ELE19-00108
| Final | 2/6/2020 | 2/6/2020 | 2/6/2020 2:08:15 PM | P | PASS |
|
|
Inspection outside building for final Phone #: ###-#### Inspection requested via web by Tom Betty Occ card signed-Final ok
|
ELE19-01628
| Final | 2/5/2020 | 2/6/2020 | 2/6/2020 1:38:42 PM | A | CANC |
|
|
This request is for a final inspection for the 4th floor. Will be open, thank you! Phone #: ###-#### Inspection requested via web by Darryn Coburn No final at this time
|
ELE19-01628
| Electrical Rough-In | 2/6/2020 | 2/6/2020 | 2/6/2020 1:38:34 PM | P | PASS |
|
|
This request is for a final inspection for the 4th floor. Will be open, thank you! Phone #: ###-#### Inspection requested via web by Darryn Coburn 4th floor hot checked-no furniture allowed as stated in a fowarded e-mail from fire marshall until fire supression system in operational
|
ELE20-00420
| Final | 2/5/2020 | 2/6/2020 | 2/6/2020 12:28:56 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by danny perrine Service final only ok
|
ELE19-03767
| Final | 2/6/2020 | 2/6/2020 | 2/6/2020 12:09:30 PM | P | PASS |
|
|
Porter corte final Phone #: ###-#### Inspection requested via web by Ryan Wake Final ok
|
ELE19-04889
| Rough-In Permanent Service | 2/5/2020 | 2/6/2020 | 2/6/2020 10:56:15 AM | A | CANC |
|
|
around 11am if possible Phone #: ###-#### Inspection requested via web by Lee VanSchoiack
|
ELE19-04889
| Permanent Service | 2/6/2020 | 2/6/2020 | 2/6/2020 10:55:28 AM | P | FAIL |
|
|
around 11am if possible Phone #: ###-#### Inspection requested via web by Lee VanSchoiack Rating posted on prints states 34,000 and breakers are rated at 22K, replace with larger sized frame of breaker
|
ELE19-04889
| Electrical Rough-In | 2/6/2020 | 2/6/2020 | 2/6/2020 10:54:10 AM | P | PASS |
|
|
around 11am if possible Phone #: ###-#### Inspection requested via web by Lee VanSchoiack Rough-in ok to cover
|
ELE20-00435
| Electrical Rough-In | 2/5/2020 | 2/6/2020 | 2/6/2020 10:33:30 AM | A | PASS |
|
|
Need ok to cover holes we made to fish in the circuits to the 2 bottom units #3 and #4. Lock box is on #4 door. Call Jimmy for the code and questions. ###-####. Mini split units going in the living room of each unit. Phone #: ###-#### Inspection requested via web by Robert Schroder areas were fished are ok to cover-baths are needed to looked at at another date
|
ELE19-03490
| Final | 2/5/2020 | 2/6/2020 | 2/6/2020 10:21:55 AM | A | CANC |
|
|
Please call Hannah ###-#### on your way. If you have any questions please feel free to contact Andrew ###-####. Thanks!! Phone #: ###-#### Inspection requested via web by Clayton Morgan Nobody home-called number given and no answer
|
ELE20-00420
| Final | 2/5/2020 | 2/6/2020 | 2/5/2020 4:43:30 PM | A | CANC |
|
|
Service change Phone #: ###-#### >> Inspection requested via web by danny perrine Inspection cancelled from web by: danny perrine
|