Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE17-00129 Final3/20/20173/20/20173/20/2017 1:31:46 PMPFAIL
House in back of main home. Phone #: ###-#### Inspection requested via web by Greg Idsinga
210.8 Receptalces located within 6' of a sink shall have GFCI protection
110.25 lockout needed fro water heater or disc
344.30 RMC shall have support within 3' of panel
110.30 fix both w/p's
ELE17-00731 Electrical Rough-In3/20/20173/20/20173/20/2017 12:58:52 PMPPASS
Need wall and ceiling rough-in cover Phone #: ###-#### Inspection requested via web by Brad Girard
Reception desk wall and back office wall and ceilings ok cover
ELE16-02546 Final3/17/20173/20/20173/20/2017 10:47:23 AMPPASS
James Phone #: ###-####
Final ok
ELE09-01607 ELE-Aging Inspection3/20/20173/20/20173/20/2017 10:40:24 AM DONE
Too busy
ELE13-02192 ELE-Aging Inspection3/20/20173/20/20173/20/2017 10:40:12 AM DONE
Too busy
ELE16-02693 Electrical Rough-In3/20/20173/20/20173/20/2017 10:23:23 AMAPASS
Call Rafael for ceiling grid inspection of the concourse level. As close to 10:00am as possible. Phone #: ###-#### Inspection requested via web by Rafael Castillo
Ceilings in corridor as noted and underground for tying in existing branch circuits also ok cover
ELE16-02546 Final3/17/20173/20/20173/20/2017 9:12:44 AMAPASS
James Phone #: ###-####
Correction fixed final ok
ELE16-01529 Final3/19/20173/20/20173/20/2017 9:01:36 AMAFAIL
Phone #: ###-#### Inspection requested via web by Nathan Taylor
110.21 Open ground on quad upstairs
110.25 Lockout required for dishwasher
210.12 AFCI protection required for all beds
406.12 Up bath needs tamper resistant
406.4 All exterior receptacles shall be weather resistant type
ELE17-00852 Electrical Rough-In3/20/20173/20/20173/20/2017 12:00:00 AMAPASS
** copied from ELE16-02693 **
Call Rafael for ceiling grid inspection of the concourse level. As close to 10:00am as possible. Phone #: ###-#### Inspection requested via web by Rafael Castillo
Ceilings in corridor as noted and underground for tying in existing branch circuits also ok cover