Inspections for the day of: Thursday, March 17, 2016.
Number of inspections: 17
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorEric Story
TitleELE-INSPECTOR
Phone #985-3493
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE16-00125 Final3/17/20163/17/20163/17/2016 2:04:16 PMPPASS
Phone #: ###-#### Inspection requested via web by Shane Dale final ok
ELE16-00857 Conference3/17/20163/17/20163/17/2016 2:03:06 PMPDONE
Phone #: ###-#### Inspection requested via web by Don Conley discussed service and supporting over head mast
ELE16-00784 Permanent Service3/17/20163/17/20163/17/2016 1:46:26 PMPCANC
Neutrals and grounds are separated. Thank You! Phone #: ###-#### Inspection requested via web by Eric Brown needed rough-in
ELE16-00784 Electrical Rough-In3/17/20163/17/20163/17/2016 1:46:04 PMPPASS
Neutrals and grounds are separated. Thank You! Phone #: ###-#### Inspection requested via web by Eric Brown correction fixed for grounds and neutrals bonded together
ELE16-00809 Electrical Rough-In3/17/20163/17/20163/17/2016 1:26:31 PMPPASS
Walls Phone #: ###-#### Inspection requested via web by Kevin Burke offices walls and cielings ok cover
ELE16-00809 Permanent Service3/17/20163/17/20163/17/2016 1:26:15 PMPFAIL
Walls Phone #: ###-#### Inspection requested via web by Kevin Burke 110.24 avaliable fault current calculation required 250.53 grounding electrode system required 250.50 shall bond and ground as per 250.53
ELE12-00588 ELE-Aging Inspection3/17/20163/17/20163/17/2016 11:38:43 AM CANC
too busy
ELE13-01051 ELE-Aging Inspection3/17/20163/17/20163/17/2016 11:37:54 AM CANC
too busy
ELE13-01450 ELE-Aging Inspection3/17/20163/17/20163/17/2016 11:37:21 AM CANC
too busy
ELE13-00238 ELE-Aging Inspection3/17/20163/17/20163/17/2016 11:37:00 AM CANC
too busy
ELE15-03985 Final3/16/20163/17/20163/17/2016 11:09:21 AMAPASS
would like call ahead; Mike Phone #: ###-#### final ok
ELE15-03755 Final3/17/20163/17/20163/17/2016 10:06:36 AMPCANC
Need final this morning if possible Phone #: ###-#### Inspection requested via web by Kendra Lanham not ready at this time
ELE16-00835 Final3/16/20163/17/20163/17/2016 9:41:23 AMACANC
Brandon Phone #: ###-#### needed p/s
ELE16-00835 Permanent Service3/17/20163/17/20163/17/2016 9:40:58 AMPPASS
Brandon Phone #: ###-#### p/s u/g n ok
ELE16-00843 Temporary Service3/16/20163/17/20163/17/2016 9:29:31 AMAPASS
Phone #: ###-#### Inspection requested via web by Alan Lusk t/s u/g n ok
ELE16-00854 Temporary Service3/16/20163/17/20163/17/2016 9:12:33 AMAFAIL
Phone #: ###-#### Inspection requested via web by Emmet Bushman 406.6 faceplates required
ELE16-00853 Temporary Service3/16/20163/17/20163/17/2016 9:11:41 AMAFAIL
Phone #: ###-#### Inspection requested via web by Emmet Bushman 590.6 GFCI protection required for all temporary receptacles