ELE20-00730
| Electrical Rough-In | 4/8/2020 | 4/8/2020 | 4/8/2020 3:10:28 PM | P | CANC |
|
|
Tyler **Cleared** Phone #: ###-####...not ready...needed conference
|
ELE20-00730
| Conference | 4/8/2020 | 4/8/2020 | 4/8/2020 3:09:41 PM | P | PASS |
|
|
Tyler **Cleared** Phone #: ###-####... discussed, make up of outlet and switches, GFCI requirement for all receptacles in bathrooms, powering of SD, dining rm circuit requirement, expansion joint at service required to be expanded halfway, 8/3 at panel needs proper connector-not B/A glued to coupling-needs positive crimp on wire, recessed can lighting junction boxes installed at first location of all rooms with recessed can lighting, hot tub wiring completed to exterior both ends
|
ELE20-00889
| Final | 4/8/2020 | 4/8/2020 | 4/8/2020 1:44:02 PM | P | PART |
|
|
Phone #: ###-#### Inspection requested via web by Greg Idsinga.... partial final...temp occupency given full final once panel is labelled so ea circuit has its clear, evident, and specific pupose or use...408.4
|
ELE20-00075
| Electrical Rough-In | 4/8/2020 | 4/8/2020 | 4/8/2020 1:27:32 PM | P | PASS |
|
|
Soffit inspection Phone #: ###-#### Inspection requested via web by Zane Robertson..
exterior soffits and first entry lid ok to cover meter pac and exterior service ok...interior panels need made up for service completion...uffer under stairs discussed LV racking system bonding and main waterline for fire sprinkler system bond
|
ELE20-00770
| Final | 4/8/2020 | 4/8/2020 | 4/8/2020 12:22:50 PM | P | FAIL |
|
|
Final Phone #: ###-#### Inspection requested via web by Greg Idsinga... 1) no low voltage or high volt wiring shall be laying on grid 2) all unused openings and connectors shall be plugged and removed in junction boxes above ceiling
|
ELE20-00886
| Final | 4/7/2020 | 4/8/2020 | 4/8/2020 11:24:50 AM | A | PASS |
|
|
We would appreciate a 30 minute call ahead. Foreman is Ryan Barnes at ###-#### Phone #: ###-#### Inspection requested via web by Kerri Hamilton..ok to final
|
ELE20-00681
| Final | 4/7/2020 | 4/8/2020 | 4/8/2020 10:26:32 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Rodney Monroe..ok to final
|
ELE20-00680
| Final | 4/7/2020 | 4/8/2020 | 4/8/2020 10:26:05 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Rodney Monroe...ok to final
|
ELE20-01234
| Final | 4/7/2020 | 4/8/2020 | 4/8/2020 9:55:13 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Garrett Collins...job complete...disconnect on shed...circuit out of shed panel labelled...ok to final
|
ELE20-00324
| Permanent Service | 4/8/2020 | 4/8/2020 | 4/8/2020 9:38:42 AM | A | PASS |
|
|
Meter main was added at the front of the home, SER ran to existing panel, grounds separated in sub panel, and under re-routed to the meter main. Phone #: ###-#### Inspection requested via web by Dan Jennings... p/s u/g new ok...moved to new location per underground requirement by ID Pwr
|
ELE20-00314
| Permanent Service | 4/8/2020 | 4/8/2020 | 4/8/2020 9:32:08 AM | A | PASS |
|
|
Meter main was added at the front of the home, SER ran to existing panel, grounds separated in sub panel, and under re-routed to the meter main Phone #: ###-#### Inspection requested via web by Dan Jennings... p/s u/g new ok...moved to new location per underground requirement by ID Pwr
|
ELE20-01094
| Temporary Service | 4/7/2020 | 4/8/2020 | 4/8/2020 8:47:10 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Todd Hall...t/s u/g new ok
|
ELE20-01118
| Electrical Rough-In | 4/7/2020 | 4/8/2020 | 4/8/2020 8:39:34 AM | P | CANC |
|
|
wall rough in Phone #: ###-#### >> Inspection requested via web by Ryan Wake Inspection cancelled from web by: Ryan Wake
|
ELE20-01243
| Final | 4/8/2020 | 4/8/2020 | 4/8/2020 8:31:26 AM | P | CANC |
|
|
Phone #: ###-#### Inspection requested via web by Jason Scott....occupied home...will reschedule after 4/17...covid19 instructions
|
ELE20-01242
| Final | 4/8/2020 | 4/8/2020 | 4/8/2020 8:31:04 AM | P | CANC |
|
|
Phone #: ###-#### Inspection requested via web by Jason Scott...occupied home...will reschedule after 4/17...covid19 instructions
|
ELE20-01241
| Temporary Service | 4/7/2020 | 4/8/2020 | 4/8/2020 8:19:53 AM | A | PASS |
|
|
Call Chase Wangen if questions, ###-####. Phone #: ###-#### Inspection requested via web by Shane Dale... t/s u/g new ok
|