ELE14-01775
| Final | 11/3/2014 | 11/4/2014 | 11/4/2014 2:12:34 PM | P | PASS |
|
|
Brian Phone #: ###-#### Final OK
|
ELE14-01969
| Final | 11/4/2014 | 11/4/2014 | 11/4/2014 1:15:41 PM | P | PASS |
|
|
Please call Brian Cornell at ###-#### when you are on your way Phone #: ###-#### Inspection requested via web by Celinda Winters FInal OK
|
ELE14-02754
| Final | 11/3/2014 | 11/4/2014 | 11/4/2014 12:51:53 PM | P | FAIL |
|
|
call for access Phone #: ###-#### Inspection requested via web by steve sellers
210.8A(3) GFI Protection required outdoors 406.4D(6) Weather resistant receptacles required where subject ot wet or damp location. called contractor
|
ELE14-03058
| Electrical Rough-In | 11/4/2014 | 11/4/2014 | 11/4/2014 12:04:52 PM | P | PASS |
|
|
Jay Phone #: ###-#### RI Ok to cover
|
ELE12-01319
| ELE-Aging Inspection | 11/4/2014 | 11/4/2014 | 11/4/2014 10:46:24 AM | | DONE |
|
|
Left message for contractor
|
ELE14-03069
| Final | 11/4/2014 | 11/4/2014 | 11/4/2014 10:38:26 AM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by jason shifflett Correction fixed, FInal OK
|
ELE14-02524
| Final | 11/3/2014 | 11/4/2014 | 11/4/2014 10:10:55 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by daniel bibikov FInal OK
|
ELE14-03069
| Final | 11/3/2014 | 11/4/2014 | 11/4/2014 9:34:19 AM | A | FAIL |
|
|
We Reolace Some Gfci Outlets To Tamper Proof And A Few Other Outlets No other Or new Wiring Done. Thanks Dave Please Call So I can Have the property Open. ###-#### Phone #: ###-#### Inspection requested via web by jason shifflett Spoke to contractor 110.a.1 all items readty for inspection, 2 outlets with no power
|
ELE14-03079
| Temporary Service | 11/3/2014 | 11/4/2014 | 11/4/2014 9:06:32 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Bob Glenn TS, UG, N OK
|
ELE14-02914
| Electrical Rough-In | 11/3/2014 | 11/4/2014 | 11/4/2014 8:46:12 AM | A | PART |
|
|
Contractor wants to sheetrock the lid, everything is roughed in except for the feeder wires, we will make sure we call in another rough in before that gets covered. Phone #: ###-#### Inspection requested via web by Clay Morgan 320.23A NM cable shall be protected at attic accesses 110.3 A All work ready for examination, switches at stairs 300.4 a (1) Cables through bored holes shall be protected when less than 1 1/4 inch
OK to cover ceiling portion of garage area ONLY! nothing upstairs
|