Inspections for the day of: Wednesday, December 17, 2014.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorCevyn Recla
TitleELE-INSPECTOR
Phone #985-3493
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
GCE14-00207 GCE-Temporary Service12/17/201412/17/201412/17/2014 2:38:46 PMPPASS
Kevin ###-#### - temp pole insp. temp pole that sits in front of Id Pow transformer #TW-14
TS, UG, N, OK
ELE14-03369 Electrical Rough-In12/17/201412/17/201412/17/2014 2:29:07 PMPPASS
Mark Phone #: ###-####
corrections made, RI OK
ELE14-03229 Rough-In Permanent Service12/17/201412/17/201412/17/2014 2:17:50 PMPFAIL
Any questions please let me know, thx, TW. Phone #: ###-#### Inspection requested via web by Stephen Kren
310.15B 4/0 AL SER, 60*, max amp rating is 150
300.4 bored holes, nm shall be protected through bored holes with less than 1 1/4 inch to framing member edge
210.70.3 lighting outlets required, attic space with equipment requiring servicing
334.30 nm cable shall be supported at intervals not exceeding 4 1/2 foot
320.23 NM shall be protected withing 6 feet of attic access
spoke to Terry
ELE14-03430 Permanent Service12/17/201412/17/201412/17/2014 1:08:11 PMPPASS
If you have any questions, please call Luke at ###-####. Thank You. Phone #: ###-#### Inspection requested via web by Clay Morgan
PS, OH, N, oK
ELE11-02792 ELE-Aging Inspection12/17/201412/17/201412/17/2014 11:09:15 AM DONE
Spoke to contractor,
ELE14-03447 Rough-In Permanent Service12/17/201412/17/201412/17/2014 11:06:10 AMAPASS
Please call Darrel Kubik ###-#### - the contractor scheduled to have the cement delivered this morning at 10:00 am and would like to have the inspection done before it arrives.
Thank you Phone #: ###-#### Inspection requested via web by Charmel Kubik
Corrections made, RI OK
poured ground wire in concrete, ok to cover,
PS, UG, N, OK
ELE14-03447 Electrical Rough-In12/16/201412/17/201412/17/2014 11:05:16 AMACANC
Please call Darrel Kubik ###-####(ASAP). The contractor has scheduled to have the concrete poured at 10:00am and the inspection will need to be done before the concrete is poured.. Thank you Phone #: ###-####
Inspection requested via web by Charmel Kubik
Called for 2 inspections, cancelled this one, see rough in permanent service
ELE14-03369 Electrical Rough-In12/16/201412/17/201412/17/2014 10:38:52 AMAFAIL
Mark Phone #: ###-####
Daryl DeGrange spoke to contractor, not all corrections have been addressed.
ELE13-02994 ELE-Request for Extension12/16/201412/17/201412/17/2014 9:52:12 AMAPASS
Mike Phone #: ###-####
Spoke to homeowner, they are moving forward with the renovation, and plan to have RI ready to inspect in near future. Extension given.
ELE13-03535 Final12/15/201412/17/201412/17/2014 9:45:24 AMAPASS
Call prior to going Phone #: 2088661213 >> Inspection requested via mobile web by Todd Nelson
corrections made, final ok
ELE14-03466 Temporary Service12/16/201412/17/201412/17/2014 9:26:45 AMAFAIL
Phone #: ###-#### Inspection requested via web by Emmet Bushman
590.6 GFI protection required for temporary power to construction sites
called Emmett
ELE14-02613 Final12/16/201412/17/201412/17/2014 9:11:51 AMAPASS
Phone #: ###-#### Inspection requested via web by Brad Girard
FInal OK
ELE14-03229 Rough-In Permanent Service12/16/201412/17/201412/17/2014 7:26:40 AMACANC
Any questions please let me know, thx, TW. Phone #: ###-#### >> Inspection requested via web by Stephen Kren Inspection cancelled from web by: Stephen Kren