Inspections for the day of: Friday, January 9, 2015.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorCevyn Recla
TitleELE-INSPECTOR
Phone #985-3493
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE14-03203 Electrical Rough-In1/8/20151/9/20151/9/2015 3:03:23 PMPPASS
Jimmy-ceiling Phone #: ###-####
corrections made, abandoned cable removed, low volt cables tied off above grid,
Ceiling OK to Cover
ELE09-01198 ELE-Aging Inspection1/9/20151/9/20151/9/2015 2:28:13 PM DONE
posted correction on door
ELE14-03169 Final1/9/20151/9/20151/9/2015 2:26:43 PMPFAIL
If house is locked please call for garage code, thank you. Also if in near vicinity ready now. Phone #: ###-#### Inspection requested via web by Robert Schroder
210.4 B multiwire branch circuit shall be provided with means to disconnect all ungrounded conductors simultaneously
314.20 boxes shall be not be set back more than 1/4 inch of finished surface
200.7 C 1 insulation shall be permanently reidentified to indicate its use as an ungrounded conductor at all visible locations
called contracor
ELE13-01804 Final1/9/20151/9/20151/9/2015 1:00:19 PMPFAIL
Contact: Brian Gee Phone #: ###-#### Inspection requested via web by Deb Gooden
ground wire has been cut and stolen, contractor will replace in conduit and call back for final, panel ok, just want to see ground on final
ELE15-00014 Electrical Rough-In1/9/20151/9/20151/9/2015 12:27:50 PMPPASS
We will be on site all day. Rough in for inspection of solar install prior to laying panels. Phone #: ###-#### Inspection requested via web by Matthew Dunay
Rough in of racks on roof, grounding, listing of equipment, OK
ELE15-00057 Electrical Rough-In1/9/20151/9/20151/9/2015 12:08:30 PMPPASS
Please call half an hour before inspection to insure access. Thanks
Shaun ###-#### Phone #: ###-#### Inspection requested via web by Shaun Kirkman
Kitchen, laundry room, hall bath, RI OK to cover
ELE15-00018 Electrical Rough-In1/8/20151/9/20151/9/2015 11:34:32 AMAPASS
Lock box 4888. Please let me know if there are any issues. Thanks Phone #: ###-#### Inspection requested via web by Clay Morgan
master bed bath closet, kit, entry area, RI OK
ELE15-00042 Final1/8/20151/9/20151/9/2015 11:21:50 AMAPASS
Please call when on way so we can meet you there. ###-#### Thanks Phone #: ###-#### Inspection requested via web by Clay Morgan
Final OK
ELE14-02652 Final1/8/20151/9/20151/9/2015 10:36:41 AMAPASS
Please call Cory with any questions. ###-####
thanks, Phone #: ###-#### Inspection requested via web by Cyndi Dale
corrections made, final OK
ELE15-00036 Final1/8/20151/9/20151/9/2015 10:11:20 AMAFAIL
Phone #: ###-#### Inspection requested via web by John VanZandt
250.32 seperate building supplied by feeder or branch circuit shall have a grounding electrode system installed
250.32.D Seperate building or structure, disconnecting means required at nearest point of entrace
called John
ELE14-03068 Final1/8/20151/9/20151/9/2015 9:01:22 AMAFAIL
Final on bath remodel and hot tub disconnect. Phone #: ###-#### Inspection requested via web by Randy Fletcher
called randy
424.44 G GFI protection required for bath floor heat
422.31 disconnecting means required for permanently installed appliances
422.11 over current protection shall be sized to rating marked on appliance
372.13 abandoned outlets and conductors shall be removed
110.12A unused openings shall be closed
NO inspection performed on floor heat installation