ELE12-02788
| ELE-Aging Inspection | 3/15/2016 | 3/15/2016 | 3/17/2016 11:39:54 AM | | CANC |
|
|
too busy
|
ELE16-00829
| Electrical Rough-In | 3/15/2016 | 3/15/2016 | 3/15/2016 2:58:06 PM | P | PASS |
|
|
Keith Phone #: ###-#### interior wall ok cover
|
ELE16-00575
| Permanent Service | 3/15/2016 | 3/15/2016 | 3/15/2016 2:18:39 PM | P | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by steve ragan 110.24 available fault current calculation required before service can be energized 250.50 grounding electrode system required
|
ELE15-03423
| Permanent Service | 3/15/2016 | 3/15/2016 | 3/15/2016 2:16:53 PM | P | FAIL |
|
|
Service inspection for HOA owned meter cabinet Phone #: ###-#### Inspection requested via web by steve ragan 110.24 available fault current calculation required before service can be energized
|
ELE16-00804
| Rough-In Permanent Service | 3/14/2016 | 3/15/2016 | 3/15/2016 1:32:41 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Alan Lusk rough-in ok cover p/s u/g n ok
|
ELE16-00683
| Conference | 3/14/2016 | 3/15/2016 | 3/15/2016 12:59:33 PM | P | DONE |
|
|
Aaron// please call before Phone #: ###-#### discussed wiring methods and code requierments for addition to bedrooms in basement and living room
|
ELE16-00442
| Electrical Rough-In | 3/15/2016 | 3/15/2016 | 3/15/2016 12:08:10 PM | P | PASS |
|
|
Jake//underground Phone #: ###-#### east side first floor underground ok cover
|
ELE16-00817
| Permanent Service | 3/14/2016 | 3/15/2016 | 3/15/2016 11:29:19 AM | A | PASS |
|
|
I need to heat up the service for temporary Phone #: ###-#### Inspection requested via web by Greg Idsinga p/s o/h rec ok
|
ELE12-03055
| ELE-Aging Inspection | 3/15/2016 | 3/15/2016 | 3/15/2016 11:28:06 AM | | PASS |
|
|
still under construction
|
ELE15-02689
| Final | 3/14/2016 | 3/15/2016 | 3/15/2016 10:44:58 AM | A | PASS |
|
|
Cory Phone #: ###-#### sign final ok
|
ELE15-03896
| Electrical Rough-In | 3/14/2016 | 3/15/2016 | 3/15/2016 10:44:49 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Thomas Jenkins cieling in entry only ok cover
|
ELE16-00784
| Electrical Rough-In | 3/15/2016 | 3/15/2016 | 3/15/2016 10:04:17 AM | A | FAIL |
|
|
This inspection is for detached garage only. Thank You Phone #: ###-#### Inspection requested via web by Eric Brown 250.32(b)(1) equipment grounding conductor shall not connected to grounded conductor in a seperate structure when fed by a branch circuit
|
ELE16-00784
| Electrical Rough-In | 3/15/2016 | 3/15/2016 | 3/15/2016 10:03:51 AM | P | PASS |
|
|
This inspection is for detached garage only. Thank You Phone #: ###-#### Inspection requested via web by Eric Brown detached garage ok cover
|
ELE15-03443
| Electrical Rough-In | 3/14/2016 | 3/15/2016 | 3/15/2016 9:30:54 AM | A | PASS |
|
|
Christina Phone #: ###-#### master bed/bath/hall/and laundry room ok cover
|
ELE16-00803
| Rough-In Permanent Service | 3/14/2016 | 3/15/2016 | 3/15/2016 9:00:17 AM | A | PASS |
|
|
Any questions please let me know, thx, TW. Phone #: ###-#### Inspection requested via web by Stephen Kren rough-in ok cover p/s u/g n ok
|
ELE16-00818
| Rough-In Permanent Service | 3/14/2016 | 3/15/2016 | 3/15/2016 8:59:18 AM | A | PASS |
|
|
rough and service Phone #: ###-#### Inspection requested via web by Rowdy Monroe rough-in ok cover p/s u/g n ok
|