Inspections for the day of: Thursday, April 20, 2017.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorEric Story
TitleELE-INSPECTOR
Phone #985-3493
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE12-01987 ELE-Aging Inspection4/20/20174/20/20174/27/2017 9:16:30 AM PASS
Talked with homeowner and will get to work on this when he gets a chance, will call for another conference.
ELE13-00519 ELE-Aging Inspection4/20/20174/20/20174/27/2017 9:11:08 AM DONE
Number given is disconnected
ELE17-00531 Electrical Rough-In4/20/20174/20/20174/20/2017 1:18:17 PMPPASS
Mike Phone #: ###-####
Far west walls in back office only ok cover
ELE17-00797 Final4/20/20174/20/20174/20/2017 12:33:27 PMPPASS
GFCI protection corrections needed
Corrections fixed final ok
ELE16-02942 Final4/20/20174/20/20174/20/2017 12:14:04 PMPFAIL
Owner not home. Man door at rear of garage is unlocked. Gfci is behind red tool box. Phone #: ###-#### Inspection requested via web by Mark Estep
680.8 All lv wires shall maintain 25' from above from water
Shall remove lights from above hot tub
ELE16-02725 Final4/17/20174/20/20174/20/2017 10:51:20 AMAPASS
Phone #: ###-#### Inspection requested via web by chris burke
Final ok
ELE16-02429 Final4/20/20174/20/20174/20/2017 9:53:18 AMPPASS
Service change final ok
ELE16-02730 Final4/19/20174/20/20174/20/2017 9:29:34 AMACANC
Partial final Phone #: ###-#### Inspection requested via web by Per Eric take out notes and change to Cancel until energy inspection has been received.
ELE17-01066 Electrical Rough-In4/19/20174/20/20174/20/2017 9:04:53 AMAPASS
We had an electrician pull a separate permit to address the issue of power for the kitchen island.
Bathroom addition is on a dedicated 20 amp circuit.
Will provide visual access to wiring in bathroom addition to verify that wiring has been properly secured inside the wall. Phone #: ###-#### Inspection requested via web by Matthew Hansen
Homeowner cut holes in sheetrock to verify support of wires and wire size. Electrician that wired island will need to pull a permit and final it out when job is complete.
Notice no insulation in walls adjacent to garage did warn homeowner it needed it.
ELE17-00797 Final4/19/20174/20/20174/20/2017 8:43:17 AMAFAIL
Final inspection request - Tim Phone #: ###-#### Inspection requested via web by Tim Lawrence
Other then residential dwellings all 120v receptacles in a kitchen shall have GFCI protection and be readly accessible