Inspections for the day of: Thursday, February 13, 2020.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorEric Story
TitleELE-INSPECTOR
Phone #985-3493
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE19-04936 Final2/13/20202/13/20202/13/2020 2:34:41 PMPPASS
Contact: Rob Lawrence Phone #: ###-#### Inspection requested via web by Deb Gooden
Final ok
ELE19-04029 Final2/13/20202/13/20202/13/2020 2:11:46 PMPPASS
Please call 1/2 hour in advance so I can let you in and show you what we did, thank you... Phone #: ###-#### Inspection requested via web by Rick Beckman
Final ok
ELE19-04029 Rough-In Permanent Service2/13/20202/13/20202/13/2020 2:11:28 PMPCANC
Please call 1/2 hour in advance so I can let you in and show you what we did, thank you... Phone #: ###-#### Inspection requested via web by Rick Beckman
ELE20-00523 Permanent Service2/13/20202/13/20202/13/2020 2:09:20 PMPPASS
Wanting the service inspected for re hook up to idaho power any questions call Dan with Steelhead electric 2087898844 thanks Phone #: ###-#### Inspection requested via web by Daniel moonen
Contractor aware of usuage of split bus panel
p/s o/h rec ok
ELE19-03946 Final2/12/20202/13/20202/13/2020 11:11:38 AMAPASS
Contact: Rob Lawrence.... close out permit, project completed and inspected in November Phone #: ###-#### Inspection requested via web by Deb Gooden
Final ok
ELE17-04060 Final2/12/20202/13/20202/13/2020 11:11:18 AMAPASS
Justin Metcalf ###-#### Phone #: ###-#### Inspection requested via web by Samatha Solberg
Final ok
ELE20-00525 Electrical Rough-In2/12/20202/13/20202/13/2020 10:07:32 AMAPASS
underground and bonding Phone #: ###-#### Inspection requested via web by Ryan Wake
U/G and bond to equipment ok to cover/4 corners stbbed and cover done(No EQ bond intalled at this time)
ELE19-04657 Final2/12/20202/13/20202/13/2020 9:51:24 AMAFAIL
Justin ###-#### Phone #: ###-#### Inspection requested via web by Samatha Solberg
1) Tamper resistant receptacles required in shop
2) WR needed for outdoor recept
3) service recept required for mini split unit
4) GFCI trips free in shed
ELE19-04620 Final2/11/20202/13/20202/13/2020 9:27:45 AMAPASS
Please call ahead with a time frame. Phone #: ###-#### Inspection requested via web by BRS Permitting
Final ok