GCE14-00199
| GCE-Final | 2/10/2015 | 2/10/2015 | 2/10/2015 3:07:56 PM | P | FAIL |
|
|
Heather ###-#### 408.36 (D) Back-Fed Devices. Plug-in-type overcurrent protection devices or plug-in type main lug assemblies that are backfed and used to terminate field-installed ungrounded supply conductors shall be secured in place by an additional fastener that requires other than a pull to release the device from the mounting means on the panel. 422.31 Disconnecting means required for permanently installed appliances 422.31 Disconnecting means shall be provided for all permanently installed appliances 330.30 MC shall be secured within 12 inches of connector 356.30 LFNC shall be secured within 12 inches of connector 406.9 all 15 and 20 amp receptacles in damp or wet location shall be weather resistant type 408.4 Every circuit shall be legibly identified 422.31 Overcurrent rating shall not exceed the device rating marked on the appliance
|
GCE15-00012
| GCE-Final | 2/10/2015 | 2/10/2015 | 2/10/2015 2:08:14 PM | P | PASS |
|
|
Contractor ###-#### Final OK
|
ELE15-00353
| Temporary Service | 2/9/2015 | 2/10/2015 | 2/10/2015 1:45:48 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by TOM BICANDI T/S, U/G, N, OK
|
ELE14-03454
| Final | 2/10/2015 | 2/10/2015 | 2/10/2015 1:34:19 PM | P | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by daniel bibikov called 110.3 B Listed or labeled equipment shall be installed in accordance to instructions. All breaker lockouts fell offf wtih panel cover removal 408.4 Every circuit shall be legibly identified, house panel schedule 210.5C Ungrounded conductors shall be identified, panels of all units 314.20 In walls of combustible material, boxes or extensions shall be flush with finished surfaces, microwave boxes BCC 4.05.26 Trim out inspections, all plates shall be installed
|
ELE15-00337
| Electrical Rough-In | 2/9/2015 | 2/10/2015 | 2/10/2015 12:16:41 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Steve McCloy OK to cover ceiling, all seismic cables are in, contractor to flag them and be available to open up ceiling to allow us to spot check for flagging per NEC 300.11
|
ELE11-02061
| ELE-Aging Inspection | 2/10/2015 | 2/10/2015 | 2/10/2015 11:45:48 AM | | DONE |
|
|
contractor trying to reach homeowner to get access for final
|
ELE14-03266
| Electrical Rough-In | 2/9/2015 | 2/10/2015 | 2/10/2015 11:14:54 AM | A | PASS |
|
|
Wall cover Phone #: ###-#### Inspection requested via web by Chris Chesnut RI OK to cover upstairs and NW room in basement that has the floor boxes and the bathroom, remainder of basement is unfinished wiring.
|
ELE15-00322
| Rough-In Permanent Service | 2/6/2015 | 2/10/2015 | 2/10/2015 10:41:59 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Alan Lusk WUI zone, no soffit inspection performed, check BLD for approval before final. RI OK< P/s, U/G, N, OK
|
ELE14-03439
| Final | 2/10/2015 | 2/10/2015 | 2/10/2015 10:01:07 AM | A | PASS |
|
|
CODE 1234 Phone #: ###-#### Inspection requested via web by Bob Glenn Final OK
|
ELE12-02788
| ELE-Aging Inspection | 2/10/2015 | 2/10/2015 | 2/10/2015 9:32:43 AM | | DONE |
|
|
Posted site 2-10-15, 9:30 am
|
ELE15-00352
| Rough-In Permanent Service | 2/9/2015 | 2/10/2015 | 2/10/2015 9:27:45 AM | A | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by TOM BICANDI 300.4 (1) Bored Holes. In both exposed and concealed locations, where a cable- or raceway-type wiring method is installed through bored holes in joists, rafters, or wood members, holes shall be bored so that the edge of the hole is not less than 32 mm (11/4 in.) from the nearest edge of the wood member. Where this distance cannot be maintained, the cable or raceway shall be protected from penetration by screws or nails by a steel plate(s) or bushing(s), at least 1.6 mm (1/16 in.) thick, and of appropriate length and width installed to cover the area of the wiring. 210.52 B 2 The two or more small appliance branch circuits shall supply no other outlets 210.52 I Foyers 60 square feet or larger shall have receptacles on walls 3 foot or larger 210.8 GFI must be readily accessible called TOM
|