ELE14-03520
| Final | 12/23/2014 | 12/23/2014 | 12/23/2014 2:14:08 PM | P | FAIL |
|
|
Inspection requested via web by ron spen cer Tried calling cell phone, contact number was not provided, used number from previous conference, no answer. 110.3 Listed and labeled equipment shall be installed in accordance with listing and labeling provided, minimum #6 and maximum 40 amp listed on product nameplate 300.5, non metallic conduit minimum burial depth is 18 inches.
|
ELE14-03416
| Permanent Service | 12/23/2014 | 12/23/2014 | 12/23/2014 1:07:28 PM | P | DONE |
|
|
Dustin Phone #: ###-#### ps, oh, n, ok, left message for Dustin, needs to address the connectors in the back of the meter base, pulled free from connection of panel and conductors do not have protection from metal.
|
ELE14-03256
| Electrical Rough-In | 12/23/2014 | 12/23/2014 | 12/23/2014 12:48:55 PM | P | FAIL |
|
|
Please give Paul a call if any questions or problems Phone #: ###-#### Inspection requested via web by Paul Young spoke to contyractor 300.4A1 nm through bored holes shall be protected when hole is less than 1 1/4 inch from edge of framing membr 334.30 securing and supporting, cable shall be secured within 12 inches of entrance to box and supported at intervals not to exceed 4 1/2 ft. (ser at meter and above meter, switch at bottom of stairs need stack-it or some other form of securing) Rock inspected concrete encased grounding electrode while inspecting the temporary service.
|
ELE12-02642
| Final | 12/23/2014 | 12/23/2014 | 12/23/2014 10:38:00 AM | P | PASS |
|
|
Aging permit, no work was ever performed under this permit, owner wants to close it and will repermit should he ever decide to follow through with project.
|
ELE14-02724
| Final | 12/23/2014 | 12/23/2014 | 12/23/2014 10:23:01 AM | P | PASS |
|
|
call half hour before// Dan Phone #: ###-#### Final OK
|
ELE12-02633
| ELE-Aging Inspection | 12/23/2014 | 12/23/2014 | 12/23/2014 9:37:44 AM | | DONE |
|
|
Spoke with contractor, project is finished, did not know that final inspection had not taken place, will attempt to arrange for Final.
|
ELE12-02642
| ELE-Aging Inspection | 12/23/2014 | 12/23/2014 | 12/23/2014 9:33:38 AM | | DONE |
|
|
left message for John
|
ELE12-01889
| ELE-Aging Inspection | 12/23/2014 | 12/23/2014 | 12/23/2014 9:30:34 AM | | DONE |
|
|
left message for Lindsay, ###-####
|
ELE14-03516
| Electrical Rough-In | 12/22/2014 | 12/23/2014 | 12/23/2014 9:20:16 AM | A | PASS |
|
|
Please call Luke when you are on your way ###-####. Thank You Phone #: ###-#### Inspection requested via web by Clay Morgan Unit 1, Kitchen, east wall, RI. 5 4sq boxes1 6X6 jboxes, left of sink RI OK
|
ELE14-03430
| Final | 12/22/2014 | 12/23/2014 | 12/23/2014 9:17:28 AM | A | PASS |
|
|
Please call Luke when you are on your way ###-####. Thank You Phone #: ###-#### Inspection requested via web by Clay Morgan FInal OK
|
ELE14-02596
| Final | 12/22/2014 | 12/23/2014 | 12/23/2014 8:37:09 AM | A | FAIL |
|
|
Garage code is JAYO enter Phone #: ###-#### Inspection requested via web by Zane Robertson left message for contractor BCC 4-05-26 TRIM-OUT (FINAL) INSPECTION Trim-out inspections shall cover the installation and/or connection of devices, cover plates, fixtures, utilization equipment
|
ELE10-00317
| ELE-Aging Inspection | 12/22/2014 | 12/23/2014 | 12/22/2014 2:12:42 PM | A | DONE |
|
|
Spoke to homeowner, Hawk, ###-#### said they are new owners, and had no idea of any open permits. I gave all the info I could, and she will talk to her husband and call back about getting final inspection.
|