Inspections for the day of: Thursday, February 6, 2020.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorEric Story
TitleELE-INSPECTOR
Phone #985-3493
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE19-00108 Final2/6/20202/6/20202/6/2020 2:08:15 PMPPASS
Inspection outside building for final Phone #: ###-#### Inspection requested via web by Tom Betty
Occ card signed-Final ok
ELE19-01628 Final2/5/20202/6/20202/6/2020 1:38:42 PMACANC
This request is for a final inspection for the 4th floor. Will be open, thank you! Phone #: ###-#### Inspection requested via web by Darryn Coburn
No final at this time
ELE19-01628 Electrical Rough-In2/6/20202/6/20202/6/2020 1:38:34 PMPPASS
This request is for a final inspection for the 4th floor. Will be open, thank you! Phone #: ###-#### Inspection requested via web by Darryn Coburn
4th floor hot checked-no furniture allowed as stated in a fowarded e-mail from fire marshall until fire supression system in operational
ELE20-00420 Final2/5/20202/6/20202/6/2020 12:28:56 PMPPASS
Phone #: ###-#### Inspection requested via web by danny perrine
Service final only ok
ELE19-03767 Final2/6/20202/6/20202/6/2020 12:09:30 PMPPASS
Porter corte final Phone #: ###-#### Inspection requested via web by Ryan Wake
Final ok
ELE19-04889 Rough-In Permanent Service2/5/20202/6/20202/6/2020 10:56:15 AMACANC
around 11am if possible Phone #: ###-#### Inspection requested via web by Lee VanSchoiack
ELE19-04889 Permanent Service2/6/20202/6/20202/6/2020 10:55:28 AMPFAIL
around 11am if possible Phone #: ###-#### Inspection requested via web by Lee VanSchoiack
Rating posted on prints states 34,000 and breakers are rated at 22K, replace with larger sized frame of breaker
ELE19-04889 Electrical Rough-In2/6/20202/6/20202/6/2020 10:54:10 AMPPASS
around 11am if possible Phone #: ###-#### Inspection requested via web by Lee VanSchoiack
Rough-in ok to cover
ELE20-00435 Electrical Rough-In2/5/20202/6/20202/6/2020 10:33:30 AMAPASS
Need ok to cover holes we made to fish in the circuits to the 2 bottom units #3 and #4. Lock box is on #4 door. Call Jimmy for the code and questions. ###-####. Mini split units going in the living room of each unit. Phone #: ###-#### Inspection requested via web by Robert Schroder
areas were fished are ok to cover-baths are needed to looked at at another date
ELE19-03490 Final2/5/20202/6/20202/6/2020 10:21:55 AMACANC
Please call Hannah ###-#### on your way. If you have any questions please feel free to contact Andrew ###-####. Thanks!! Phone #: ###-#### Inspection requested via web by Clayton Morgan
Nobody home-called number given and no answer
ELE20-00420 Final2/5/20202/6/20202/5/2020 4:43:30 PMACANC
Service change Phone #: ###-#### >> Inspection requested via web by danny perrine Inspection cancelled from web by: danny perrine