Inspections for the day of: Tuesday, March 15, 2016.
Number of inspections: 16
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorEric Story
TitleELE-INSPECTOR
Phone #985-3493
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE12-02788 ELE-Aging Inspection3/15/20163/15/20163/17/2016 11:39:54 AM CANC
too busy
ELE16-00829 Electrical Rough-In3/15/20163/15/20163/15/2016 2:58:06 PMPPASS
Keith Phone #: ###-#### interior wall ok cover
ELE16-00575 Permanent Service3/15/20163/15/20163/15/2016 2:18:39 PMPFAIL
Phone #: ###-#### Inspection requested via web by steve ragan 110.24 available fault current calculation required before service can be energized 250.50 grounding electrode system required
ELE15-03423 Permanent Service3/15/20163/15/20163/15/2016 2:16:53 PMPFAIL
Service inspection for HOA owned meter cabinet Phone #: ###-#### Inspection requested via web by steve ragan 110.24 available fault current calculation required before service can be energized
ELE16-00804 Rough-In Permanent Service3/14/20163/15/20163/15/2016 1:32:41 PMPPASS
Phone #: ###-#### Inspection requested via web by Alan Lusk rough-in ok cover p/s u/g n ok
ELE16-00683 Conference3/14/20163/15/20163/15/2016 12:59:33 PMPDONE
Aaron// please call before Phone #: ###-#### discussed wiring methods and code requierments for addition to bedrooms in basement and living room
ELE16-00442 Electrical Rough-In3/15/20163/15/20163/15/2016 12:08:10 PMPPASS
Jake//underground Phone #: ###-#### east side first floor underground ok cover
ELE16-00817 Permanent Service3/14/20163/15/20163/15/2016 11:29:19 AMAPASS
I need to heat up the service for temporary Phone #: ###-#### Inspection requested via web by Greg Idsinga p/s o/h rec ok
ELE12-03055 ELE-Aging Inspection3/15/20163/15/20163/15/2016 11:28:06 AM PASS
still under construction
ELE15-02689 Final3/14/20163/15/20163/15/2016 10:44:58 AMAPASS
Cory Phone #: ###-#### sign final ok
ELE15-03896 Electrical Rough-In3/14/20163/15/20163/15/2016 10:44:49 AMAPASS
Phone #: ###-#### Inspection requested via web by Thomas Jenkins cieling in entry only ok cover
ELE16-00784 Electrical Rough-In3/15/20163/15/20163/15/2016 10:04:17 AMAFAIL
This inspection is for detached garage only. Thank You Phone #: ###-#### Inspection requested via web by Eric Brown 250.32(b)(1) equipment grounding conductor shall not connected to grounded conductor in a seperate structure when fed by a branch circuit
ELE16-00784 Electrical Rough-In3/15/20163/15/20163/15/2016 10:03:51 AMPPASS
This inspection is for detached garage only. Thank You Phone #: ###-#### Inspection requested via web by Eric Brown detached garage ok cover
ELE15-03443 Electrical Rough-In3/14/20163/15/20163/15/2016 9:30:54 AMAPASS
Christina Phone #: ###-#### master bed/bath/hall/and laundry room ok cover
ELE16-00803 Rough-In Permanent Service3/14/20163/15/20163/15/2016 9:00:17 AMAPASS
Any questions please let me know, thx, TW. Phone #: ###-#### Inspection requested via web by Stephen Kren rough-in ok cover p/s u/g n ok
ELE16-00818 Rough-In Permanent Service3/14/20163/15/20163/15/2016 8:59:18 AMAPASS
rough and service Phone #: ###-#### Inspection requested via web by Rowdy Monroe rough-in ok cover p/s u/g n ok