Inspections for the day of: Tuesday, December 16, 2014.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorCevyn Recla
TitleELE-INSPECTOR
Phone #985-3493
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE14-03420 Rough-In Permanent Service12/15/201412/16/201412/16/2014 3:41:02 PMPFAIL
reinspect service clearances, recess cans outside, crawl access, kitchen island wiring Phone #: ###-#### Inspection requested via web by Emmet Bushman
WUI zone fire area, recessed can boxes must be fire caulked at openings
ELE12-02467 ELE-Aging Inspection12/16/201412/16/201412/16/2014 1:22:55 PM DONE
Spoke to John, will research project for final
ELE12-02504 ELE-Aging Inspection12/16/201412/16/201412/16/2014 1:19:26 PM DONE
Spoke to company, they will investigate project
ELE14-03331 Final12/16/201412/16/201412/16/2014 1:16:08 PMPPASS
The access code is 3902
The panel cover is secured and ready for the final insp, any questions please let me know, thx, TW. Phone #: ###-#### Inspection requested via web by Stephen Kren
Final OK
ELE14-03153 Final12/16/201412/16/201412/16/2014 1:01:57 PMPPASS
Please call half hour before. Need to meet you with key.
Thanks Phone #: ###-#### Inspection requested via web by mark hood
Final OK
ELE14-02751 Final12/15/201412/16/201412/16/2014 12:19:03 PMPPASS
Phone #: ###-#### Inspection requested via web by Jarod Murray
Final OK
ELE14-03447 Electrical Rough-In12/15/201412/16/201412/16/2014 10:58:27 AMAFAIL
Any questions, please call Darrel Kubik ###-#### Phone #: ###-#### Inspection requested via web by Charmel Kubik
Phone number listed is non-working
300.4A1 Nm through bored holes shall have protection where edge of hole is less than 1 1/4 inch from edge of framing member

BCC all work shall be finished and ready for inspection, wire and box hanging directly from ceilning and not made up
ELE14-02853 Conference12/15/201412/16/201412/16/2014 10:13:03 AMADONE
discuss usable wall space Phone #: ###-#### Inspection requested via web by ERIC CENTERS
Open railing wall space, discussed useable wall space with concrete floor, contractor to put outlet at both ends of open rail to cover wall space.
ELE14-03452 Final12/15/201412/16/201412/16/2014 9:37:12 AMAPASS
Shop at southeast of property 4 8'' fluorescents and 2 coaches Phone #: ###-#### Inspection requested via web by Cindie Swaim
Final OK
ELE14-01776 Final12/15/201412/16/201412/16/2014 9:23:32 AMAPASS
Inspection requested via web by steve ragan
Final OK
ELE14-02464 Final12/15/201412/16/201412/16/2014 9:01:24 AMAFAIL
Garage code is JAYO enter Phone #: ###-#### Inspection requested via web by Zane Robertson
422.30 Disconnecting means required on all permanently installed appliances
250.148 metal boxes shall be grounded my means of grounding screw
left message for Zane