Inspections for the day of: Monday, September 27, 2010.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE10-02026 Final9/24/20109/27/20109/27/2010 2:31:04 PMPPASS
Fianl Inspection for Loco Shop Power. Call Jeremy at ###-####! Thanks! Phone #: ###-#### >> Inspection requested via web by Kevin Perez met contractor, ok final
ELE10-02073 Electrical Rough-In9/27/20109/27/20109/27/2010 12:35:43 PMPPASS
gene Phone #: ###-#### ri ok
ELE10-02101 Electrical Rough-In9/27/20109/27/20109/27/2010 11:09:56 AMPPASS
need ok to cover open walls and ceilings. Call Jimmy @ ###-#### to gain access. Phone #: ###-#### >> Inspection requested via web by John Edwards called, ri ok
ELE10-02090 Permanent Service9/24/20109/27/20109/27/2010 9:54:26 AMAPASS
kenny Phone #: ###-#### p/s o/h rec ok
ELE10-02113 Electrical Rough-In9/24/20109/27/20109/27/2010 9:00:19 AMAFAIL
jim Phone #: ###-#### called, left messages, NEC 210.52 shall add 2 receptacles, 3-way switch
ELE10-01957 Final9/24/20109/27/20109/27/2010 8:18:17 AMAFAIL
call for access if needed//Rob Phone #: ###-#### called, left correction notice, NEC 408.4 shall provide circuit directory at service panel, 410.62(C) cord connected luninaires shall be directly below outlet, 110.22(A) garage disconnect shall be legibly marked to indicate purpose
ELE09-00292 DOC - Permit Expired9/27/20109/27/20109/27/2010 5:34:44 AMAPASS
no activity
ELE09-00308 DOC - Permit Expired9/27/20109/27/20109/27/2010 5:32:13 AMAPASS
no activity