Inspections for the day of: Monday, August 12, 2019.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTom Saunders
TitleELE-INSPECTOR
Phone #208-794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE19-00979 Final8/12/20198/12/20198/12/2019 3:36:44 PMPFAIL
access 3600 Phone #: ###-#### Inspection requested via web by David Nelson...
1..MOCP on mini split units do not meet manuf rating...exceed 80% of circuit
2..NM cable not rated to be used outside...thhn needed to wire mini split units...all previous units will be reinspected for proper wiring...building 9333 needs addressed
ELE19-01542 Final8/12/20198/12/20198/12/2019 3:16:09 PMPPASS
access 3600 Phone #: ###-#### Inspection requested via web by David Nelson..ok to final
ELE19-02874 Electrical Rough-In8/12/20198/12/20198/12/2019 2:52:38 PMPPASS
Please call Journeyman, Preston Seay, ###-#### for any timeline or questions. We will be ready ASAP for your inspections if you can accomodate us. Thanks. Phone #: ###-#### Inspection requested via web by Rob Maes...
UL listing verified
ELE19-02967 Final8/9/20198/12/20198/12/2019 2:24:34 PMPPASS
Phone #: ###-#### Inspection requested via web by sam petterson...ok to final
ELE19-00030 Electrical Rough-In8/12/20198/12/20198/12/2019 1:49:01 PMPPASS
Inspection needed for Retail area.
Journeyman on-site, Wade Luthy ###-#### Phone #: ###-#### Inspection requested via web by Bryan Atkins...
vestibule walls and ceiling
wall of retail sales/accessories
ok to cover
ELE19-02542 Electrical Rough-In8/12/20198/12/20198/12/2019 1:49:01 PMPPASS
Under slab Phone #: ###-#### Inspection requested via web by Dan Cox...electrical rm underground...discussed job and requirements...
ok'ed wiring methods discussed
ELE19-02742 Permanent Service8/9/20198/12/20198/12/2019 12:07:05 PMAPASS
Electrical service for portable classroom. Contact is Bill Stokes. Phone #: ###-#### Inspection requested via web by Richard Montgomery...
p/s new ok
ELE19-01542 Final8/12/20198/12/20198/12/2019 9:45:41 AMPCANC
access 3600 Phone #: ###-#### >> Inspection requested via web by David Nelson Inspection cancelled from web by: David Nelson
ELE19-02587 Final8/5/20198/12/20198/12/2019 9:16:22 AMANH
Pls contact Bryce (Foreman) @ ###-#### or George (Electrician) @ ###-#### one hr prior or if you have any questions. Thank you. Inspection requested via web by Rob Maes...
no access...no one home...dog barking and no response
TWO PERMITS ON HOUSE..INSPECTIONS NEED CLARIFIED
ELE19-02943 Electrical Rough-In8/9/20198/12/20198/12/2019 9:08:32 AMAPASS
Call Kevin ###-#### to meet you there. If you have any questions please feel free to contact Andrew ###-####. Thanks!! Phone #: ###-#### Inspection requested via web by Clayton Morgan...
rough in of kitchen, new butlers pantry, and bonus rm with laundry
ok to cover excluding back wall of bonus rm-new and existing mini splits wiring needs addressed
ELE19-01451 Final8/11/20198/12/20198/12/2019 8:34:16 AMAPASS
contact Todd for gate code Phone #: ###-#### Inspection requested via web by Todd Hall
ok to final
ELE19-01456 Final8/11/20198/12/20198/12/2019 8:33:38 AMAPASS
contact Todd Phone #: ###-#### Inspection requested via web by Todd Hall...ok to final
ELE17-04113 Final8/9/20198/12/20198/9/2019 12:36:42 PMACANC
Original Permit and Inspection passed in December 2017. Contacted by Darryl on August 9th 2019 and was informed we needed to order a final because the system did not show this as an "aging" permit until now. We were asked to contact the owner Travis Dick at ###-#### and will do so. Thank you. If you need to contact us you can call the office at ###-#### and ask for Paula or Lauren and if you would like to speak to our foreman Dustin you can reach him at ###-####. Sorry for the confusion. Thank you
Lauren Phone #: ###-#### >> Inspection requested via web by Paula Gratiot Inspection cancelled from web by: Paula Gratiot