Inspections for the day of: Wednesday, July 10, 2019.
Number of inspections: 14
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTom Saunders
TitleELE-INSPECTOR
Phone #208-794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE17-02380 ELE-Aging Inspection7/10/20197/10/20197/10/2019 3:49:19 PM PASS
DOC expired
ELE17-02380 DOC - Permit Expired7/10/20197/10/20197/10/2019 3:49:03 PMPPASS
permit expired...no activity in 180 days
ELE19-02534 Conference7/9/20197/10/20197/10/2019 3:45:39 PMPPASS
Tom, I spoke to you this morning about my unfinished basement. Since I work during the day, can you text me with the latest time you can meet on Wednesday and I can meet you at my house. Phone #: ###-#### Inspection requested via web by Daniel Grover...
discussed wiring of new basement
pamphlet given...homeowner competent
ELE18-03476 Final7/9/20197/10/20197/10/2019 2:08:18 PMPNR
Zack- inspection for admond area Phone #: ###-####...
areas checked off in rough inspection...see notes
ELE18-03476 Electrical Rough-In7/10/20197/10/20197/10/2019 2:07:10 PMPPASS
Zack- inspection for admond area Phone #: ###-####...areas approved as finaled...Admin up to line 16 ok to occupy
ELE18-04786 Final7/10/20197/10/20197/10/2019 1:32:36 PMPFAIL
Garage code 8671 Phone #: ###-#### Inspection requested via web by Kotton Corder...
1) all walls 2ft or larger shall have an outlet
2) all romex under 8ft ran horizontally shall be protected from physical damage
3) outlet shall be installed within 3ft of bath sink
4) a seperate circuit needs ran to ea disposal..
no load shall not exceed 80 percent of circuit
ELE19-02542 Electrical Rough-In7/10/20197/10/20197/10/2019 12:07:36 PMPPASS
UFER ground inspection Phone #: ###-#### Inspection requested via web by Dan Cox..
bare copper uffer ground ok to cover
ELE18-04652 Final7/9/20197/10/20197/10/2019 11:19:25 AMAPASS
Final inspection request. Homeowner will be on site all morning. Phone #: ###-#### Inspection requested via web by Tyler Stewart...
work complete...ok to final
ELE19-02522 Final7/9/20197/10/20197/10/2019 10:36:23 AMAPASS
Please call Juan with any questions Phone #: ###-#### Inspection requested via web by William Salts...existing circuits used or modified/fused ...ok to final
ELE19-02526 Electrical Rough-In7/9/20197/10/20197/10/2019 10:00:13 AMAPASS
Nick Phone #: ###-####...
UL listed equipment verified...solar kit engineered and guaranteed...purchased from GoGreenSolar company
discussed future inspections breaker in panel will need access for final
ELE19-02526 Conference7/9/20197/10/20197/10/2019 9:53:51 AMAPASS
Nick Phone #: ###-####...
solar install requirements...homeowner competent in work
ELE19-02499 Conference7/8/20197/10/20197/10/2019 9:05:56 AMAPASS
Phone #: ###-#### Inspection requested via web by GABE BEAL...
discussed wiring of sun room and required outlets...work had been started...outlets will be removed off dining room circuit and use living room circuit...not requiring outlet be added on wall where existing rock is instsalled...pamphlet given
ELE19-01824 Final7/9/20197/10/20197/10/2019 8:25:04 AMAFAIL
Phone #: ###-#### Inspection requested via web by Greg Traudt...
1) OCPD on A/C not matching nameplate or manufacturers requirement
2) A/C needs hooked up...wiring needs completed
ELE19-02524 Final7/9/20197/10/20197/9/2019 2:00:55 PMACANC
Kelly Phone #: ###-####...
did perm service inspection previous day...not ready for final