Inspections for the day of: Friday, July 26, 2019.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTom Saunders
TitleELE-INSPECTOR
Phone #208-794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE19-02038 Electrical Rough-In7/26/20197/26/20197/26/2019 2:20:09 PMPPASS
rUSTEN Phone #: ###-####...heated bath floors x 2 ...ok to cover
ELE19-02776 Conference7/25/20197/26/20197/26/2019 2:10:58 PMPPASS
KRUSE Phone #: ###-####...
discussed wiring of shop
underground and above ground requirements
wiring material used
pamphlet given...homeowner very knowledgeable...recommend second consult once building framed
ELE19-02421 Permanent Service7/25/20197/26/20197/26/2019 1:15:34 PMPPASS
Give call early afternoon so can get power restored to continue work Rod Phone #: ###-####...p/s o/h reconnect ok
ELE19-02098 Final7/19/20197/26/20197/26/2019 11:13:35 AMAPASS
owner will be at site at 9am. Please call him 15 min before going. ###-####
Phone #: ###-#### Inspection requested via web by Tim Dunlop...
required circuit removed and box blanked off
ok to final
ELE19-02780 Permanent Service7/25/20197/26/20197/26/2019 10:49:45 AMAPASS
Phone #: ###-#### Inspection requested via web by danny perrine...
access required for final...verify interior panel
p/s o/h reconnect ok
ELE19-02206 Final7/25/20197/26/20197/26/2019 10:26:25 AMAPASS
Phone #: ###-#### Inspection requested via web by Kirt Palmer...ok to final
ELE19-01763 Final7/25/20197/26/20197/26/2019 10:01:47 AMAFAIL
Phone #: ###-#### Inspection requested via web by TOM BICANDI....
1..water heater disconnect
2..loft lights not working
3..furnaces need identification
4..panels need identification..at panel and exterior disconnect
5..panels shall be completely labelled with breaker directory
6..all offices requiring OCC sensor shall be installed-rm 119

ELE19-01316 Final7/25/20197/26/20197/26/2019 9:18:12 AMAPART
2nd six units from north end Phone #: ###-#### Inspection requested via web by Kevin Burke...
RMs 105,106,205,206,305,306 ok to final
ELE17-02581 ELE-Aging Inspection7/26/20197/26/20197/26/2019 7:14:24 AM DONE
no work performed or inspections scxheduled in 120 days