:50 AMAFAIL
Phone #: ###-#### Inspection requested via web by David Baker...
1) junction box shall be rated for exterior use...weather proof box...110.3
2)junction boxes shall have a cover...314.28(C)
ELE17-00694 ELE-Aging Inspection4/5/20194/5/20194/5/2019 7:24:57 AM PASS
still under construction