Inspections for the day of: Tuesday, February 10, 2015.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorCevyn Recla
TitleELE-INSPECTOR
Phone #985-3493
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
GCE14-00199 GCE-Final2/10/20152/10/20152/10/2015 3:07:56 PMPFAIL
Heather ###-####
408.36 (D) Back-Fed Devices. Plug-in-type overcurrent protection
devices or plug-in type main lug assemblies that are
backfed and used to terminate field-installed ungrounded
supply conductors shall be secured in place by an additional
fastener that requires other than a pull to release the
device from the mounting means on the panel.
422.31 Disconnecting means required for permanently installed appliances
422.31 Disconnecting means shall be provided for all permanently installed appliances
330.30 MC shall be secured within 12 inches of connector
356.30 LFNC shall be secured within 12 inches of connector
406.9 all 15 and 20 amp receptacles in damp or wet location shall be weather resistant type
408.4 Every circuit shall be legibly identified
422.31 Overcurrent rating shall not exceed the device rating marked on the appliance
GCE15-00012 GCE-Final2/10/20152/10/20152/10/2015 2:08:14 PMPPASS
Contractor ###-####
Final OK
ELE15-00353 Temporary Service2/9/20152/10/20152/10/2015 1:45:48 PMPPASS
Phone #: ###-#### Inspection requested via web by TOM BICANDI
T/S, U/G, N, OK
ELE14-03454 Final2/10/20152/10/20152/10/2015 1:34:19 PMPFAIL
Phone #: ###-#### Inspection requested via web by daniel bibikov
called
110.3 B Listed or labeled equipment shall be installed in accordance to instructions. All breaker lockouts fell offf wtih panel cover removal
408.4 Every circuit shall be legibly identified, house panel schedule
210.5C Ungrounded conductors shall be identified, panels of all units
314.20 In walls of combustible material, boxes or extensions shall be flush with finished surfaces, microwave boxes
BCC 4.05.26 Trim out inspections, all plates shall be installed
ELE15-00337 Electrical Rough-In2/9/20152/10/20152/10/2015 12:16:41 PMPPASS
Phone #: ###-#### Inspection requested via web by Steve McCloy
OK to cover ceiling, all seismic cables are in, contractor to flag them and be available to open up ceiling to allow us to spot check for flagging per NEC 300.11
ELE11-02061 ELE-Aging Inspection2/10/20152/10/20152/10/2015 11:45:48 AM DONE
contractor trying to reach homeowner to get access for final
ELE14-03266 Electrical Rough-In2/9/20152/10/20152/10/2015 11:14:54 AMAPASS
Wall cover Phone #: ###-#### Inspection requested via web by Chris Chesnut
RI OK to cover upstairs and NW room in basement that has the floor boxes and the bathroom, remainder of basement is unfinished wiring.
ELE15-00322 Rough-In Permanent Service2/6/20152/10/20152/10/2015 10:41:59 AMAPASS
Phone #: ###-#### Inspection requested via web by Alan Lusk
WUI zone, no soffit inspection performed, check BLD for approval before final. RI OK< P/s, U/G, N, OK
ELE14-03439 Final2/10/20152/10/20152/10/2015 10:01:07 AMAPASS
CODE 1234 Phone #: ###-#### Inspection requested via web by Bob Glenn
Final OK
ELE12-02788 ELE-Aging Inspection2/10/20152/10/20152/10/2015 9:32:43 AM DONE
Posted site 2-10-15, 9:30 am
ELE15-00352 Rough-In Permanent Service2/9/20152/10/20152/10/2015 9:27:45 AMAFAIL
Phone #: ###-#### Inspection requested via web by TOM BICANDI
300.4 (1) Bored Holes. In both exposed and concealed locations,
where a cable- or raceway-type wiring method is installed
through bored holes in joists, rafters, or wood members,
holes shall be bored so that the edge of the hole is not less
than 32 mm (11/4 in.) from the nearest edge of the wood
member. Where this distance cannot be maintained, the
cable or raceway shall be protected from penetration by
screws or nails by a steel plate(s) or bushing(s), at least
1.6 mm (1/16 in.) thick, and of appropriate length and width
installed to cover the area of the wiring.
210.52 B 2 The two or more small appliance branch circuits shall supply no other outlets
210.52 I Foyers 60 square feet or larger shall have receptacles on walls 3 foot or larger
210.8 GFI must be readily accessible
called TOM