Inspections for the day of: Wednesday, October 21, 2009.
Number of inspections: 16
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ESC09-00407 General Inspection10/21/200910/21/200910/21/2009 3:47:00 PMPPASS
looked ok
ESC09-00213 General Inspection10/21/200910/21/200910/21/2009 3:45:01 PMPPASS
looked ok
ESC09-00258 General Inspection10/21/200910/21/200910/21/2009 3:44:21 PMPPASS
looked ok
ESC09-00401 General Inspection10/21/200910/21/200910/21/2009 3:42:35 PMPPASS
looked ok
ELE09-02036 Electrical Rough-In10/21/200910/21/200910/21/2009 3:38:16 PMPPASS
Bob That islsnd is ready for cover and i have removed and sealed and taken care of the items on the ceiling we discussed. The rest of the work i will make availble for your review on final. Thanks Dave Phone #: ###-#### Internet Inspection Request from: jason shifflett ric ok, no esc this project
ELE09-02049 Electrical Rough-In10/21/200910/21/200910/21/2009 2:56:35 PMPPASS
Phone #: ###-#### Internet Inspection Request from: Dan Mitchell ric ok, no esc this project
ELE09-02049 Final10/21/200910/21/200910/21/2009 2:56:23 PMPPASS
Phone #: ###-#### Internet Inspection Request from: Dan Mitchell ok to final, no esc this project
ELE09-02008 Rough-In Permanent Service10/20/200910/21/200910/21/2009 2:08:02 PMPFAIL
Aly Phone #: ###-#### homeowner not doing work, called homeowner, 412, ipco, and city to void permit, told that electrical contractor shall permit and do work, no esc this project
ELE09-00845 Electrical Rough-In10/21/200910/21/200910/21/2009 1:58:38 PMPPASS
mike Phone #: ###-#### ric ok
ELE09-01695 Final10/21/200910/21/200910/21/2009 12:45:56 PMPFAIL
Daniel Phone #: ###-#### called, left correction notice, NEC 200.7 shall not use white for phase conductor at a/c, 406.4 shall securely mount receptacles, 422.11(A) shall not exceed rating of a/c nameplate for overcurrent protection, 210.52(C)(2)(4) shall add receptacle to left of sink in countertop space
ELE09-01886 Rough-In Permanent Service10/20/200910/21/200910/21/2009 11:45:12 AMPPASS
Phone #: ###-#### Internet Inspection Request from: Stephen Kren ric ok house and garage, p/s u/g n ok
ELE09-01887 Rough-In Permanent Service10/20/200910/21/200910/21/2009 10:35:56 AMPPASS
Phone #: ###-#### Internet Inspection Request from: Stephen Kren ric ok house and garage, p/s u/g n ok, no esc this project
ELE09-02047 Electrical Rough-In10/20/200910/21/200910/21/2009 10:07:36 AMAFAIL
Tom Phone #: ###-#### called, left correction notice, BCC all commercial wiring shall be in mc cable or conduit and wire- no nm cable, no esc this project
ELE09-01607 Electrical Rough-In10/20/200910/21/200910/21/2009 9:13:46 AMAFAIL
Josh Phone #: ###-#### called, left correction notice, NEC 300.14 shall provide minimum 6" free conductor length at boxes, 334.30 shall staple nm cable over panel within 12" of panel, 100.12(B) shall maintain integrity of conductor- no cuts or nicks thru insulation- by panel
ELE09-02041 Conference10/20/200910/21/200910/21/2009 8:28:26 AMACANC
Jeff Pierce Phone #: ###-#### Internet Inspection Request from: Dave Friend see ri
ELE09-02041 Electrical Rough-In10/21/200910/21/200910/21/2009 8:28:07 AMAFAIL
Jeff Pierce Phone #: ###-#### Internet Inspection Request from: Dave Friend met contractot, left correction notice to owner, NEC 358.30 emt shall be securely fastened within 3' of termination, 725.25 abandoned low voltage cables shall be removed, 300.11(A) cables shall not be supported by ceiling, BCC no violations shall be retained