Inspections for the day of: Tuesday, November 4, 2014.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorCevyn Recla
TitleELE-INSPECTOR
Phone #985-3493
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE14-01775 Final11/3/201411/4/201411/4/2014 2:12:34 PMPPASS
Brian Phone #: ###-####
Final OK
ELE14-01969 Final11/4/201411/4/201411/4/2014 1:15:41 PMPPASS
Please call Brian Cornell at ###-#### when you are on your way Phone #: ###-#### Inspection requested via web by Celinda Winters
FInal OK
ELE14-02754 Final11/3/201411/4/201411/4/2014 12:51:53 PMPFAIL
call for access Phone #: ###-#### Inspection requested via web by steve sellers

210.8A(3) GFI Protection required outdoors
406.4D(6) Weather resistant receptacles required where subject ot wet or damp location. called contractor
ELE14-03058 Electrical Rough-In11/4/201411/4/201411/4/2014 12:04:52 PMPPASS
Jay Phone #: ###-####
RI Ok to cover
ELE12-01319 ELE-Aging Inspection11/4/201411/4/201411/4/2014 10:46:24 AM DONE
Left message for contractor
ELE14-03069 Final11/4/201411/4/201411/4/2014 10:38:26 AMPPASS
Phone #: ###-#### Inspection requested via web by jason shifflett
Correction fixed,
FInal OK
ELE14-02524 Final11/3/201411/4/201411/4/2014 10:10:55 AMAPASS
Phone #: ###-#### Inspection requested via web by daniel bibikov
FInal OK
ELE14-03069 Final11/3/201411/4/201411/4/2014 9:34:19 AMAFAIL
We Reolace Some Gfci Outlets To Tamper Proof And A Few Other Outlets No other Or new Wiring Done. Thanks Dave Please Call So I can Have the property Open. ###-#### Phone #: ###-####
Inspection requested via web by jason shifflett
Spoke to contractor
110.a.1 all items readty for inspection, 2 outlets with no power
ELE14-03079 Temporary Service11/3/201411/4/201411/4/2014 9:06:32 AMAPASS
Phone #: ###-#### Inspection requested via web by Bob Glenn
TS, UG, N OK
ELE14-02914 Electrical Rough-In11/3/201411/4/201411/4/2014 8:46:12 AMAPART
Contractor wants to sheetrock the lid, everything is roughed in except for the feeder wires, we will make sure we call in another rough in before that gets covered. Phone #: ###-#### Inspection requested via web by Clay Morgan
320.23A NM cable shall be protected at attic accesses
110.3 A All work ready for examination, switches at stairs
300.4 a (1) Cables through bored holes shall be protected when less than 1 1/4 inch

OK to cover ceiling portion of garage area ONLY! nothing upstairs