ELE17-00129
| Final | 3/20/2017 | 3/20/2017 | 3/20/2017 1:31:46 PM | P | FAIL |
|
|
House in back of main home. Phone #: ###-#### Inspection requested via web by Greg Idsinga 210.8 Receptalces located within 6' of a sink shall have GFCI protection 110.25 lockout needed fro water heater or disc 344.30 RMC shall have support within 3' of panel 110.30 fix both w/p's
|
ELE17-00731
| Electrical Rough-In | 3/20/2017 | 3/20/2017 | 3/20/2017 12:58:52 PM | P | PASS |
|
|
Need wall and ceiling rough-in cover Phone #: ###-#### Inspection requested via web by Brad Girard Reception desk wall and back office wall and ceilings ok cover
|
ELE16-02546
| Final | 3/17/2017 | 3/20/2017 | 3/20/2017 10:47:23 AM | P | PASS |
|
|
James Phone #: ###-#### Final ok
|
ELE09-01607
| ELE-Aging Inspection | 3/20/2017 | 3/20/2017 | 3/20/2017 10:40:24 AM | | DONE |
|
|
Too busy
|
ELE13-02192
| ELE-Aging Inspection | 3/20/2017 | 3/20/2017 | 3/20/2017 10:40:12 AM | | DONE |
|
|
Too busy
|
ELE16-02693
| Electrical Rough-In | 3/20/2017 | 3/20/2017 | 3/20/2017 10:23:23 AM | A | PASS |
|
|
Call Rafael for ceiling grid inspection of the concourse level. As close to 10:00am as possible. Phone #: ###-#### Inspection requested via web by Rafael Castillo Ceilings in corridor as noted and underground for tying in existing branch circuits also ok cover
|
ELE16-02546
| Final | 3/17/2017 | 3/20/2017 | 3/20/2017 9:12:44 AM | A | PASS |
|
|
James Phone #: ###-#### Correction fixed final ok
|
ELE16-01529
| Final | 3/19/2017 | 3/20/2017 | 3/20/2017 9:01:36 AM | A | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Nathan Taylor 110.21 Open ground on quad upstairs 110.25 Lockout required for dishwasher 210.12 AFCI protection required for all beds 406.12 Up bath needs tamper resistant 406.4 All exterior receptacles shall be weather resistant type
|
ELE17-00852
| Electrical Rough-In | 3/20/2017 | 3/20/2017 | 3/20/2017 12:00:00 AM | A | PASS |
|
|
** copied from ELE16-02693 **
Call Rafael for ceiling grid inspection of the concourse level. As close to 10:00am as possible. Phone #: ###-#### Inspection requested via web by Rafael Castillo Ceilings in corridor as noted and underground for tying in existing branch circuits also ok cover
|