Inspections for the day of: Friday, December 12, 2014.
Number of inspections: 5
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorCevyn Recla
TitleELE-INSPECTOR
Phone #985-3493
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE12-00559 ELE-Aging Inspection12/12/201412/12/201412/15/2014 11:44:48 AM DONE
left message for David
ELE14-03421 Final12/11/201412/12/201412/12/2014 9:37:26 AMAPASS
call to scheduel hopefully between 10am and noon thanks Phone #: ###-#### Inspection requested via web by ron spen cer
THis was for conference only, discussed what will be required for home should the contractor add wiring for homeowners hot tub. Service issues, clearances from service drop, bonding
ELE14-03426 Final12/12/201412/12/201412/12/2014 9:14:06 AMPCANC
Phone #: ###-#### >> Inspection requested via web by daniel bibikov Inspection cancelled from web by: daniel bibikov
ELE14-03420 Rough-In Permanent Service12/11/201412/12/201412/12/2014 9:10:12 AMAFAIL
Phone #: ###-#### Inspection requested via web by Emmet Bushman
spoke to Emmett
WUI zone, cans in soffit need building approval before cover,
110.26 A working clearance, meter base needs 3 feet
210.52C1 kitchen wall countertop space, no more than 24 inches to receptacles
320.23 NM cable shall be protected at attic access within 6 feet of opening
300.4 bored holes- protect nm cable through bored holes with less than 1 1/4 inch to framing member edge.
ELE14-03369 Electrical Rough-In12/11/201412/12/201412/12/2014 8:13:04 AMAFAIL
Phone #: ###-#### Inspection requested via web by Mark Hansen
210.17 Electric vehicle branch circuit shall supply no other outlets
210.52A.1 spacing, no wall space greater than 6 foot from a receptacle
210.52C.1 wall countertop space, no point greater than 24 inches from a receptacle
210.52 I dining receptacle shall be supplied from 20 amp small appliance circuit
300.13B Grounded conductor multi wire circuit, shall not depend on device
300.4 nm cable through bored hole less than 1 1/4 inch from framing member edge shall be protected
The range box is rated for up to a #10 wire, you need to use a box rated for the wire installed.