ELE19-00909
| Final | 5/30/2019 | 5/30/2019 | 5/30/2019 3:00:14 PM | P | PASS |
|
|
access 1027 Phone #: ###-#### Inspection requested via web by David Nelson Occ card signed final ok
|
ELE19-00030
| Electrical Rough-In | 5/29/2019 | 5/30/2019 | 5/30/2019 2:59:48 PM | P | PASS |
|
|
West side of the showroom. On-site contact: Wade Luthy ###-#### Phone #: ###-#### Inspection requested via web by Bryan Atkins West side walls ok to cover
|
ELE19-01981
| Electrical Rough-In | 5/30/2019 | 5/30/2019 | 5/30/2019 1:18:35 PM | P | FAIL |
|
|
Recessed can roughin for cover Phone #: ###-#### Inspection requested via web by Steve Craig 1)Unused openings shall be closed 2) Type MC shall be supported within 6' between runs and 12" of a box 3) main run from building has a big nick in wire and needs replaced
|
ELE19-01980
| Temporary Service | 5/30/2019 | 5/30/2019 | 5/30/2019 12:23:28 PM | P | CANC |
|
|
Temporary power pole Phone #: ###-#### >> Inspection requested via web by David McClellan Inspection cancelled from web by: David McClellan
|
ELE19-01970
| Conference | 5/29/2019 | 5/30/2019 | 5/30/2019 12:15:47 PM | P | CANC |
|
|
Julio please call for access Phone #: ###-#### Inspector 445 scheduled himself for this conference
|
ELE19-01955
| Final | 5/30/2019 | 5/30/2019 | 5/30/2019 12:14:27 PM | A | PASS |
|
|
I will be on site at 9am to open electrical room. The unit is on front porch. Phone #: ###-#### Inspection requested via web by Taras Shulga Final for mini split unit ok
|
ELE19-01889
| Final | 5/29/2019 | 5/30/2019 | 5/30/2019 11:53:10 AM | A | PASS |
|
|
Please call Thomas 20 minutes before arrival and he will meet inspector at the job site Phone #: ###-#### Inspection requested via web by Keith Chetta Final ok
|
ELE19-00747
| Final | 5/29/2019 | 5/30/2019 | 5/30/2019 11:35:20 AM | A | PASS |
|
|
Final on last 3 units for this phase. Units 127, 129, 225. Justin will be available on site for access to units. Phone #: ###-#### Inspection requested via web by Tod Lane Final for phase ok
|
ELE18-04715
| Final | 5/30/2019 | 5/30/2019 | 5/30/2019 10:43:46 AM | A | CANC |
|
|
No final at this time
|
ELE18-04715
| Electrical Rough-In | 5/30/2019 | 5/30/2019 | 5/30/2019 10:43:23 AM | P | PASS |
|
|
Front reception desk and U/G ok to cover Checked first floor rooms with retro fit lighting and conference room are ok(2 rooms on west wing need smoke detectors re-installed) Note* east wing ceiling in hallway needs addressed multiple violations exist and EC has been warned of them and needs fixed in order to cover....
|
ELE19-01775
| Final | 5/29/2019 | 5/30/2019 | 5/30/2019 9:59:31 AM | A | PASS |
|
|
Please call if you need me to be there for the final it will be unlocked and superintendent will be there Phone #: ###-#### Inspection requested via web by TRENT Swaim Occ card signed Final ok
|
ELE18-04715
| Final | 5/29/2019 | 5/30/2019 | 5/30/2019 9:56:43 AM | A | PASS |
|
|
Final for 1st Floor Rms , Conference rm, hallway and ceiling rough in. Phone #: ###-#### Inspection requested via web by Dan Cox Occ card signed Final ok
|
ELE19-00899
| Final | 5/30/2019 | 5/30/2019 | 5/30/2019 9:44:32 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Kevin Burke Final ok
|
ELE19-00587
| Final | 5/30/2019 | 5/30/2019 | 5/30/2019 9:11:14 AM | A | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Lee VanSchoiack *Conduit to J-box of pump has seperated *Label circuit breakers *W/R GFCI required *Conductors #4 and larger shall be required to have a bushing
|