Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE17-00783 Conference5/29/20185/29/20185/29/2018 3:14:42 PMPPASS
Chris Phone #: ###-####...discussed requirements for out building...circuit size, wiring methods, and protection...pamphlet givin...homeowner knowledgeable and capable
ELE05-04330 Final5/24/20185/29/20185/29/2018 2:30:27 PMPFAIL
Lynn Phone #: ###-####-please call with a meet time...
1.. light switch and fixture need added at each exterior door exiting grade level
2..romex shall be protected from physical damge..horizontal runs under 8'
3..w/p proof outlet cover needs fixed
4...outlets under panel need removed or wired correctly
ELE05-04329 Final5/24/20185/29/20185/29/2018 2:27:28 PMPFAIL
Lynn Phone #: ###-####-please call with a meet time...
1..listed breakers installed in sub panel
2..labelling of main service
3..labelling at house sub panel
ELE06-03887 Final5/24/20185/29/20185/29/2018 2:25:45 PMPPASS
Lynn-please call with a meet time Phone #: ###-####...job complete...ok to final
ELE05-03730 Final5/29/20185/29/20185/29/2018 2:25:10 PMPPASS
ok nto final
ELE18-01983 Electrical Rough-In5/29/20185/29/20185/29/2018 12:56:13 PMPPASS
Inspection requested via web by Matthew White..rough ok to cover...wiring of new interior walls off existing circuits as need, added circuits for new washer/dryer area and pantry circuit...new outlets and switches thru out house
ELE14-00051 Final5/29/20185/29/20185/29/2018 12:35:57 PMPPASS
Gracey Phone #: ###-####...job complete...ok to final
ELE18-01956 Temporary Service5/29/20185/29/20185/29/2018 12:21:14 PMPPASS
Phone #: ###-#### Inspection requested via web by JENNY EMEL...t/s o/h new ok...in alley way behind building
MIS18-00198 ELE-Final5/29/20185/29/20185/29/2018 11:48:19 AMPPASS
closing permit...no work has been done on hot tub...no electrical
MIS18-00198 MIS-Aging Inspection5/25/20185/29/20185/29/2018 11:47:26 AMAPASS
conversatiopn with homeowner that no work has been done on hot tub...is trying to find electrician to hire...fired previous electrician
ELE18-01988 Electrical Rough-In5/29/20185/29/20185/29/2018 11:11:55 AMPPASS
Potting Bonding And Equal Potential Phone #: ###-#### Inspection requested via web by Louis Keller...1 light potting, 4 corners to ring, cover rails, cover motor, pwr feed, and bonding to volleyball net mounts x 2...all ok
ELE18-01273 Electrical Rough-In5/25/20185/29/20185/29/2018 10:35:29 AMPCANC
Pls contact Brad (Foreman) @ ###-#### or Preston (Electrician) @ ###-#### one hr prior or if you have any questions. Thank you. Inspection requested via web by Rob Maes...job will be rescheduled do to changes in solar design
ELE18-01970 Rough-In Permanent Service5/25/20185/29/20185/29/2018 10:34:29 AMACANC
Pls contact Preston (Electrician) @ ###-#### one hr prior or if you have any questions. Thank you. Inspection requested via web by Rob Maes...inspection changed to conference
ELE18-01970 Conference5/29/20185/29/20185/29/2018 10:34:01 AMAPASS
Pls contact Preston (Electrician) @ ###-#### one hr prior or if you have any questions. Thank you. Inspection requested via web by Rob Maes...inspection changed to conference...new service needs to be done...changing location of main service to shop location and refeeding house...house service location is unable to be refed...will violate code requirement of clearances-3' needed infront of disconnect...basement window below location...new line diagram needs done to show new service locations and solar feeds and disconnects...grounding needs updated and other code violations at house and shop shall be fixed...another conference inspection is recommended to be scheduled
ELE18-01969 Electrical Rough-In5/25/20185/29/20185/29/2018 9:37:12 AMAPASS
Wired for detached shop. Phone #: ###-#### Inspection requested via web by Alan Lusk..rough ok to cover...underground approved..ends opened up
ELE13-01749 ELE-Aging Inspection5/29/20185/29/20185/29/2018 9:20:54 AM FAIL
company has new owner...permits need dealt with
ELE13-01602 DOC - Permit Expired5/29/20185/29/20185/29/2018 9:18:29 AMPPASS
expiring permit...no contact from contractor to verify work ever done
ELE18-00657 Electrical Rough-In5/28/20185/29/20185/29/2018 9:05:37 AMAPASS
Hope you had a great Memorial Day. I have a job now and leave at 0700 till 1630 so will not be home to go over a few things that might be an issue. Unless you want to come by after 1630 or I can meet around lunch time 1###-####? Dogs will be in the house but do not have access to the master suite. I will leave west gate unlock, just have to push right side open, master suite door is unlocked. Outside South wall; breaker for mini split ready, outlet is not anchored as it will be mortared in with the bricks(is that ok?). North inside wall Bathroom area, I hooked into the gfi of 1/2 bath for outlet on bathroom counter. did not know if I needed shower light to be gfi on same circuit or no gfi needed? with no wall space do I need an reg outlet on north wall below counters right side? Center ceiling light and old pantry(new shower) lights are temp till I can get lighting in room. Breakers are in panel and wired but turned off. Phone #: ###-#### Inspection requested via web by Robert Smith....rough ok to cover
ELE18-01698 Rough-In Permanent Service5/25/20185/29/20185/29/2018 8:41:42 AMAPASS
Phone #: ###-#### Inspection requested via web by Darryn Coburn...rough ok to cover...p/s u/g new ok
ELE18-01709 Electrical Rough-In5/29/20185/29/20185/29/2018 12:00:00 AMPPASS
Potting Bonding And Equal Potential Phone #: ###-#### Inspection requested via web by Louis Keller...1 light potting, 4 corners to ring, cover rails, cover motor, pwr feed, and bonding to volleyball net mounts x 2...all ok//// from duplicate permit ELE18-01988