Inspections for the day of: Tuesday, December 23, 2014.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorCevyn Recla
TitleELE-INSPECTOR
Phone #985-3493
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE14-03520 Final12/23/201412/23/201412/23/2014 2:14:08 PMPFAIL
Inspection requested via web by ron spen cer
Tried calling cell phone, contact number was not provided, used number from previous conference, no answer.
110.3 Listed and labeled equipment shall be installed in accordance with listing and labeling provided, minimum #6 and maximum 40 amp listed on product nameplate
300.5, non metallic conduit minimum burial depth is 18 inches.
ELE14-03416 Permanent Service12/23/201412/23/201412/23/2014 1:07:28 PMPDONE
Dustin Phone #: ###-####
ps, oh, n, ok,
left message for Dustin, needs to address the connectors in the back of the meter base, pulled free from connection of panel and conductors do not have protection from metal.
ELE14-03256 Electrical Rough-In12/23/201412/23/201412/23/2014 12:48:55 PMPFAIL
Please give Paul a call if any questions or problems Phone #: ###-#### Inspection requested via web by Paul Young
spoke to contyractor
300.4A1 nm through bored holes shall be protected when hole is less than 1 1/4 inch from edge of framing membr
334.30 securing and supporting, cable shall be secured within 12 inches of entrance to box and supported at intervals not to exceed 4 1/2 ft. (ser at meter and above meter, switch at bottom of stairs need stack-it or some other form of securing)
Rock inspected concrete encased grounding electrode while inspecting the temporary service.
ELE12-02642 Final12/23/201412/23/201412/23/2014 10:38:00 AMPPASS
Aging permit, no work was ever performed under this permit, owner wants to close it and will repermit should he ever decide to follow through with project.
ELE14-02724 Final12/23/201412/23/201412/23/2014 10:23:01 AMPPASS
call half hour before// Dan Phone #: ###-####
Final OK
ELE12-02633 ELE-Aging Inspection12/23/201412/23/201412/23/2014 9:37:44 AM DONE
Spoke with contractor, project is finished, did not know that final inspection had not taken place, will attempt to arrange for Final.
ELE12-02642 ELE-Aging Inspection12/23/201412/23/201412/23/2014 9:33:38 AM DONE
left message for John
ELE12-01889 ELE-Aging Inspection12/23/201412/23/201412/23/2014 9:30:34 AM DONE
left message for Lindsay, ###-####
ELE14-03516 Electrical Rough-In12/22/201412/23/201412/23/2014 9:20:16 AMAPASS
Please call Luke when you are on your way ###-####. Thank You Phone #: ###-#### Inspection requested via web by Clay Morgan
Unit 1, Kitchen, east wall, RI. 5 4sq boxes1 6X6 jboxes, left of sink
RI OK
ELE14-03430 Final12/22/201412/23/201412/23/2014 9:17:28 AMAPASS
Please call Luke when you are on your way ###-####. Thank You Phone #: ###-#### Inspection requested via web by Clay Morgan
FInal OK
ELE14-02596 Final12/22/201412/23/201412/23/2014 8:37:09 AMAFAIL
Garage code is JAYO enter Phone #: ###-#### Inspection requested via web by Zane Robertson left message for contractor
BCC 4-05-26 TRIM-OUT (FINAL) INSPECTION Trim-out
inspections shall cover the installation and/or connection of devices, cover plates, fixtures,
utilization equipment
ELE10-00317 ELE-Aging Inspection12/22/201412/23/201412/22/2014 2:12:42 PMADONE
Spoke to homeowner, Hawk, ###-#### said they are new owners, and had no idea of any open permits. I gave all the info I could, and she will talk to her husband and call back about getting final inspection.