Inspections for the day of: Friday, June 14, 2019.
Number of inspections: 7
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorEric Story
TitleELE-INSPECTOR
Phone #985-3493
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE19-01714 Final6/14/20196/14/20196/14/2019 1:09:34 PMPCANC
Please call John Nate Phone #: ###-#### >> Inspection requested via web by Kevin Perez Inspection cancelled from web by: Jeremy Cloud
ELE19-02068 Permanent Service6/13/20196/14/20196/14/2019 1:01:49 PMAPASS
energize service only, in backyard, gate open Phone #: ###-#### Inspection requested via web by Dale Johnson
P/S O/H REC OK
ELE19-00884 Final6/13/20196/14/20196/14/2019 11:22:55 AMAPASS
Garage access code 5050 enter. Phone #: ###-#### Inspection requested via web by Jason Scott
Final ok
ELE19-00883 Final6/13/20196/14/20196/14/2019 11:22:39 AMAPASS
Garage access code 5050 enter. Phone #: ###-#### Inspection requested via web by Jason Scott
Final ok
ELE19-02143 Rough-In Permanent Service6/13/20196/14/20196/14/2019 11:00:53 AMAPASS
Phone #: ###-#### Inspection requested via web by Emmet Bushman
Rough-in ok to cover
p/s u/g n ok
ELE19-00108 Electrical Rough-In6/14/20196/14/20196/14/2019 10:40:44 AMAPASS
3RD floor hallway , lobby and comm rm. Phone #: ###-#### Inspection requested via web by Tom Betty
3rd floor drop ceilngs in lobby and comm room ok to cover
ELE18-03596 Final6/13/20196/14/20196/14/2019 10:19:49 AMAFAIL
This Is Ready For Final Please Call Me With Any Issues Phone #: ###-#### Inspection requested via web by jason shifflett
Room ID required
210.12 AFCI protection required
410 Luminaires shall not be within 6" of shelving on LED fixtures unless rated
210.8 All receptacles located withn 6' of a sink shall have GFCI protection
Manufact spec required for connectors used on type MC connectors on mini split units.....