Inspections for the day of: Tuesday, October 27, 2015.
Number of inspections: 17
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorEric Story
TitleELE-INSPECTOR
Phone #985-3493
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE15-03408 Rough-In Permanent Service10/27/201510/27/201510/27/2015 3:11:50 PMPPASS
Phone #: ###-#### Inspection requested via web by Bob Glenn rough-in ok cover p/s o/h n ok
ELE15-03467 Electrical Rough-In10/27/201510/27/201510/27/2015 2:58:30 PMPPASS
underground from house to detached garage ok cover
ELE15-03467 Conference10/27/201510/27/201510/27/2015 2:55:24 PMPCANC
Call Troy Ground Works inpsection Phone #: ###-#### Inspection requested via web by Don Conley needed rough-in
ELE15-03445 Conference10/26/201510/27/201510/27/2015 2:00:35 PMPCANC
Linda-please call to meet Phone #: ###-####
ELE15-02739 Electrical Rough-In10/26/201510/27/201510/27/2015 1:38:57 PMPFAIL
Al Phone #: ###-#### 210.11 down bathroom shall have a dedicated 20amp circuit
ELE15-02397 Final10/27/201510/27/201510/27/2015 1:07:11 PMPFAIL
Phone #: ###-#### Inspection requested via web by Darryn CoburnOCPD shall be at manufactorers specification 250.94 (1) intersystem bond missing 352.30(a) riser support missing
ELE15-02396 Final10/27/201510/27/201510/27/2015 1:05:34 PMPPASS
Phone #: ###-#### Inspection requested via web by Darryn Coburn final ok
ELE15-03432 Electrical Rough-In10/26/201510/27/201510/27/2015 11:52:38 AMAPASS
Contact is Derek Ball Phone #: ###-#### Inspection requested via web by Scott Campbell pathway lighting parrell to 1161 building ok cover
ELE14-03084 Permanent Service10/26/201510/27/201510/27/2015 11:28:54 AMAFAIL
Service only Phone #: ###-#### Inspection requested via web by mike brown 250.50 grounding electrode required for main breaker and discconects
ELE15-03463 Rough-In Permanent Service10/27/201510/27/201510/27/2015 11:20:59 AMPFAIL
Phone #: ###-#### Inspection requested via web by TOM BICANDI 334.12 type nm cable shall be protected from physical damage
ELE15-02771 Conference10/27/201510/27/201510/27/2015 10:21:08 AMPDONE
EQ bonding plane wiring. Please call 1/2 hr ahead, need to meet on site and discuss eq wire placement. Phone #: ###-#### Inspection requested via web by Lars Johnson discussed bonding for pool and surrounding walls
ELE15-02771 Electrical Rough-In10/26/201510/27/201510/27/2015 10:20:18 AMACANC
EQ bonding plane wiring. Please call 1/2 hr ahead, need to meet on site and discuss eq wire placement. Phone #: ###-#### Inspection requested via web by Lars Johnson needed conference
ELE15-03458 Rough-In Permanent Service10/27/201510/27/201510/27/2015 9:29:48 AMAPASS
Phone #: ###-#### Inspection requested via web by Alan Lusk rough-in ok cover/s u/g n ok
ELE15-03459 Temporary Service10/27/201510/27/201510/27/2015 9:16:07 AMAPASS
Phone #: ###-#### Inspection requested via web by Alan Lusk t/s u/g n ok
ELE15-03307 Temporary Service10/27/201510/27/201510/27/2015 9:04:08 AMAPASS
Phone #: ###-#### Inspection requested via web by Alan Lusk t/s u/g n ok
ELE15-03460 Temporary Service10/27/201510/27/201510/27/2015 8:58:22 AMAPASS
Phone #: ###-#### Inspection requested via web by Alan Lusk t/s u/g n ok
ELE15-03432 Electrical Rough-In10/23/201510/27/201510/26/2015 2:27:23 PMPCANC
Contact is Derek Ball - conduit rough-in inspection Phone #: ###-#### >> Inspection requested via web by Scott Campbell Inspection cancelled from web by: Scott Campbell