Inspections for the day of: Tuesday, January 19, 2016.
Number of inspections: 15
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorEric Story
TitleELE-INSPECTOR
Phone #985-3493
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE15-04134 Electrical Rough-In1/18/20161/19/20161/19/2016 3:06:39 PMPPASS
Call George before hand at ###-#### Phone #: ###-#### Inspection requested via web by Shannon Wall verfied ul listing and disc. also scope of work
ELE16-00055 Electrical Rough-In1/19/20161/19/20161/19/2016 2:47:49 PMPFAIL
Call George before hand so he can meet you on the job site. ###-#### Phone #: ###-#### Inspection requested via web by Shannon building permit not payed
ELE15-03403 Final1/19/20161/19/20161/19/2016 2:36:07 PMPCANC
If possible make it the last inspection of the day, they would like a final and we have a few more things to wrap up thank you Phone #: ###-#### Inspection requested via web by Brad Baker contractor not ready
ELE16-00168 Electrical Rough-In1/19/20161/19/20161/19/2016 1:16:38 PMPPASS
Inspection requested via web by Larry Richardson master closet ok cover
ELE16-00148 Electrical Rough-In1/18/20161/19/20161/19/2016 12:55:14 PMPPASS
Unable to install meter base, will schedule service inspection on a later date. Thank You Phone #: ###-#### Inspection requested via web by Robert Schroder contrator will call for service inspection on a later date rough-in ok cover
ELE15-01131 Final1/19/20161/19/20161/19/2016 12:38:54 PMPPASS
Final for exterior and garage. Please call Eric @ ###-#### to schedule entrance to site. Thank You Phone #: ###-#### Inspection requested via web by Eric Brown exterior final ok
ELE15-03640 Final1/19/20161/19/20161/19/2016 12:18:30 PMPPASS
Please call ahead for access - Will Phone #: ###-#### panel wall ok cover
ELE15-02860 Final1/18/20161/19/20161/19/2016 12:18:18 PMPFAIL
Inspection requested via web by Lynn Solmon 210.8(5) unfinished basements shall have GFCI protection 406.6 cover plates required 314.22 extension required for light in mechanical room
ELE14-01817 Final1/14/20161/19/20161/19/2016 11:18:51 AMAPASS
Phone #: ###-#### Inspection requested via web by Kendra Lanham master bath final ok
ELE16-00065 Final1/15/20161/19/20161/19/2016 11:05:08 AMAPASS
call for access; Eric Phone #: ###-#### final ok
ELE16-00149 Electrical Rough-In1/19/20161/19/20161/19/2016 10:36:33 AMAPASS
Mother-in-law quarters in the back Phone #: ###-#### Inspection requested via web by Greg Idsinga mother in law quarters ok cover
ELE16-00141 Electrical Rough-In1/15/20161/19/20161/19/2016 10:09:24 AMAFAIL
Tom// please call before Phone #: ###-#### 210.52 (g) branch circuit suppling garages shall not supply any outside receptacles
ELE16-00161 Rough-In Permanent Service1/19/20161/19/20161/19/2016 9:43:01 AMAPASS
Phone #: ###-#### Inspection requested via web by TOM BICANDI rough-in ok cover p/s u/g n ok
ELE16-00136 Rough-In Permanent Service1/18/20161/19/20161/19/2016 9:19:39 AMAPASS
Phone #: ###-#### Inspection requested via web by daniel bibikov rough-in ok cover p/s u/g n ok 4-meters
ELE15-03590 Final1/18/20161/19/20161/19/2016 9:19:01 AMAFAIL
Phone #: ###-#### Inspection requested via web by daniel bibikov 408.4 field indentififcation required (house panel) 200.11Polarity of connections (kitchen GFCI) unit 201/ arc fault breaker shall be firmly mounted unit 201